| 2007-02-01 18:30:50 | 2007-02-01 18:30:50 |
| | |
| | ******* UNSAT 2ND REVIEW ****** |
| | |
| | *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| | COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION |
| | AND/OR CHANGES MADE TO PLANS. |
| | |
| | **** IMPORTANT**** |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*. |
| | |
| | A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY |
| | THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE |
| | PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE |
| | #1** |
| | |
| | B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A |
| | REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW |
| | NOTE WILL BE REMOVED. |
| | |
| | C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF |
| | THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL. |
| | THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS |
| | REVIEW NOTE #1** |
| | |
| | D) NEW NOTES WILL BE ADDED TO THE END AND LABELED ** |
| | NEW NOTES ** |
| | |
| | |
| | |
| | |
| | 1) A) NOTE: NO, PLEASE SEE THE ADDRESS HAS NOT YET BEEN |
| | CHANGED AND PLEASE SEE THIS IS NOT A SEPARATE BUILDING |
| | BY DEFINITIONS OF THE FBC AND MAY OR MAY NOT CONTAIN A |
| | NEW ADDRESS. THIS HAS BEEN SENT TO THE ADDRESSING |
| | REVIEWER AS IT IS A CODE RELATED COMMENT. PLEASE SEE |
| | POSSIBLE COMMENTS FROM BUILDING, AND FIRE REVIEWER(S). |
| | THIS ADDRESS MAY OR MAY NOT BE OK, IT IS UNCERTIAN AT |
| | THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE PERMIT APPLICATION AND PLANS MENTIONS AND |
| | SHOWS "3021", HOWEVER THIS PROJECT IS LOCATED ON A |
| | LEGAL ADDRESS IN OUR SYSTEM OF "3001". |
| | PLEASE KNOW TITLE BLOCKS SHALL BE REVISED UPON |
| | CORRECTING OF ADDRESS. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK FOR MEP PLANS, SEE NEW COMMENTS FOR OTHER |
| | SHEETS WHICH DO NOT APPLY TO TEELE & ASSC. |
| | |
| | 3) NOTE: NO/OK, NOTES ADDED FOR ITEMS BELOW 18INCHES, |
| | HOWEVER PLEASE SEE ROOMS CONTAINING FUEL/LIQUIDS ETC |
| | WHICH WILL BE A CLASS AND DIVISION LOCATION NEED TO BE |
| | DESIGNATED. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE NEC 511, AND PLEASE INDICATE ALL RELEVANT AREAS |
| | AND LAYOUT ON PLANS. |
| | |
| | 4) NOTE:NO, PLEASE SEE SOME AREAS FOR STAIRS WERE |
| | ADDED; HOWEVER PLEASE SEE THIS COMMENT IS BASED ON ALL |
| | EGRESS PATHS WHICH MAY CONTAIN OCCUPANTS WHICH NEED TO |
| | EGRESS FROM THE BUILDING. |
| | PLEASE SEE THE EXIT CORRIDOR; PLEASE SEE AREAS OF |
| | PARKING GARAGE WHICH DO NOT SEEM TO CONTAIN ANY |
| | EMERGENCY LIGHTING. PLEASE SEE THE LIGHTING IS BEING |
| | SHOWN ON THESE SAME UPPER LEVELS WITH OUT THE USE OF |
| | ANY NIGHT LIGHTS OR PHOTO-CELL OVER RIDES EVEN FOR DAY |
| | TIME OPERATIONS FOR MINIMUM LIGHTING.PLEASE SEE |
| | COMMENTS WITH RESPECT TO CONTACTORS AND CONTROLS. |
| | PLEASE EXPLAIN HOW THE STAIRS ARE SHOWING ONE LEVEL OF |
| | LIGHTING UNDER NORMAL AND ONE LEVEL OF LIGHTING UNDER |
| | EMERGENCY WHEN THE FIXTURES ARE THE SAME TYPES AND ARE |
| | BATTERY BACK UP. DO THESE CONTAIN A REDUCTION OF THE |
| | LIGHTING LEVELS BUILT IN? |
| | PLEASE ALSO SEE THAT THE STAIR LIGHTING IS BEING SHOWN |
| | ON OCCUPANCY SENSOR TYPE DEVICES WHICH ARE OK, HOWEVER |
| | PLEASE SEE DUE TO THE LAYOUT, THE FAILURE OF ONE DEVICE |
| | WOULD LEAVE ANY ONE AREA IN THE MEANS OF EGRESS PATH IN |
| | TOTAL WHICH WOULD NOT MEET THE MINIMUM LIGHTING FOR |
| | LIFE SAFETY. PLEASE ADJUST DEVICES OR CALL TO GO OVER |
| | OTHER POSSIBLE OPTIONS. |
| | ** PLEASE SEE THE FOLLOWING SCENARIO:AN OCCUPANT IS |
| | LOCATED IN THE PARKING GARAGE ON THE SECOND LEVEL (OR |
| | OTHER LOCATIONS IN BUILDING) WHICH DO NOT CONTAIN OF |
| | OVER RIDE(S) FOR LIGHTING WHEN THE LIGHTING SHUTS OFF |
| | DUE TO THE TIME SET. PLEASE SEE THE AREA FOR MEANS OF |
| | EGRESS WOULD BE A HAZARD AND SHOULD CONTAIN EITHER |
| | SENOR DEVICES WHICH PROVIDE COVERAGE FOR OVER RIDE OR |
| | OTHER MEANS OF LIGHT FOR THE OCCUPANT TO FIN THEIR WAY |
| | TO THE MANUAL OVER RIDE DEVICE. |
| | PLEASE PROVIDE TIMES OF SCHEDULING. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE NFPA-101 7.8.1.3, |
| | 7.9.2.2. PLEASE SUBMIT AND SUPPLY ALL MIN PHOTO-METRICS |
| | REQUIRED FOR STAIR TOWERS UNDER NORMAL AND EMERGENCY |
| | POWER. |
| | PLEASE ALSO INDICATE LIGHTING LEVELS (MIN) REQUIRED FOR |
| | ALL OTHER AREAS OF EGRESS. PLEASE SEE THERE ARE AREAS |
| | ON PLANS WHICH DO NOT SEEM TO MEET THIS. |
| | 10FT CANDLES UNDER NORMAL AND 1FT CANDLE UNDER EM IN |
| | STAIRS. |
| | ALL OTHER AREAS 1FT MIN. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: OK. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: NO, NOTED ABOVE IN COMMENT #4. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1** |
| | PLEASE SEE FIRE REVIEW COMMENTS FOR GARAGE AREAS LTS, |
| | REQ'D EM BACK UP. |
| | AS PREVIOUSLY NOTED ABOVE FOR ELECTRICAL REVIEW ALSO. |
| | LS101 7.9 |
| | |
| | 13) NOTE: NO/OK, PLEASE SEE SOME AREAS WHERE INGRESS |
| | INTO SPACE ARE SHOWN INDICATE A *S* AS FOR A STANDARD |
| | SWITCH. PLEASE SEE ANY OVER RIDE TYPE SHOWN THIS WAY |
| | SHOULD BE CLARIFIED ON SYMBOL LEGEND. |
| | PLEASE SEE SEPARATE AREAS (ELEVATOR PIT) WHICH WILL |
| | REQUIRE AUTOMATIC MEANS OF SHUT OFF (TIMER). PLEASE SEE |
| | THERE ARE OVER RIDES SHOWN ON CONTACTOR #1 WHICH DOES |
| | NOT INDICATE TYPE AND AMOUNT OF TIME ON THE OVER RIDE. |
| | PLEASE SEE OTHER AREAS WHICH A DEVICE WILL BE REQUIRED |
| | AND MAXIMUM TIMES FOR ALL DEVICES SHOULD BE INDICATED. |
| | PLEASE SEE 30MINS FOR OCCUPANCY SENSOR TYPE DEVICES AND |
| | 4HRS MAX FOR TIMER TYPE. |
| | PLEASE SEE INPUT DATA IS MISSING FROM THE ENERGY |
| | CALCULATIONS. |
| | PLEASE SEE METHOD USED WILL AFFECT THE INFORMATION. |
| | THESE CALCULATIONS SUBMITTED ARE METHOD *B*. |
| | ** PLEASE SEE NEW NOTES WITH RESPECT TO CONTACTORS, |
| | CONTROLS AND CIRCUITING ON PLANS AND CONTACTORS. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1** |
| | PLEASE SEE 2004 FBC CHAPTER 13 FOR CONTROLS FOR ALL |
| | LIGHTING. |
| | PLEASE INDICATE AND SHOW THE SYSTEM BEING PROPOSED. |
| | PLEASE PROVIDE SCHEDULING OF SYSTEMS. |
| | PLEASE PROVIDE OVER RIDES, LOCATIONS, AND AREAS FOR |
| | SEPARATE CONTROLS REQUIRED. PLEASE SEE FBC |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE SHOW AND INDICATE THE TYPE OF OVER RIDE |
| | DEVICES, AND MAX ALLOWED TIMES. (NOTE: TIMER TYPE (4HRS |
| | MAX), OCCUPANT SENSOR TYPE 30MINS MAX). |
| | ALL AREAS WITH FLR TO CEILING HEIGHT PARTITIONS REQUIRE |
| | SEPARATE CONTROLS. |
| | PLEASE PROVIDE PERFORMANCE CALCULATIONS AND PLEASE SEE |
| | THE MAXIMUM PERMITTED |
| | "LIGHTING POWER DENSITIES" (LPD) ALLOWED FOR AREAS. |
| | PLEASE SEE SPACES AND USE PERMITTED IN TABLES. |
| | 13-415.2, 13-415.2.ABC.1, TABLES? 13-415.2.B. |
| | ALL LPD'S ARE TO BE SHOWN. |
| | |
| | 14) NOTE: NO, PLEASE SEE PLANS THE ARCHITECTURAL PLANS |
| | DO NOT CORRELATE WITH THE MECHANICAL AND PLUMBING |
| | SHEETS WITH RESPECT TO THE WALL(S) FROM THE SHOWROOM OF |
| | THE EXISTING BUILDING AND THE ADDITION. |
| | PLEASE SEE THAT A PARTIAL 2HR RATED WALL DOES NOT |
| | CONSTITUTE A SEPARATE BUILDING BY DEFINITION IN THE |
| | FBC. THIS WOULD BE REQUIRED TO BE A 4 HOUR RATED FIRE |
| | WALL. PLEASE SEE THE DEFINITIONS OF A FIRE WALL IN THE |
| | FBC. THE PLANS AS SUBMITTED DO NOT COMPLY WITH THIS. |
| | PLEASE KNOW BASED ON THIS AND COORDINATION OF SHEETS A |
| | SEPARATE SERVICE FOR THIS ADDITION TO AN EXISTING |
| | BUILDING IS NOT GRANTED AS PREVIOUSLY STATED. PLEASE |
| | ALSO SEE THE PLANS STILL INDICATE MECHANICAL EQUIPMENT |
| | FOR THE NEW BUILDING BEING SHOWN INSTALLED ON THE |
| | EXISTING SHOW ROOM PORTION OF THE BUILDING. |
| | ** PLEASE BE SURE TO SEE NEW NOTES FOR COORDINATION |
| | FROM ELECTRICAL PLANS TO ARCHITECTURAL PLANS. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE THIS IS NOT BEING CONSIDERED A SEPARATE |
| | "BUILDING" AND IS PART OF THE CURRENT STRUCTURE AS THIS |
| | NEW STRUCTURE CONTAINS OPENINGS ETC FOR EGRESS ETC. |
| | PLEASE SEE FBC DEFINITIONS. |
| | PLEASE SEE NEC 230.2, AS THE NEW PROPOSED SEPARATE |
| | SERVICE NOT BEING FED FROM THE EXISTING SERVICE |
| | LOCATION GROUPED ETC IS NOT PERMITTED AS SHOWN. 230.2, |
| | 230.72 ETC. |
| | IN ORDER TO GRANT THE NEW SERVICE FOR A NEW "BUILDING", |
| | THIS WOULD REQUIRE AND |
| | "FIREWALL", 4 HR RATED, COLLAPSIBLE ON BOTH SIDES WITH |
| | OUT AFFECTS ON THE STRUCTURAL INTEGRITY OF EITHER |
| | STRUCTURE. BY THE PLANS SUBMITTED, THIS IS NOT ACHIEVED |
| | AT THIS TIME. |
| | |
| | 15) NOTE: OK. |
| | |
| | 16) NOTE: OK.. |
| | |
| | 17) NOTE: OK. |
| | |
| | 18) NOTE: NO? RESPONSE LETTER MENTIONS TO SEE REVISED |
| | ELECTRICAL PLANS FOR THIS HOWEVER THIS INFORMATION |
| | COULD NOT BE LOCATED. |
| | PLEASE KNOW PLANS ARE REQUIRED TO STATE THE MINIMUM, A |
| | *PROVISO* MAY BE SET UP TO OBTAIN THE STRUCTURAL |
| | CALCULATIONS LATER BEFORE ANY INSTALLATION OF BOLTS, |
| | BASE, ETC FOR POLES. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SUBMIT ALL WIND LOAD CALCULATIONS FOR ROOF TOP |
| | LT POLES WITH |
| | EPA FIGURED FOR ALL LT FIXTURES PROPOSED. |
| | THE CALCULATIONS AND SPEC FOR POLES WILL BE REVIEWED |
| | FOR STRUCTURAL CONNECTIONS, WIND LOADS ETC BY THE |
| | STRUCTURAL REVIEWER. |
| | THEY MUST MEET FBC 2004 140MPH MIN, 3 SEC GUST. |
| | |
| | 19) NOTE: NO? RESPONSE MENTIONS TO SEE REVISED PLANS, |
| | HOWEVER NO INFORMATION COULD BE FOUND FOR PREVIOUS |
| | REQUEST. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SUBMIT THE MANUFACTURE SPECS /CUT SHEETS FOR |
| | THE TANK LESS WATER HEATER. PLEASE BE SURE THEY |
| | INDICATE THE |
| | NRTL LISTING. |
| | 110.3, 90.7. |
| | |
| | 20) NOTE:NO, SAME COMMENT. THIS IS NOTED AS THIS IS |
| | BEING PROPOSED AS A SEPARATE BUILDING, YET THIS IS NOT |
| | BEING MET AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE AS PLUMBING PLANS ALSO INDICATE BEING TIED |
| | INTO THE EXISTING BUILDING, IT SEEMS THE PERMIT |
| | APPLICATION WOULD BETTER DESCRIBE PROJECT AS AN |
| | ADDITION. |
| | THIS WILL BE DECIDED BY DESIGN FOR NOTES FROM ALL |
| | REVIEWER(S). |
| | |
| | |
| | ************ NEW NOTES ********* |
| | |
| | 21) NOTE: PLEASE SEE THE *S* SHEETS SUBMITTED CONTAIN A |
| | *RUBBER STAMP* FOR THE REQUIRED ORIGINAL SIGNATURE FROM |
| | THE ENGINEER. PLEASE SEE THE FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.002 AND FLORIDA STATUTES 471.025. THIS |
| | COMMENT IS MADE AND REQUIRED WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | PLEASE KNOW ONE SET OF PLANS WILL BE RETAINED AS THIS |
| | COMMENT HAS BEEN MADE TO THIS SAME ENGINEER ON OTHER |
| | PROJECTS PREVIOUSLY. |
| | |
| | 22) NOTE: PLEASE SEE FIRE SPRINKLER PLANS DO NOT |
| | CONTAIN ANY TITLE BLOCK FOR THE ENGINEER WHICH IS |
| | SIGNING AND SEALING DOCUMENTS. |
| | PLEASE ALSO SEE THAT THE SEAL IS NOT CLEAR AND VISIBLE |
| | WITH INFORMATION ON SAID SEAL. |
| | PLEASE SEE THAT EVEN SHADOWING DOES NOT PROVIDE |
| | INFORMATION. |
| | FAC 61G15-23.002 AND 61G15-23.001., |
| | THIS COMMENT IS ALSO REQUIRED WHETHER OR NOT COMMENT IS |
| | MADE BY ANY OTHER TRADE(S). |
| | ONE SET IS BEING RETAINED. |
| | ** PLEASE KNOW THAT THE FIRE SPRINKLERS EVEN THOUGH |
| | REQUIRED TO BE SHOWN WITH THE BASE BUILDING PERMITTED |
| | PLANS WILL STILL BE REQUIRED TO BE UNDER A SEPARATE |
| | PERMIT, PLANS AND FEES AT A LATE DATE. |
| | |
| | 23) NOTE: PLEASE SUBMIT COMPLETE DETAILS FOR FIRE ALARM |
| | SYSTEM BEING PROPOSED AND HOW THIS SYSTEM WILL BE TIED |
| | IN THE EXISTING SYSTEM. PLEASE KNOW THE BASE LOCATIONS |
| | AND DEVICES ARE REQUIRED AT THIS TIME FOR BASE |
| | BUILDING. |
| | PLEASE SEE THAT ALL OF THE MINIMUM LEVELS TO MEET FBC |
| | 11-4.28.1, .2 AND .3(4) IS REQUIRED TO BE STATED ON |
| | PLANS. |
| | THIS COMMENT WAS NOT MADE ON THE PREVIOUS PLAN REVIEW |
| | BY THIS REVIEWER HOWEVER THIS IS NOW REQUIRED AS PART |
| | OF THE ELECTRICAL REVIEW. |
| | FBC 106.1.2 AND 106.3.5.1.2 |
| | |
| | ** PLEASE KNOW THAT THE FIRE ALARM SCOPE OF WORK WILL |
| | STILL BE UNDER A SEPARATE PERMIT PLANS AND FEES ART A |
| | LATER DATE. |
| | |
| | 24) NOTE: PLEASE SEE THERE ARE SEVERAL DIFFERENCES ON |
| | THE ARCH SHEETS, FROM THE ELECTRICAL, MECHANICAL AND |
| | PLUMBING SHEETS. |
| | WALLS DO NOT CORRELATE. (DOORS ETC) |
| | FBC 106.1, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION ANDFBC CHAPTER 11. |
| | |
| | |
| | PLEASE SEE THE STAIRS AS THE ELECTRICAL PLANS SHOW |
| | DOORS WHICH ARE OPPOSING WHICH DO NOT MEET THE MINIMUM |
| | REQUIREMENTS FOR ADA. PLEASE SEE STAIRS/VESTIBULE |
| | AREAS. THE A SHEETS DO NOT SHOW THIS SAME DOOR SWINGS. |
| | PLEASE SEE CHAPTER 11 AND BUILDING REVIEW COMMENTS FOR |
| | THIS. THIS IS FOR INFORMATION AT THIS TIME AS |
| | COORDINATION BETWEEN THE SHEETS IS IMPERATIVE. |
| | |
| | 25) NOTE: PLEASE SEE THAT THE CIRCUITS AS SHOWN ON THE |
| | PLANS WHICH ARE NOTED TO THE LIGHTING CONTACTORS ARE |
| | NOT COMPLETE ON THE LIGHTING CONTACTORS. |
| | PLEASE SEE THE IDENTIFICATION OF THE CIRCUITS ON THE |
| | SECOND FLOOR INDICATES TO LIGHTING CONTACTOR #2, |
| | HOWEVER PLEASE SEE THE CONTACTOR DETAIL ON THAT SHEET |
| | IS LABELED *CONTACTOR #1*. |
| | PLEASE SEE LEVELS ANDFIXTURES WHICH MENTIONS LIGHTING |
| | CONTACTOR #3, YET NO DETAIL FOR A LC #3 WAS SHOWN. |
| | PLEASE COORDINATE. |
| | PLEASE SEE NOTES ABOVE WITH RESPECT TO THE CONTACTORS |
| | AND THE OVER RIDE DEVICES REQUIRES AND THE MAXIMUM |
| | AMOUNT OF TIMES ON THESE OVER RIDES. |
| | |
| | 27) NOTE: PLEASE SEE 109.3.6.4.4 |
| | PLANS WHICH ARE SIGNED, DATED AND SEALED BY AN |
| | ARCHITECT OR ENGINEER SHALL CONTAIN A STATEMENT THAT: * |
| | TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, |
| | THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND CHAPTER (FLORIDA |
| | STATUTES) 633. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES FOR ALL TRADES/TITLE SHEETS FOR EACH TRADE |
| | AND/OR TITLE BLOCKS. |
| | |
| | 28) NOTE: PLEASE PROVIDE A DETAIL/NOTE FOR ALL |
| | EMERGENCY AND EXIT LIGHTS WHICH ARE REQUIRED TO BE |
| | WIRED AHEAD OF ANY SWITCHING DEVICES. |
| | PLEASE KNOW THIS IS NOT A NEW CODE, HOWEVER SINCE THE |
| | IMPLEMENTATION OF CHAPTER 13 OF THE FBC. THIS |
| | JURISDICTION HAS HAD NUMEROUS INSTANCES WHERE THE |
| | EMERGENCY FIXTURES ARE BEING WIRED ON THE LOAD OF THE |
| | NEW OCCUPANCY SENSORS, OVER RIDES, TIMERS ETC. THIS |
| | SHOULD NOT HAVE TO BE MADE ON PLANS, HOWEVER PLEASE |
| | PROVIDE A DETAIL CLOUDED OFF OF THE CONTACTOR OR ON A |
| | SEPARATE DETAIL OF SOME KIND. |
| | FBC 106.1.2, NEC 700.12E. |
| | |
| | 29) NOTE: PLEASE SEE COLOR CODING FOR CONDUCTORS FOR |
| | 277/480V SHOULD BE BROWN, PURPLE , YELLOW. AS NO |
| | 277/480V IS BEING SHOWN AS PART OF THIS BUILDING, THIS |
| | COULD BE REDLINED ON PLANS. |
| | |
| | 30) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT CODE COMPLIANT COMMENTS. THIS IS ONLY |
| | A NOTICE BEING GIVEN AT THIS TIME. |
| | ** PLEASE KNOW BASED ON THE NOTES FOR ALL TRADES, ONE |
| | COMPLETE SET OF PLANS IS BEING RETAINED BY THIS |
| | OFFICE. |
| | |
| | |
| | |
| | |
| | ** PLEASE BE AWARE OF COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |