| Plan Review Notes For Permit 06090390 |
| Permit Number |
06090390 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-14 00:00:00 | *** DENIED *** | | | 1) MANUAL J CALCULATIONS ON FILE ARE | | | CALLING FOR 12,577 SENSIBLE BTU'S, YOUR | | | MECHANICAL PLANS ARE CALLING FOR 20,720 | | | SENSIBLE BTU'S, THE PLANS CAN ONLY CALL | | | FOR 20% MORE THAN THE MANUAL J CAL'S, | | | PER 2004 FBC CH.13 607.1.ABC.1.1 . | | | PLEASE SEE ATTACHED COPY OF THE MANUAL J | | | CAL'S. | | | | | | 2) PLEASE SHOW THE LOCATION OF THE | | | CLOTHES DRYER VENT AND BATHROOM EXHAUST | | | FANS ON THE MACHANICAL PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|