| 2007-02-23 10:18:31 | *****UNSAT***** |
| | |
| | |
| | THE FOLLOWING COMMENTS TAKEN FROM PREVIOUS FIRE PLAN |
| | REVIEW OF 10/25/2006 STILL NEED TO BE ADDRESSED: |
| | |
| | |
| | 01.INDICATE THE TYPES OF AUTOMOTIVE REPAIRS THAT ARE |
| | PLANNED FOR THE BUILDING.PLEASE BE SPECIFIC |
| | |
| | 02.SPRINKLER PLANS WERE SUBMITTED, HOWEVER, SEE |
| | ELECTRICAL PLAN REVIEW NOTE #22 IN REFERENCE TO THE |
| | SIGNING AND SEALING OF DOCUMENTS. |
| | |
| | 03.ON PAGE E-103 ONLY TWO ILLUMINATED EXIT SIGNS |
| | EXIST.EXIT SIGNAGE IS USED TO DIRECT PERSONS TO EXITS |
| | EVEN WHEN THEY ARE NOT CLEARY OBVIOUS. ADD EXTRA EXIT |
| | SIGN LIGHTIN PARKING AREA DIRECTING PERSONS TO THE |
| | NEAREST EXIT. |
| | |
| | 04.NO EMERGENCY SIGN LIGHTING DECLARED ON PAGE E-103. |
| | PLEASE INDICATE LOCATION OF THESE DEVICES |
| | |
| | 06.PLEASE PROVIDE PRODUCT APPROVALS FOR THE CO |
| | DETECTORS PLANNED FOR USE. |
| | |
| | 09.BUILDING ADDRESS WITH A MININIMUM OF 6" IN HEIGHT |
| | AND 1" IN WIDTH REQUIRED.PLEASE DISPLAY/SHOW ON THE |
| | APPROPIATE EXTERIOR ELEVATION |
| | |
| | 12.NO PORTABLE FIRE EXTINGUISHERS PROVIDED.SHOW THE |
| | LOCATION OF THE FIRE EXTINGUISHERS WHICH SATISFY THE |
| | 75' TRAVEL DISTANCE |
| | |
| | 13.PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS |
| | FOR ALL HANDRAILS, GUARDRAILS, AND CABLE RAIL SYSTEMS. |
| | INDICATE THE LOCATION OF THIS INFORMATION ON THE |
| | SPECIFIC STRUCTURAL SHEET(S) |
| | |
| | 15.CONSTRUCTION, DEMOLITION, AND RENOVATION |
| | OPERATIONS SHALL COMPLY WITH NFPA 241.INDICATE ON |
| | APPROPIATE PLAN SHEET |
| | |
| | 16.DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| | INDICATE ON THE APPROPIATE PLAN SHEET |
| | |
| | 17.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. |
| | INDICATE ITS LOCATION ON THE APPROPIATE EXTERIOR |
| | ELEVATION |
| | |
| | 19.PLEASE DECLARE DISTANCE FROM EXHAUST TERMINATION |
| | POINTS TO ANY BUILDING OPENINGS.SHOW THE DISTANCE OF |
| | EXHAUST FUMES BEING EMITTED TO THE NEAREST WINDOWS, |
| | DOORS, AIR INTAKES, OR SIMILAR OPENINGS |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT |
| | WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |