Plan Review Notes
Plan Review Notes For Permit 06090366
Permit Number 06090366
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2007-07-24 10:48:38***DENIED***
  
 1) OK
  
 2) OK
  
 3) OK
  
 4) OK
  
 5) OK
  
 6) OK
  
 7) OK
  
 8) OK
  
 9) OK
  
 10) PLEASE NOTE THAT ONLY ELECTRICAL CONDUIT THAT
 SERVES THAT PARTICULAR STAIRWAY WOULD BE ALLOWED WITHIN
 THE EXIT ENCLOSURE.
  
 11) OK
  
 12) OK
  
 13) OK
  
 14) OK
  
 15) OK
  
 16) OK
  
 17) OK
  
 18) OK
  
 19) OK
  
 NEW COMMENT:
  
 1) THE MINIMUM HEADROOM REQUIREMENT FOR NEW AND
 EXISTING STAIRS IS EIGHTY (80") IN ACCORDANCE WITH NFPA
 101.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756