| 2007-11-16 18:01:59 | ****CORRECTIONS**** |
| | 3ND COURTESY REVIEW FOR 4TH SUBMITTAL |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | |
| | FROM PREVIOUS LISTS: |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| | PERMIT PICKUP, FS713.13. |
| | |
| | 2.)ADDRESSED. |
| | |
| | 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| | 561-233-5025 FOR MORE INFORMATION. |
| | |
| | 4-55.)ADDRESSED. |
| | |
| | 56.)COMMENTS REGARDING PRODUCT APPROVALS: |
| | |
| | A.SEE PREVIOUS LISTS IN REGARDS TO OVERHEAD DOOR |
| | PRODUCT APPROVALS.THE NOAS SUBMITTED DO NOT COMPLY |
| | WITH DESIGN PRESSURE REQUIREMENTS FOR D1A (SHEET S10, |
| | +56/-73).IT IS COMPLIANT FOR D1 ONLY (+56/-61). |
| | |
| | B.SUBMIT PRODUCT APPROVALS FOR THE FLEMING DOOR.THE |
| | PRODUCT APPEARS TO MEET DESIGN PRESSURE REQUIREMENT OF |
| | +56/-61, BUT PRODUCT APPROVALS WERE NOT SUBMITTED, ONLY |
| | SHOP DRAWINGS.THE COVER SHEET REFERS TO THREE |
| | DIFFERENT NOAS.ONLY ONE STEEL DOOR IS BEING |
| | INSTALLED.PROVIDE THE FLORIDA STATE PRODUCT APPROVAL |
| | (IF AVAILABLE) AND A CURRENT NOA FOR THIS PRODUCT. |
| | REFERRING TO THE NOA NUMBER IS NOT SUFFICE AS THE |
| | EVALUATION REPORT AND INSTALLATION INSTRUCTIONS ARE |
| | ALSO REQUIRED. |
| | |
| | |