| 2007-05-17 15:37:57 | *****UNSAT***** |
| | |
| | |
| | PREVIOUS COMMENTS WHICH STILL NEED TO BE ADDRESSED: |
| | |
| | 03.ON PAGE E-103 ONLY TWO ILLUMINATED EXIT SIGNS |
| | EXIST.EXIT SIGNAGE IS USED TO DIRECT PERSONS TO EXITS |
| | EVEN WHEN THEY ARE NOT CLEARY OBVIOUS.DISPLAY NEW |
| | EXIT SIGN PLACEMENT SUCH THAT NO POINT IN AN EXIT |
| | ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING |
| | DISTANCE OR 100 FEET, WHICHEVER IS LESS, FROM THE |
| | NEAREST SIGN. |
| | |
| | 04.NO EMERGENCY SIGN LIGHTING DECLARED ON PAGE E-103. |
| | PLEASE INDICATE LOCATION OF THESE DEVICES |
| | |
| | 09.BUILDING ADDRESS WITH A MININIMUM OF 6" IN HEIGHT |
| | AND 1" IN WIDTH REQUIRED.IN ADDITION TO THE HEIGHT |
| | REQUIREMENT AS SHOWN ON SHEET A-5, THE WIDTH |
| | REQUIREMENT SHALL BE ADHERED ALSO. |
| | |
| | 15.CONSTRUCTION, DEMOLITION, AND RENOVATION |
| | OPERATIONS SHALL COMPLY WITH NFPA 241.INDICATE ON |
| | APPROPIATE PLAN SHEET |
| | |
| | 16.DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| | INDICATE ON THE APPROPIATE PLAN SHEET |
| | |
| | 17.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. |
| | INDICATE ON THE APPROPIATE PLAN SHEET THAT THE KNOX BOX |
| | WILL BE INSTALLED IN AN ACCESSIBLE LOCATION AND/OR |
| | WHERE DIRECTED BY THE FIRE MARSHAL. |
| | |
| | NEW COMMENT |
| | |
| | AA.IT IS NOTED AS PER LILU URSA THAT THE NUMERICAL |
| | ADDRESS IS 3023;HOWEVER3021 IS LISTED IN THE TITLE |
| | BLOCK OF SOME OF THE SUBMITTED PLAN SHEETS. |
| | |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT |
| | WAS ADDRESSED |
| | |
| | |