2006-09-14 00:00:00*** DENIED ***
 1) MANUAL J CALCULATIONS ON FILE ARE
 CALLING FOR 12,577 SENSIBLE BTU'S, YOUR
 MECHANICAL PLANS ARE CALLING FOR 20,720
 SENSIBLE BTU'S, THE PLANS CAN ONLY CALL
 FOR 20% MORE THAN THE MANUAL J CAL'S,
 PER 2004 FBC CH.13 607.1.ABC.1.1 .
 PLEASE SEE ATTACHED COPY OF THE MANUAL J
 CAL'S.
  
 2) PLEASE SHOW THE LOCATION OF THE
 CLOTHES DRYER VENT AND BATHROOM EXHAUST
 FANS ON THE MACHANICAL PLANS.
  