| Date |
Text |
| 2007-06-22 13:55:13 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| | PERMIT PICKUP, FS713.13. |
| | |
| | 2.)ADDRESSED. |
| | |
| | 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| | 561-233-5025 FOR MORE INFORMATION. |
| | |
| | 4-5.) ADDRESSED. |
| | |
| | 6.)THE INFORMATION REQUIRED FOR THE ENGINEER |
| | FAC61G15-23.002 IS TO BE ON EACH SHEET.THIS COMMENT |
| | IS FOR THE FIRE SPRINKLER ENGINEER.THIS APPLIES TO |
| | THE CALCS AND THE DRAWINGS.IF AN INDEX SHEET IS NOT |
| | PROVIDED FOR THE CALCS, EACH SHEET IS TO BE SIGNED, |
| | SEALED, AND DATED. |
| | |
| | 7.) FBC* 109.3.7 RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| | RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| | DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT |
| | INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO |
| | ONE OR MORE OF THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE |
| | DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | - BUILDINGS OVER 20,000 SQFT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS |
| | OF CONSTRUCTION |
| | |
| | ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION |
| | SERVICES MANAGER - TEL: |
| | 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT |
| | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS |
| | MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL |
| | SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING. |
| | |
| | 3RD REVIEW ? ONLY TWO SETS WERE SUBMITTED.NOTE THAT |
| | ALTHOUGH THIS PLAN HAS PASSED SOME REVIEWS, ANOTHER |
| | REVIEW WILL BE REQUIRED SO THAT THOSE REVIEWERS CAN |
| | STAMP THEIR SHEETS WHEN THE THIRD SET IS SUBMITTED. |
| | |
| | 8.) PROVIDE ORIGINAL SIGNED, SEALED, DATED SOILS |
| | REPORTS, FBC1802.2.1, 1802.2.3.THREE SETS REQUIRED. |
| | AS STATED IN THE PREVIOUS REVIEWS, THE SIGNATURE CANNOT |
| | BE A PHOTOCOPY. |
| | |
| | 9.) ADDRESSED. |
| | |
| | 10.)ADDRESSED, BUT SEE OTHER COMMENTS REGARDING |
| | PRODUCT APPROVALS. |
| | |
| | 11.)ADDRESSED. |
| | |
| | 12.)IT IS NOT CLEAR IF THE EQUIPMENT SHEDS WERE |
| | INCLUDED IN THE BUILDING CODE SUMMARY.THIS IS THE |
| | THIRD REQUEST FOR THIS INFORMATION.IS THIS AREA |
| | INCLUDED IN ONE OF THE OTHER EXISTING BUILDINGS?THE |
| | PLAN SHOWS THE EXISTING EQUIPMENT SHED AGAINST THIS |
| | BUILDING.ARE YOU DESIGNING AS ONE BUILDING OR TWO |
| | SEPARATE BUILDINGS? |
| | |
| | 13-17.) ADDRESSED. |
| | |
| | 18.)REGARDING MAXIMUM AREA OF EXTERIOR WALL OPENINGS, |
| | OPENINGS AND PERCENTAGES WERE PROVIDED FOR THE EXISTING |
| | BUILDINGS.PROVIDE ALSO FOR THE PROPOSED BUILDING TO |
| | SHOW COMPLIANCE WITH FBC TABLE 704.8.NOTE THAT EAST |
| | ELEVATION HAS A LARGE AMOUNT OF OPENINGS ON A PORTION |
| | OF THE WALL.SEE THE ATTACHED COMMENTARY IN REGARDS TO |
| | UNIFORM DISTRIBUTION. |
| | |
| | THE % OF WALL OPENINGS, EXISTING VW SERVICE TO NEW |
| | SERVICE, SHOULD BE 15%-45%. |
| | |
| | EQUIPMENT SHEDS ARE SHOWN.ARE THEY ALSO TYPE II B |
| | CONSTRUCTION?ONE IS SHOWN CONNECTED TO THE NEW |
| | SERVICE BUILDING, BUT NOT DETAILS ARE PROVIDED.IS |
| | THIS AN EXISTING BUILDING?COMPLIANCE WITH FBC TABLE |
| | 601, FBC TABLE 704.8 IS TO BE SHOWN ON THE PLAN. |
| | |
| | 19.)ADDRESSED. |
| | |
| | 20.)MSP1 STATES THAT EXISTING HUMMER BUILDING HAS A 2 |
| | HOUR WALL.IS THIS THE EXISTING CONDITION, OR WILL THE |
| | FIRE RESISTANCE OF THE WALL BE INCREASED TO COMPLY WITH |
| | THE NEW 2 HOUR REQUIREMENT?PROVIDE A DETAIL, EITHER |
| | CALCULATED FIRE RESISTANCE OR UL ASSEMBLY FOR THE |
| | EXISTING WALL.SEE FBC TABLE 602.IT IS ACCEPTABLE TO |
| | EXCEED CODE COMPLIANCE, BUT B OCCUPANCY REQUIREMENT IS |
| | 1 HOUR.THE NEW SERVICE HAS A 2 HOUR REQUIREMENT. |
| | |
| | MSP1 STATES THAT THE EXISTING SERVICE BUILDING HAS A 2 |
| | HOUR WALL.IS THIS THE EXISTING CONDITION, OR WILL THE |
| | FIRE RESISTANCE OF THE WALL BE INCREASED TO COMPLY WITH |
| | THE NEW 2 HOUR REQUIREMENT?PROVIDE A DETAIL, EITHER |
| | CALCULATED FIRE RESISTANCE OR UL ASSEMBLY FOR THE |
| | EXISTING WALL. |
| | |
| | PLEASE NOTE REQUIREMENTS FOR NEW SERVICE BUILDING. NOTE |
| | ON MSP1 AND SHOW REQUIREMENTS ON THE PLAN.MSP1 SHOWS |
| | 2 HOUR ON THE WALL ADJACENT TO THE HUMMER SHOWROOM, BUT |
| | DOES NOT SHOW THE 2 HOUR REQUIREMENT FOR THE STORAGE |
| | AND OIL STORAGE AREAS. |
| | |
| | 21.)ADDRESSED. |
| | |
| | 22.)WHAT IS BETWEEN THE PROPOSED SERVICE/PARKING AND |
| | EXISTING VW SERVICE/VW SHOWROOM?THIS WAS DISCUSSED IN |
| | A MEETING AS BEING A CANOPY. PLEASE LABEL THIS AREA. |
| | |
| | 23.)A101 AND OTHER DETAILS, STAIR DOORS A132, A2-03, |
| | A303, SEE FBC11-4.13 AND FBC FIGURE 11-26, TWO HINGED |
| | DOORS IN A SERIES. |
| | |
| | THIS WAS ADDRESSED ON MOST PAGES.PLEASE ALSO REVISE |
| | THE ELECTRICAL SHEETS AND CHECK ALL SHEETS. |
| | |
| | 24-27.) ADDRESSED. |
| | |
| | 28.)RESPONSE LETTER STATES THAT ALL LIFE SAFETY |
| | INFORMATION WAS INCLUDED IN MSP1.I WAS UNABLE TO |
| | LOCATE OCCUPANT LOAD, SEE FBC 1004.1.2, TABLE |
| | 1004.1.2. |
| | |
| | 34.)ADDRESSED. |
| | |
| | 33.)STATE WHETHER THIS HAS BEEN DESIGNED AS AN OPEN |
| | PARKING GARAGE OR ENCLOSED PARKING GARAGE, STATE IN THE |
| | CODE SUMMARY, FBC406, AND SEE ALL REQUIREMENTS, SHOW ON |
| | PLAN. |
| | |
| | PLEASE INCORPORATE INFORMATION INTO THE PLAN AS |
| | REQUESTED.THIRD REQUEST. THE RESPONSE LETTER STATES |
| | THAT THIS INFORMATION IS INCLUDED ON MSP1, BUT I WAS |
| | UNABLE TO FIND THE CLASSIFICATION OF OPEN OR ENCLOSED. |
| | |
| | 34-36.) ADDRESSED. |
| | |
| | 37.)A101, ROOF PLAN, 2ND FLOOR PLAN, STORAGE IS SHOWN |
| | WITH AN OPENING INTO THE STAIR.SEE 1019.1.1, OPENINGS |
| | TO BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS FROM |
| | NORMALLY OCCUPIED SPACES. |
| | |
| | YOUR OBJECTION TO THE COMMENT IS NOTED.PLEASE SEE |
| | ATTACHED COMMENTARY, INCLUDING THE SENTENCE WHICH |
| | SPECIFICALLY EXCLUDES STORAGE CLOSETS AS THEY DO NOT |
| | CONSIDER THIS A "NORMALLY OCCUPIED SPACE" REGARDLESS OF |
| | BUILDING OCCUPANCY CLASSIFICATION.ALSO NOTE THAT |
| | ALTHOUGH YOU ARE PROPOSING ENCLOSED SPACE ON THE ROOF, |
| | A FIRE SPRINKLER PLAN WAS NOT PROVIDED FOR THE ROOF. |
| | |
| | 38.)FIRE EXIT, FIRST FLOOR, TO HAVE SEPARATION FROM |
| | THE OCCUPANCY ABOVE IF AN OCCUPANCY SEPARATION IS |
| | REQUIRED.GG-A108. |
| | |
| | YOUR RESPONSE STATES THAT VERTICAL OPENINGS ARE NOT |
| | REQUIRED TO BE PROTECTED.I WAS REFERRING TO THE FLOOR |
| | CEILING ASSEMBLY BETWEEN THE FIRE EXIT 1ST FLOOR, S1 |
| | OCCUPANCY, AND THE RAMP/PARKING GARAGE, S2 ON THE |
| | SECOND FLOOR.A 2 HOUR IS SHOWN THROUGHOUT THE |
| | REMAINDER OF THE BUILDING ON SECTION G-G AND APPEARS TO |
| | ALSO BE SHOWN ON A-A-106.THIS ALSO APPLIES TO MENS |
| | ROOM F-F A108. |
| | |
| | 39.)ADDRESSED. |
| | |
| | 40.)PLEASE PROVIDE OCCUPANT LOAD AS PREVIOUSLY |
| | REQUESTED FOR THE LOUNGE/TRAINING AREA SO THAT EGRESS |
| | REQUIREMENTS AND COMPLIANCE CAN BE DETERMINED. |
| | |
| | 41-51.) ADDRESSED. |
| | |
| | 52.)PLEASE SUBMIT ALL PRODUCT APPROVALS REQUIRED AT |
| | THIS TIME.DOOR PRODUCT APPROVALS WERE NOT SUBMITTED. |
| | PROVIDE WIND DESIGN CRITERIA FBC1603.1.4 INCLUDING |
| | COMPONENTS AND CLADDING DESIGN PRESSURES. |
| | |
| | 53.)THE SIGNATURE FOR AN ENGINEER CANNOT BE A STAMP |
| | (STRUCTURAL ENGINEER), SEE FAC61G15-23.002, FS471.025. |
| | |
| | 54.)PLEASE CLOUD ALL CHANGES AND SUBMIT OLD SHEETS. |
| | PLEASE INCLUDE A RESPONSE LETTER INDICATING HOW EACH |
| | ITEM HAS BEEN ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | |
| | 55.)FLORIDA STATE PRODUCT APPROVAL COVER SHEET, |
| | FL5723, WAS SUBMITTED FOR SHUTTERS.USE OF REMOVABLE |
| | SHUTTERS ON COMMERCIAL BUILDINGS IS TO BE APPROVED BY |
| | THE BUILDING OFFICIAL, SEE ATTACHED POLICY, ITEM 13. |
| | SUBMIT AN INSTALLATION PLAN WITH ALL REQUIRED |
| | INFORMATION (SEE POLICY).THIS MAY BE DONE PRIOR TO |
| | RESUBMITTAL VIA EMAIL.ONCE A PRELIMINARY INSTALLATION |
| | PLAN IS APPROVED BY THE BUILDING OFFICIAL, ORIGINALS |
| | WILL BE REQUIRED. |
| | |
| | 56.)IF YOU ARE USING SHUTTERS, AN INSTALLATION |
| | SCHEDULE IS REQUIRED ALONG WITH A KEY PLAN SHOWING |
| | INSTALLATION LOCATIONS; SEE ATTACHED.ALSO PRINT THE |
| | EVALUATION REPORT AND INSTALLATION INSTRUCTIONS.IT IS |
| | NOT CLEAR WHY SHUTTERS WERE INCLUDED IN THE PACKAGE |
| | (NOT CLEAR WHERE THEY WILL BE INSTALLED). |
| | |
| | 57.)OLD SHEETS WERE LEFT IN THE PACKAGE.PLEASE MARK |
| | THESE SHEETS VOID, REMOVE FROM THE SETS, AND SUBMIT |
| | SEPARATELY FOR REFERENCE. |
| | |
| | 58.)S2 SHOWS EXISTING FOOTERS AND FOOTERS WHICH |
| | APPEAR TO ENCROACH THE ASSUMED PROPERTY LINE AND THE |
| | EXISTING HUMMER BUILDING, 1'6" AWAY.PLEASE CLARIFY. |