| Date |
Text |
| 2006-10-02 00:00:00 | *******UNSAT ****** |
| | |
| | |
| | 1)A) NOTE: PLEASE SEE PERMIT APPLICATION |
| | AND PLANS MENTIONS AND SHOWS "3021", |
| | HOWEVER THIS PROJETC IS LOCATED ON A |
| | LEGAL ADDRESS IN OUR SYSTEM OF "3001". |
| | PLEASE KNOW TITLE BLOCKS SHALL BE |
| | REVISED UPON CORRECTING OF ADDRESS. |
| | |
| | 1) NOTE: PLEASE BE SURE ALL OF THE |
| | FOLLOWING CODES ARE STATED ON PLANS AT A |
| | MINIMUM. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101, NFPA-30A AND 2004 FBC. |
| | PLEASE KNOW, THERE MAY BE OTHER CODES |
| | REQUESTED BY OTHER TRADES TO BE STATED |
| | ON PLANS RELEVANT TO DESIGN. |
| | |
| | 2) NOTE: PLEASE SEE MISSING LICENSING |
| | INFORMATION ON TITLE BLOCKS FOR ALL MEP |
| | PLANS AS REQUIRED PER FAC 61G15-23.002, |
| | FS 471.023 |
| | |
| | 3) NOTE: PLEASE NEC 511, AND PLEASE |
| | INDICATE ALLRELEVANT AREAS AND LAYOUT |
| | ON PLANS. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-101 7.8.1.3, |
| | 7.9.2.2. PLEASE SUBMIT AND SUPPLY ALL |
| | MIN PHOTO-METRICS REQUIRED FOR STAIR |
| | TOWERS UNDER NORMAL AND EMERGENCY POWER. |
| | PLEASE ALSO INDICATE LIGHTING LEVELS |
| | (MIN) REQUIRED FOR ALL OTHER AREAS OF |
| | EGRESS. PLEASE SEE THERE ARE AREAS ON |
| | PLANS WHICH DO NOT SEEM TO MEET THIS. |
| | 10FT CANDLES UNDER NORMAL AND 1FT CANDLE |
| | UNDER EM IN STAIRS. |
| | ALL OTHER AREAS 1FT MIN. |
| | |
| | 5) NOTE: PLEASE SEE THERE ARE AREAS OF |
| | EGRESS WHICH IS NOT INDICATING ANY |
| | EGRESS OR BATTERY BACK UP LTS. PLEASE |
| | SEE ALL AREAS OF COMMON USAGE |
| | INCLUDING MAIN ELECTRICAL ROOM, ELEVATOR |
| | EQUIPMENT RM AND OTHER AREAS ON PLANS |
| | WHICH WILL REQUIRE BATTERY BACK UP |
| | FIXTURES OF SOME SORT. PLEASE SEE |
| | 700.12E, 700.16, LS 101 7.8, 7.9, STATE |
| | ELEVATOR CODE. |
| | ** PLEASE KNOW, EM ILLUMINATION IS |
| | REQUIRED OUT OF THE BUILDING TO THE |
| | PUBLIC RIGHT OF WAY. |
| | PLEASE ALSO BE SURE TO ADJUST FIXTURE |
| | SCHEDULE FOR ALL. |
| | |
| | 6) NOTE: PLEASE LIST AND IDENTIFY ALL |
| | LIGHTING FIXTURES ON PLANS AND CORRELATE |
| | WITH THE SUBMITTED SCHEDULE. |
| | FBC 106.1.2, 106.3.5.1.2 ADMINISTRATIVE |
| | SECTIONS AS ADOPTED BY THE CITY OF WEST |
| | PALM BEACH. |
| | |
| | 7) NOTE: PLEASE PROVIDE ROOM AND AREA |
| | DESIGNATIONS ON PLANS FOR ALL SPACES. |
| | PLEASE KNOW, MANY ITEMS FOR REVIEW OF |
| | CODE COMPLIANCE MAY NOT BE DONE AT THIS |
| | TIME. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECT. |
| | |
| | 8) NOTE: PLEASE COMPLETE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE PANEL |
| | SCHEDULES SUBMITTED. |
| | 408.4, 310.16, 240.4 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE SEE 620.23 AND 620.24. |
| | PLEASE SEE LTS/RECEPTS FOR THE ELEVATOR |
| | ROOM(S) SHALL CONTAIN DEDICATED CIRCUITS |
| | AND MAY NOT FEED ANY OTHER AREAS. |
| | |
| | 10) NOTE: PLEASE SEE SOME LOCATION ON |
| | PLANS WHERE AN "S" IS SHOWN WHICH IS THE |
| | SYMBOL FOR "SWITCH" ON LEGEND, HOWEVER |
| | THEY ARE NOT SHOWN AS CONTROLLING |
| | ANYTHING? |
| | PLEASE COMPLETE, OR ADJUST. |
| | FBC 106.1.2 |
| | |
| | 11) NOTE: PLEASE SEE A BATH RM WITH NOT |
| | LT FIXTURE BEING SHOWN. |
| | PLEASE ALSO SEE BATH RMS WITH MULTIPLE |
| | STALLS SHALL ALSO CONTAIN EM BATTERY |
| | BACK UP FIXTURES. |
| | LS 101 7.8,7.9 |
| | |
| | 12) NOTE: PLEASE SEE FIRE REVIEW |
| | COMMENTS FOR GARAGE AREAS LTS, REQ'D EM |
| | BACK UP. |
| | AS PREVIOUSLY NOTED ABOVE FOR ELECTRICAL |
| | REVIEW ALSO. |
| | LS101 7.9 |
| | |
| | 13) NOTE: PLEASE SEE 2004 FBC CHAPTER 13 |
| | FOR CONTROLS FOR ALL LIGHTING. |
| | PLEASE INDICATE AND SHOW THE SYSTEM |
| | BEING PROPOSED. PLEASE PROVIDE |
| | SCHEDULING OF SYSTEMS. |
| | PLEASE PROVIDE OVER RIDES, LOCATIONS, |
| | AND AREAS FOR SEPARATE CONTROLS |
| | REQUIRED. PLEASE SEE FBC |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE SHOW AND INDICATE THE TYPE OF |
| | OVER RIDE DEVICES,A ND MAX ALLOWED |
| | TIMES. (NOTE: TIMER TYPE (4HRS MAX), |
| | OCCUPANT SENSOR TYPE 30MINS MAX). |
| | ALL AREAS WITH FLR TO CEILING HEIGHT |
| | PARTITIONS REQUIRE SEPARATE CONTROLS. |
| | PLEASE PROVIDE PERFORMANCE CALCULATIONS |
| | AND PLEASE SEE THE MAXIMUM PERMITTED |
| | "LIGHTING POWER DENSITIES" (LPD) ALLOWED |
| | FOR AREAS. |
| | PLEASE SEE SPACES AND USE PERMITTED IN |
| | TABLES. |
| | 13-415.2, 13-415.2.ABC.1, TABLES |
| | 13-415.2.B. |
| | ALL LPD'S ARE TO BE SHOWN. |
| | |
| | 14) NOTE: PLEASE SEE THIS IS NOT BEING |
| | CONSIDERED A SEPARATE "BUILDING" AND IS |
| | PART OF THE CURRENT STRUCTURE AS THIS |
| | NEW STRUCTURE CONTAINS OPENINGS ECT FOR |
| | EGRESS ETC. |
| | PLEASE SEE FBC DEFINITIONS. |
| | PLEASE SEE NEC 230.2, AS THE NEW |
| | PROPOSED SEPARATE SERVICE NOT BEING FED |
| | FROM THE EXISTING SERVICE LOCATION |
| | GROUPED ETC IS NOT PERMITTED AS SHOWN. 230.2,230.72 |
| | ETC. |
| | IN ORDER TO GRANT THE NEW SERVICE FOR A |
| | NEW "BUILDING", THIS WOULD REQUIRE AND |
| | "FIREWALL", 4 HR RATED, COLLAPSIBLE ON |
| | BOTH SIDES WITH OUT AFFECT THE |
| | STRUCTURAL INTEGRITY OF EITHER |
| | STRUCTURE. BY THE PLANS SUBMITTED,THIS |
| | IS NOT ACHIEVED AT THIS TIME. |
| | |
| | 15) NOTE: PLEASE SEE MISSING EXT/EM LT |
| | AS VEST, FOR EGRESS. |
| | LS 101 7.8, 7.9 |
| | PLEASE SEE PLANS ARE REDLINED FOR MANY |
| | AREAS IN WHICH SOME COMMENTS ARE |
| | RELEVANT, HOWEVER ARE IN NO WAY ALL. |
| | |
| | 16) NOTE: PLEASE SEE 250.50, AS THE NEW |
| | FOOTER STEEL SHALL BE PART OF THE |
| | EXISTING GROUNDING ELECTRODE SYSTEM. |
| | 250.50 |
| | |
| | 17) NOTE: PLEASE SEE AREA ON "MEZZ" |
| | LEVEL WHICH SEEMS TO INDICATE A/C |
| | EQUIPMENT. PLEASE SEE 210.63 FOR MISSING GFI.210.8B |
| | |
| | 18) NOTE: PLEASE SUBMIT ALL WIND LOAD |
| | CALCULATIONS FOR ROOF TOP LT POLES WITH |
| | EPA FIGURED FOR ALL LT FIXTURES |
| | PROPOSED. |
| | THE CALCULATIONS AND SPEC FOR POLES WILL |
| | BE REVIEWED FOR STRUCTURAL CONNECTIONS, |
| | WIND LOADS ETC BY THE STRUCTURAL |
| | REVIEWER. |
| | THEY MUST MEET FBC 2004 140MPH MIN, 3 |
| | SEC GUST. |
| | |
| | 19) NOTE: PLEASE SUBMIT THE MANUFACTURE |
| | SPECS /CUT SHEETS FOR THE TANKLESS WATER |
| | HEATER. PLEASE BE SURE THEY INDICATE THE |
| | NRTL LISTING. |
| | 110.3, 90.7. |
| | |
| | 20) NOTE: PLEASE SEE AS PLUMBING PLANS |
| | ALSO INDICATE BEING TIED INTO THE |
| | EXISTING BUILDING, IT SEEMS THE PERMIT |
| | APPLICATION WOULD BETTER DESCRIBE |
| | PROJECT AS AN ADDITION. |
| | THIS WILL BE DECIDED BY DESIGN FOR NOTES |
| | FROM ALL REVIEWER(S). |
| | |
| | ** PLEASE KNOW, AS THERE ARE ITEMS NOT |
| | IN DESIGN AT THIS TIME REQUIRED FOR |
| | REVIEW, THERE MAY BE COMMENTS ON FURTHER |
| | REVIEWS. |
| | |
| | ** PLEASE BE AWARE OF COMMENTS FROM |
| | OTHER TRADES WHICH WILL AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2006-10-01 00:00:00 | *** REVIEW IN PROGRESS, PLANS TO GO |
| | INTO "F" STATUS, NOTES OT FOLLOW. |
| 2006-09-29 00:00:00 | IN ELEC FOR REVIEW, |