| 2006-09-27 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED ON |
| | THE ISOMETRIC DRAWING FOR GAS PLAN |
| | REVIEW: |
| | |
| | 1. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: THIS INCLUDES THE EXISTING GAS |
| | SYSTEM PLEASE SEE THE ATTACHED PERMIT |
| | INFORMATION INDICATING GAS AT SAID |
| | ADDRESS. |
| | |
| | 2. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: REFERENCE NOTE ON COMMENT 1 |
| | |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT AND INSTALLATION INSTRUCTIONS |
| | TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND THE FBC-2004 FUEL GAS |
| | CODE SEC 402.2 |
| | NOTE: NEED SHEETS ON REGULATORS AND |
| | GENERATOR. |
| | |
| | 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |