Plan Review Notes
Plan Review Notes For Permit 06090410
Permit Number 06090410
Review Stop B
Sequence Number 4
Notes
Date Text
2007-07-26 07:22:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LISTS:
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)ADDRESSED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4-6.) ADDRESSED.
  
 7.)SEE PREVIOUS LISTS REGARDING RESIDENT INSPECTOR
 REQUIREMENT AND A MEETING WITH HAROLD PISKURA,
 561-805-6711.THE PERMIT CANNOT BE PASSED, STAMPED,
 AND ISSUED UNTIL THIS IS COMPLETED.
  
 8-27.)ADDRESSED.
  
 28.)THE THIRD RESPONSE LETTER STATES THAT ALL LIFE
 SAFETY INFORMATION WAS INCLUDED IN MSP1; THIS FOURTH
 RESPONSE LETTER STATES THAT THE INFORMATION IS ON A101.
 I WAS UNABLE TO LOCATE OCCUPANT LOAD, SEE FBC 1004.1.2,
 TABLE 1004.1.2.THERE IS A PLUMBING FIXTURE OCCUPANT
 LOAD ON A102, BUT THIS ONLY INCLUDES ONE FLOOR OF THE
 GARAGE.THIS OCCUPANT LOAD DOES NOT INCLUDE THE
 SERVICE AREA OR ROOF PARKING.FOR EGRESS, YOU MUST
 DECLARE OCCUPANT LOAD PER AREA AND IT CANNOT BE LESS
 THAN FBC TABLE 1004.1.2 AS PER REQUIREMENTS OF FBC
 1004.1.2.THE PLUMBING FIXTURE OCCUPANT LOAD USES
 200SF PER OCCUPANT, BUT THIS IS FOR PARKING GARAGE
 ONLY, NOT FOR THE SERVICE AREA.OCCUPANT LOAD IS A
 LIFE SAFETY ISSUE (CONFIRM ADEQUATE MEANS OF EGRESS)
 AND CANNOT BE WAIVED, ALSO CANNOT USE THE PLUMBING
 FIXTURE OCCUPANT LOAD AS IT DOES NOT BREAK DOWN
 OCCUPANTS BY FLOOR AND OCCUPANCY AND THAT NUMBER IS
 LESS THAN HALF OF WHAT IS REQUIRED FOR EGRESS.AN
 OCCUPANT LOAD WAS PROVIDED FOR THE LOUNGE/TRAINING, BUT
 THIS NEEDS TO BE DONE FOR EVERY SPACE (OCCUPANT LOAD
 FOR SERVICE AREA, 2ND FLOOR PARKING, ROOFTOP PARKING,
 STORAGE AREAS).IT IS NOT CLEAR WHY THE PLUMBING
 FIXTURE OCCUPANT LOAD WOULD INCLUDE ONLY THE SECOND
 FLOOR PARKING GARAGE OF 17,365 AND NOT INCLUDE THE
 SERVICE GARAGE, ROOFTOP PARKING, AND OTHER AREAS.
  
 40-55.)ADDRESSED.
  
 56.)REGARDING THE PRODUCT APPROVALS SUBMITTED (FIRST
 REVIEW FOR THE PRODUCT APPROVALS):
  
 THE OVERHEAD DOOR PRODUCT APPROVAL IS LIMITED TO A 10'
 WIDE DOOR, +-65PSF.THERE ARE THREE OVERHEAD DOORS
 WHICH ARE WIDER THAN 10' AND ONE WHICH HAS A DESIGN
 PRESSURE WHICH EXCEEDS -65 (HAS A DP OF -73).PLEASE
 ADDRESS.
  
 THE FLEMING DOOR SPECS REFER TO THREE DIFFERENT NOA
 NUMBERS BUT NONE WERE PROVIDED.THE SHOP DRAWINGS
 PROVIDED ARE NOT REQUIRED, BUT THE EVALLUATION REPORT
 (NOA) IS REQUIRED.PLEASE PRINT THE NOA(S) FOR THE
 DOOR(S) YOU WISH TO USE.IT APPEARS THAT THE PRODUCTS
 ARE COMPLIANT WITH THE DP REQUIREMENT OF +56/-61.
  
  
  