| Plan Review Notes For Permit 06090366 |
| Permit Number |
06090366 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-12-15 08:59:11 | REVISION DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 11 | | | | | | 1. SHT A-1 PER TABLE 403.1 A DRINKING FOUNTAIN IS | | | REQUIRED. PLEASE INDICATE ON MINIMUM FIXTURES REQUIRED, | | | SHOW THE LOCATION ON THE FLOOR PLAN AND SUBMIT A DETAIL | | | SHOWING COMPLIANCE WITH SECTIONS 11-4.15 WITH ALL | | | SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING IF THE DRINKING FOUNTAIN IS NOT A HI/LOW | | | TYPE. | | | | | | 2. SHTS P-1 KEY NOTE #8, P-2 WATER HEATER DETAIL & P-3 | | | SANITARY RISER DIAGRAM. HUB DRAIN ABOVE THE CEILING FOR | | | THE T/P, PAN DRAIN, THERMAL EXPANSION VALVE IS NOT | | | APPROVED. THE AIR GAP FOR THE P/T VALVE SHALL BE | | | VISIBLE, A TRAP PRIMER IS REQUIRED PER SECTION 1002.4 | | | AND THERE IS NO PIPE, TRAP SUPPORT INDICATED AS | | | REQUIRED PER SECTION 308.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|