2008-04-03 16:45:27BUILDING PLAN REVIEW
 PERMIT: 06090366
 ADD: 221 CLEMATIS STPHASE II SUITE 104 CONT:
 CASTLE FLORIDA
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW:
 ACTION: DENIED
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PLANS ARE MISSING THE BUILDING TYPE? TABLE 503/
 601.
  
 2) PLEASE SEE A1VERSES A4 FOR LAYOUT OF FURNATURE AND
 FOR LIFE SAFETY, THEY DO NOT MATCH AT THE FRONT OF THE
 UNIT BY THE GLASS WINDOW UNITS. PLANS INDICATE A COMMON
 PATH OF TRAVEL OF 76'-0".
 PLEASE SEE 1024.8 COMMON PATH OF TRAVEL FOR ASSEMBLY
 OCCUPANCY.
  
 3) ADDITIONAL INFORMATION IS REQUIRED, COVER SHEET
 INDICATE THESE PLANS ARE FOR PHASE II AREA IS HATCHED
 TO LOCATE AREA OF WORK TO BE COVERED UNDER PHASE II,
 BUT THE SHEET A-2 INDICATES WORK UNDER PHASE I INCLUDED
 IN THIS PLAN, POOL HALL STOREFRONT ELEVATIONS. NOTE
 SHEET A-4 INDICATES A "NEW TENANT" ON THE MEZZANINE
 LEVEL. NOTE WHEN YOU ENCLOSE THE MEZZANINE LEVEL IT
 WILL BECOME A TRUE SECOND FLOOR SEE 505.2 AREA OF
 MEZZANINE, PLEASE REMOVE THE WORDING OF MEZZANINE.
  
 4) THE WORDING OF "NEW TENANT" ON THE MEZZANINE LEVEL
 ALSO CREATES ANOTHER ISSUE, IN OUR MEETINGS IT WAS
 DISCUSSED IT IS THE SAME TENANT A NEW AREA IS BEING
 OPENED. NEW TENANT WILL REQUIRE, TENANT SEPERATION
 WALLS OR FIE WALLS REQUIRING A ONE HOUR RATING OF THIS
 WALL, SEE 708.3. IF THE INTENT IS DIFFERENT THEME
 AREAS, INDICATE SUCHBUT SINGLE TENANT.
  
 5)SHEET A-2 DETAIL# 2, STAIR ELEVATION INDICATES A
 6'-9" CLEAR HEIGTH BUT IN ACTUALLITY THE PLAN INDICATES
 6'-0" FROM THE EDGE OF THE NOSING, PLEASE SEE 1009.2
 HEADROOM.
  
 6)SHEET A-2 DETAIL# 2 INDICATES THE MECHANICAL
 EQUIPMENT AS BEING HOUSED WITHIN A MEZZANINE, THIS
 SPACE IS NOT TO BE CONSIDERED A MEZZANINEBUT A
 PENTHOUSE SEE 1509.2.
 THE STAIR THAT LEADS TO THE MECHANICAL PENTHOUSE
 INDICATES STORAGE IN WHAT WOULD BE CONSIDEREDTHE EXIT
 THAT LEADS TO THE MECHANICAL PENTHOUSE. THE COMMON WALL
 FROM THE MECHANICAL PENTHOUSE AND ELECTRIC ROOM IS TO
 BE 1 HOUR RATED. THIS WOULD CREATE PART OF THE RATED
 VERTICAL EXIT THE OTHER WALL THAT WOULD BE COMMON TO
 THE WOMENS RESTROOM TO THE DOORWAY WOULD ALSO CREATE
 THE 1 HR RATED EXIT TO THE MECHANICAL PENTHOUSE.
  
 7) SHEET A-4 PLEASE INDICATE COMPLIANCE WITH 11-5.1 AND
 11-5.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved