| 2007-02-12 14:39:15 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. THE IMPRESSION SEAL SHALL |
| | IMPRESS INFORMATION REQUIRED BY FAC 61G1-16.002(1) & FS |
| | 481.2055 ON EACH SHEET. |
| | *****RESPONSE NOTED, BUT ALL REQUIRED INFORMATION SHALL |
| | BE IMPRESSED ON EACH SHEET, AND THE INFORMATION SHALL |
| | BE LEGLBLE. NOT ALL INFORMATION IS LEGIBLE. |
| | |
| | 2. OK |
| | |
| | 3. SHT A-104 INDICATE THE SQUARE FOOTAGE AND OCCUPANCY |
| | OF THE SERVICE AREA, OIL STORAGE ARE, AND BUSINESS |
| | AREAS. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES FOR |
| | EACH OCCUPANCY PER TABLES 1004.1.2 & 403.1. SEPARATE |
| | FACILITIES ARE REQUIRED FOR EACH SEX PER SECTION 403.2. |
| | ONLY MEN'S FACILITIES ARE SHOWN. |
| | ****RESPONSE NOTED, BUT THE INFORMATION IS NOT LOCATED |
| | ON SHT A-104. ALSO RESPONSE "ALSO PLEASE SEE RESPONSES |
| | TO BUILDING PLAN REVIEW" IS NOT TOO CLEAR AS BUILDING |
| | HAS 51 COMMENTS. PLEASE INDICATE WHICH COMMENT WILL |
| | RESPOND TO MY COMMENT. THIS WILL HELP EXPEDITE THE PLAN |
| | REVIEW PROCESS. IT APPEARS THAT THERE ARE SOME AREAS |
| | THAT ARE NOT STORAGE. THE PARTS WARRANTY AREA, AND THE |
| | LOUNGE/TRAINING AREA.--SECTION 403.3 STATES THAT |
| | THE REQUIRED WATER CLOSETS, LAVS, SHALL BE DISTRIBUTED |
| | EQUALLY BETWEEN THE SEXES.THE OCCUPANT LOAD SHALL BE |
| | COMPOSED OF 50 PERCENT OF EACH SEX, UNLESS STATISTICAL |
| | DATA APPROVED BY THE CODE OFFICIAL INDICATE A DIFFERENT |
| | DISTRIBUTION OF THE SEXES. |
| | |
| | 4. SHT A-200 SHOW COMPLIANCE FOR THE FOLLOWING:FOR |
| | W/C'S |
| | A. OK |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | ****RESPONSE NOTED, BUT DETAILS 18 & 31 SHOW THE FLUSH |
| | CONTROL ON THE WALL SIDE. |
| | FOR TOILET STALL |
| | A. OK |
| | FOR THE URINAL |
| | A. OK |
| | FOR LAVS |
| | A. 11-4.19.2 CLEARANCES |
| | ****NOT ADDRESSED |
| | B. 11-4.19.5 FAUCETS |
| | ****NOT ADDRESSED |
| | |
| | 5. SHT A-201 SHOW COMPLIANCE FOR THE FOLLOWING:FOR |
| | KIT. SINK |
| | A. 11-4.24.5 CLEAR FLOOR SINK (FORWARD APPROACH |
| | REQUIRED) |
| | ****NOT ADDRESSED |
| | B. OK |
| | |
| | 5. OK |
| | |
| | 6. SHT P-100 BECAUSE OF THE AUTOMOBILE SERVICE WORK AN |
| | OIL/GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT |
| | LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER FOR A |
| | DETERMINATION. CONTACT HER AT (561) 822-2271, OR BY FAX |
| | (561) 822-2279, OR BY E-MAIL [email protected]. WASTE |
| | ORD. 3434. |
| | ****WAITING FOR WORD FROM ENVIRONMENTAL COMPLIANCE AS |
| | THEY WILL HAVE TO ISSUE THE RESULTS OF THE REQUIREMENT. |
| | THERE ARE STILL SERVICE SINKS AND IT WILL BE THEIR |
| | DETERMINATION. |
| | |
| | 7. SHT P-101 SUBMIT MANUF. SPECIFICATION SHEETS FOR THE |
| | INSTANT-FLOW WATER HEATER FOR THE KITCHEN SINK. SPECS. |
| | SHALL SHOW A LISTING FOR THE W/H. SECTIONS 106.1.2 & |
| | 303.4. |
| | ****RESPONSE NOTED, BUT MANUF. SPECIFICATION SHEETS |
| | WERE NOT LOCATED. |
| | |
| | 8. SHT P-200 SHOW THE CLEANOUTS AS REQUIRED IN SECTION |
| | 1101.8 FOR THE STORM RISERS. |
| | ****RESPONSE NOTED, BUT THE CLEANOUTS FOR SECTIONS |
| | 708.3.1, 708.3.2, 708.3.3, & 708.3.4 WERE NOT SHOWN ON |
| | THE FLOOR PLAN, NOR ON THE RISER DIAGRAMS. |
| | |
| | 9.OK |
| | 10. OK |
| | |
| | 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO |
| | THE BUILDING. SECTION 608.13.2. |
| | ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED ON |
| | EACH BUILDING. PLEASE INDICATE A BACKFLOW PRIOR TO THE |
| | WATER SERVICE ENTERING THE BUILDING TO SHOW |
| | COMPLIANCE. |
| | |
| | 12. SHT P-200 WATER RISER DIAGRAM. FULL OPEN VALVES |
| | REQUIRED ON EACH WATER DOWN-FEED PIPE. SECTION |
| | 606.1(4). |
| | ****RESPONSE NOTED, BUT THE VALVES ARE NOT SHOWN AT |
| | FIXTURES P1, P2, P3, P4, P4, P6 & P9. |
| | |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | |
| | ************NEW COMMENT************* |
| | |
| | 1B. SHTS A-200 & A-201 ARE OUT OF SEQUENCE IN ONE SET |
| | OF PLANS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |