| 2007-04-22 11:16:36 | |
| | ******* UNSAT 3RD REVIEW ****** |
| | |
| | ** PLEASE SEE THAT THERE ARE STILL SOME ITEMS FROM |
| | PREVIOUS REVIEWS WHICH HAVE NOT YET BEEN CLEARED UP AND |
| | NEED TO BE ADDRESSED. |
| | |
| | 1) NOTE: PLEASE SEE RESPONSE FROM DESIGNERS MENTIONS |
| | THE ADDRESS WHICH HAS BEEN GIVEN BY THE ADDRESSING |
| | REVIEWER IS THAT OF 3023 AND IS NOW ON ALL TITLE BLOCKS |
| | ACCORDINGLY, HOWEVER THE TITLE BLOCKS ON ALL SHEETS |
| | STILL INDICATE 3021? |
| | PLEASE KNOW IF THIS IS THE ONLY COMMENT ON SOME SHEETS, |
| | THIS MAY BE HAND PRINTED ON SHEETS BY CONTRACTOR OR |
| | OTHER DESIGN STAFF. |
| | PLEASE REVISE ON SHEETS WHICH NEED TO BE CHANGED OUT. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | CONTROL OF EGRESS LIGHTING IN STAIRS. RESPONSE MENTIONS |
| | THAT ONCE ON DEVICE IS ACTIVATED THAT 15MINS IS MORE |
| | THAN ENOUGH TIME TO EGRESS TO THE NEXT LEVEL, HOWEVER |
| | THE COMMENT IS FOR THE FAILURE OF ANY ONE SINGLE DEVICE |
| | (OCCUPANCY SENSORS) CAN NOT LEAVE ANY ONE AREA OF |
| | EGRESS IN TOTAL DARKNESS. |
| | PLEASE SEE 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE |
| | LIGHTING SWITCHES SHALL BE PERMITTED WITHIN THE MEANS |
| | OF EGRESS, PROVIDED THAT THE SWITCH CONTROLLERS ARE |
| | EQUIPPED FOR FAIL-SAFE OPERATION, THE ILLUMINATION |
| | TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION, AND |
| | THE MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT |
| | IN THE AREA SERVED BY THE LIGHTING UNITS. |
| | PLEASE ALSO SEE CHAPTER 10 OF THE FBC 1006.1.2 WHICH |
| | STATES THE SAME. |
| | IT IS LS 101 7.9.2.2 WHICH MENTIONS THE FAILURE OF A |
| | SINGLE DEVICE, SWITCHING, TRIPPING OF A BREAKER ETC. |
| | THIS WOULD REQUIRE A MINIMUM OF TWO OCCUPANCY SENSORS |
| | OR DEVICES OF SOME TYPE TO DETECT THE OCCUPANT AND TURN |
| | ON THE LIGHTING. IF AN OCCUPANT WAS TO LEAVE AN UPPER |
| | FLOOR, AND THE DEVICE WAS NOT IN WORKING ORDER, THEN A |
| | SECOND DEVICE IS REQUIRED IN THE VICINITY TO DO THE |
| | SAME AS THE PRIMARY DEVICE. |
| | |
| | 3) NOTE: PLEASE SEE THAT AS THIS IS BEING CONSIDERED |
| | AND CONSTRUCTED AS A SEPARATE BUILDING, AS NOTED ON |
| | PREVIOUS REVIEW, THE MECHANICAL AND ELECTRICAL |
| | EQUIPMENT IS STILL BE SHOWN ON THE EXISTING ROOF OF THE |
| | EXISTING BUILDING WHICH IS NOT CONSIDER PART OF THE NEW |
| | *BUILDING* |
| | PLEASE RELOCATE. |
| | PLEASE SEE SOME SHEETS STILL INDICATE THE PREVIOUS WALL |
| | AND FLOOR LAYOUTS WHICH DO NOT COORDINATE WITH THE REST |
| | OF THE PLANS. (*SITE PLANS*) |
| | FBC 106.1.2 |
| | 225.30, 230.3. |
| | |
| | 4) NOTE: PLEASE SEE NOW THERE ARE HAND DRAWN CHANGES TO |
| | SHEET E-101 WHICH ONE OF THE ITEMS IN THAT OF AN EXIT |
| | SIGN WHICH IS PLACED SO THAT THE OCCUPANTS IN SOUTHEAST |
| | STAIR TOWER ARE TO EGRESS INTO THE ADJACENT HUMMER |
| | BUILDING?? |
| | NO HAND DRAWN CHANGES ARE PERMITTED TO PLANS FS |
| | 471.025 |
| | PLEASE SEE FIRE AND BUILDING REVIEWS. |
| | PLEASE SEE THE ELEVATION ON A105 SHOWS WHAT APPEARS TO |
| | BE AN EXIT DOORWAY FROM VESTIBULE TO OUTSIDE, SHOULD |
| | NOT THIS EXIT LIGHT BE LOCATED ABOVE THE EAST DOOR IN |
| | THIS STAIR TOWER? |
| | PLEASE SEE OTHER HAND DRAWN CIRCULAR SYMBOL WHICH IS |
| | ALSO ADJACENT TO THIS SAME AREA? |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE RESPONSE LETTERS MENTIONS THE OVER |
| | RIDE TIMES AND TIMES HOWEVER COULD NOT LOCATE THE TIMES |
| | FOR THE OCCUPANCY DEVICES. PLANS DO NOTE THE TIME FOR |
| | THE OVER RIDE OF THE SERVICE BAY. 13-415.1.ABC.1.1 |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE |
| | MINIMUM LEVELS FOR HORN AND STROBE DEVISE WHICH ARE |
| | REQUIRED TO BE STATED ON THE BASE SET OF BUILDING PLANS |
| | FOR FBC ADA COMPLIANCE. IT IS KNOWN THAT ANY FA WORK |
| | WILL BE UNDER SEPARATE PERMIT HOWEVER BASE BUILDINGS |
| | MUST INDICATE MINIMUM COMPLIANCE. |
| | FBC 11-4.28.1,.2 AND .3(4). |
| | FBC 106.3.5.1.2 |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS REVIEW AND RESPONSE |
| | MENTIONS THAT THE MINIMUM LEVELS FOR WIND LOADS FOR |
| | ROOF TOP LIGHT POLES WILL BE STATED ON PLANS AND TO SEE |
| | FIXTURE LEGEND HOWEVER THE FIXTURE LEGEND DOES NOT |
| | INDICATE THE *140MPH MINIMUM* DESIGNATION. |
| | THE CALCULATIONS CAN BE SET UP AS A *PROVISO* WHICH |
| | WILL ALLOW ISSUANCE AND CALCULATIONS TO BE SUBMITTED |
| | BEFORE INSTALLATION, HOWEVER PLEASE STATE THE 140. FBC |
| | 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE THE THIRD PARKING |
| | LEVEL/OUTSIDE/EXTERIOR LIGHTING WHICH STILL INDICATE |
| | LIGHTING TO A LIGHTING CONTACTOR #3, BUT NO DETAIL WAS |
| | SUBMITTED. |
| | PLEASE SHOW. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE SEE PREVIOUS NOTES WHICH MENTIONED TO |
| | CORRELATE AND COMPLETE THE ENERGY CALCULATIONS AND TO |
| | VERIFY THE METHOD AS SUBMITTED. |
| | PLEASE SEE THE FRONT COVER SHEET MENTIONS THAT THE |
| | INPUT DATA REPORT MUST BE SUBMITTED ALONG WITH |
| | COMPLIANCE REPORT, HOWEVER THIS HAS NOT BEEN DONE. |
| | PLEASE SEE 13-415.1.AB.1.1 |
| | |
| | 10) NOTE: ** NOT A COMMENT FOR TEELE ENGINEERING. |
| | PLEASE SEE THE PREVIOUS REVIEW WHICH INDICATED THAT THE |
| | *S* SHEETS CONTAINED A *RUBBER-STAMP* FOR REQUIRED |
| | ORIGINAL SIGNATURE, AND RESPONSE WAS THAT ALL SHEETS |
| | WILL NOW BE SIGNED, HOWEVER ONLY ONE OF THE *S* SHEETS |
| | WERE CORRECTED. PLEASE SEE BUILDING REVIEW NOTES AS |
| | THIS IS ONLY BEING NOTED BY THIS REVIEWER AT THIS TIME |
| | AND DOES NOT AFFECT THE ELECTRICAL PLANS. |
| | FS 471.025 |
| | |
| | 11) NOTE: PLEASE SEE NOTE BELOW ON PREVIOUS REVIEW |
| | WHICH REQUESTED ALL OLD/VOIDED SHEETS TO BE REMOVED |
| | FROM THE TWO COMPLETED SETS. ONE SET OF EACH OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED WITH THE TWO SETS |
| | SEPARATELY AND NOT INCLUDED IN SETS. |
| | THIS WILL HELP ALLEVIATE ANY CONFUSION FOR NEW AND OLD |
| | SHEETS , AND WILL HELP TO NOT CAUSE ANY FURTHER DELAYS |
| | IN THE PROJECT. |
| | |
| | |
| | ** PLEASE BE AWARE OF COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |