| Date |
Text |
| 2006-10-25 14:48:51 | 1. PLEASE INDICATE THE TYPES OF AUTOMOTIVE REPAIRS THAT |
| | ARE PLANNED FOR THE BUILDING. |
| | 2. PLANS SEEM TO INDICATE THAT THE BUILDING WILL BE |
| | FIRE SPRINKLER PROTECTED HOWEVER NO FIRE SPRINKLER |
| | PLANS WERE NOTED. |
| | 3. ON PAGE E-103 ONLY TWO ILLUMINATED EXIT SIGNS EXIST. |
| | EXIT SIGNAGE IS USED TO DIRECT PERSONS TO EXITS EVEN |
| | WHEN THEY ARE NOT CLEARLY OBVIOUS. |
| | 4. NO EMERGENCY LIGHTING DECLARED ON PAGE E-103. 5. NO |
| | EXIT SIGN MARKINGS SHOWN ON PAGE E-200. |
| | 6. PLEASE PROVIDE PRODUCT APPROVALS FOR THE CO |
| | DETECTORS PLANNED FOR USE. DO THEY COME FACTORY SET OR |
| | WILL CALIBRATION GAS BE NEEDED TO SET THESE POINTS. 7. |
| | NO EMERGENCY LIGHTS DISPLAYED FOR MEZZANINE ON PAGE |
| | E-102. |
| | 8. PLEASE PROVIDE A LIST OF CHEMICALS AND THEIR AMOUNTS |
| | PLANNED FOR THE BUILDING. |
| | 9. BUILDIND ADDRESS REQUIRED . A MINIMUM OF AT LEAST 6" |
| | IN HEIGHT AND 1" IN WIDTH. |
| | 10. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR |
| | WALLS AND CEILINGS IN NON AUTOMOTIVE WORK AREAS. 11. |
| | SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE SPRINKLER |
| | AND FIRE ALARM SYSTEM. |
| | 12. NO PORTABLE FIRE EXTINGUISHERS PROVIDED. |
| | 13. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR ALL HANDRAILS, GUARDRAILS, AND CABLE RAIL SYSTEMS. |
| | 14. PLEASE DECLARE OCCUPANCY TYPE AND OCCUPANT LOADS |
| | FOR THE BUILDING. |
| | 15. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | 16. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. 17. A |
| | KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. 18. IS THE |
| | BUILDING CONSIDERED OPEN OR CLOSED FOR DESIGN |
| | PURPOSES. |
| | 19. PLEASE DECLARE DISTANCE FROM EXHAUST TERMINATION |
| | POINTS TO ANY BUILDING OPENINGS. |
| | 20. PLEASE INDICATE HOW FLAMMABLE OR COMBUSTIBE LIQUIDS |
| | WILL BE STORED, HANDLED, AND DISPOSED OF WITHIN THE |
| | BUILDING. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709 |
| | |
| | MICHAEL A. WILLIAMS, FIRE PREVENTION CAPTAIN 805-6722 |