| 2007-06-20 20:23:51 | 2007-06-20 20:23:51 |
| | |
| | ** HOLD REMOVED** |
| | |
| | *** UNSAT 3RD REVIEW *** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| | CHAPTER 13 HAS NOT BEEN ACHIEVED ON PLANS FOR CODE |
| | COMPLIANCE. PLEASE SEE PLANS NOW INDICATE LIGHTING |
| | CONTROLS THROUGH-OUT BUILD OUT HOWEVER NO TIMES ON |
| | DEVICES IS NOTED OR SHOWN. PLEASE SEE THE TYPE OF |
| | DEVICES AS LISTED DOES NOT SHOW UP ON THE MANUFACTURES |
| | WEBSITE FOR THE DEVICE AS LISTED ON LEGEND. NO |
| | INFORMATION COULD BE LOCATED ON THESE. PLEASE SEE THE |
| | COMPLETE LIST OF DEVICES PRINTED OUT ON ATTACHED SHEETS |
| | FROM MANUFACTURE WHICH DOES NOT COORDINATE WITH THE |
| | DEVICES AS NOTED. PLEASE PROVIDE INFORMATION ON DEVICES |
| | AS NOTED. |
| | PLEASE SEE NO COVERAGE FOR CONTROL OF EGRESS LIGHTING |
| | FROM SECOND FLOOR. SEE ELECTRICAL COMMENT WITH RESPECT |
| | TO THE LIFE SAFETY METHODS OF CONTROL REQUIRED. PLEASE |
| | SEE THE AREAS WHICH THESE DEVICES ARE BEING PLACED IN |
| | MANY LOCATIONS ARE IN QUESTION. PLEASE SEE BATHROOMS AS |
| | SEPARATE SPACES MAY NOT HAVE THE COVERAGE NEEDED. MORE |
| | INFORMATION ON TYPES OF DEVICES AND MAXIMUM TIMES ON |
| | ARE NEEDED. |
| | PLEASE PROVIDE DETAIL FOR EMERGENCY/EXIT LIGHTING AS |
| | THESE ARE SHOWN ON THE SAME CONTROL OF DIMMERS OR |
| | SWITCHES. NOTE OR DETAIL THESE ON THE HOT/LINE SIDE OF |
| | THESE CONTROLS. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS THE FIXTURES, |
| | TYPES, AND WATTAGE DO NOT CORRELATE WITH PLANS AND |
| | FIXTURE LEGEND. |
| | PLEASE SEE 13-415.1.ABC.1.1,.1.2, 13-415.1.AB.1.1. |
| | **PLEASE SEE THE OWNER AGENT IS NOT SIGNED ON ENERGY |
| | CALCULATION SHEETS AS REQUIRED. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WHICH |
| | REQUESTED PHOTO-METRICS FOR ALL EGRESS PATHS BASED ON |
| | NEW CHANGE IN OCCUPANCY. PLEASE SEE THERE ARE STILL |
| | STAIR AREAS WHICH DO NOT CONTAIN ANY LIGHTING |
| | PHOTO-METRICS. THESE HAVE BEEN REDLINED ON PLANS. |
| | PLEASE SEE E-5 WHERE THE DETAILS ON THE LOWER RIGHT |
| | HAND SIDE SHOW BOTH DETAILS AS ENTRY STAIRS NORMAL? |
| | PLEASE SEE AREA WHICH EXITS INTO THE EXISTING AREA |
| | WHICH IS SHOWING OCCUPANCY TYPE DEVICES LOCATED AT THE |
| | UPPER LEVEL HOWEVER NOT METHOD OF CONTROL FOR THE |
| | LIGHTING ON STAIRS FROM LOWER LEVEL OR IN STAIR AREA. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2, 7.8.1.2.2, FBC |
| | CHAPTER 10, 1006.1.2. |
| | |
| | 3) NOTE: PLEASE SEE THE REVISED RISER WHICH INDICATES |
| | THE SAME CONDUCTORS BEING TAPPED FROM GUTTER TO THE NEW |
| | MAIN WHICH ARE BEING SHOWN AS RATED 800AMPS INTO A NEW |
| | 600AMP MAIN? PLEASE CLARIFY THE SIZES INTO THIS MAIN |
| | AND REVISE CONDUCTORS AT THIS TIME IF NEED. THE LARGER |
| | CONDUCTORS ARE NOT A CODE VIOLATION BUT MAY NOT FIT. |
| | PLEASE ALSO CLARIFY THE EXISTING SERVICE ENTRANCE |
| | CONDUCTOR SIZES FROM OUTSIDE INTO GUTTER. |
| | 310.16, 240.4 |
| | |
| | 4) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH |
| | RESPECT TO MINIMUM HEAD ROOM CLEARANCE FOR DETAIL SHOWN |
| | ON E-5 FOR STAIRWAY. DETAIL SHOWS 76 INCHES WHICH DOES |
| | NOT SEEM TO MEET BUILDING CODE. |
| | |
| | 5) NOTE: PLEASE SEE THE PLANS INDICATE NEW SUITE |
| | NUMBERS FOR NEW TENANT SPACES HOWEVER THIS IS ACTUALLY |
| | BEING MADE AND ADDED INTO THE SAME EXISTING TENANT |
| | SPACE AS THE FIRST FLOOR SUITE 104. NEW EXTENSIONS FOR |
| | ADDRESS WAS GIVEN AND TITLE BLOCKS INDICATE THIS AS |
| | SEPARATE TENANT SPACES, HOWEVER THIS IS NOT POSSIBLE |
| | WHEN THERE IS NO TENANT SEPARATION FROM THE FIRST FLOOR |
| | EXISTING TENANT AREA. |
| | |
| | 6) NOTE: PLEASE SEE THE VALUATION WAS INCREASED AND |
| | ADDITIONAL FEES ARE OWED. |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS REVIEW A NOTICE WAS GIVEN |
| | WITH RESPECT TO CODE COMPLIANT COMMENTS BEING REPEATED |
| | PER FS 553.80(2)(B). PLANS ARE BEING RETAINED AND THE |
| | PLANS, ENERGY CALCULATIONS, AND REVIEW NOTES WILL BE |
| | GONE OVER AS CODE COMPLIANCE HAS NOT BEEN MET FOR THE |
| | THIRD REVIEW. PENDING PIER REVIEW A 4X FEE FOR THE PLAN |
| | REVIEW PORTION OF THE PERMIT FEE MAY BE ASSESSED TO THE |
| | DESIGNER OF RECORD AS REQUIRED BY THE FLORIDA |
| | STATUTES. |
| | |
| | THIS FEE HAS NOT YET BEEN ASSESSED AND IT NOT THE |
| | RESPONSIBILITY OF THE OWNER OR CONTRACTOR OF RECORD. |
| | |
| | ** AS STATED ON ALL PREVIOUS REVIEWS, PLEASE CALL TO GO |
| | OVER ANY COMMENTS, IF THERE ARE ANY QUESTIONS OR IF THE |
| | COMMENTS AS TYPED ARE NOT UNDERSTOOD. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| 2007-06-20 09:29:36 | 2007-06-20 09:29:36 |
| | ** ON HOLD ** |
| | |
| | A MESSAGE WAS LEFT ON VOICE MAIL OF MR. JOHN SATEU OF |
| | CASTLE CONSTRUCTION FOR UPDATED VALUATION TO BE GIVEN |
| | BEFORE REVIEW CAN BE DONE. |
| | THIS WAS REQUESTED ON TWO PREVIOUS REVIEWS AND NO |
| | INFORMATION AND/OR CHANGES WERE MADE TO PERMIT |
| | APPLICATION.PLEASE SEE FBC 108.3 VALUE SHALL INCLUDE |
| | ALL LABOR, MATERIALS, EQUIPMENT, DESIGN ARCHITECT AND |
| | ENGINEERING COSTS EVEN IF ANY OF THIS IS OWNER |
| | SUPPLIED. |
| | PLANS ARE ON HOLD IN ELECTRICAL FOR REVIEW. |
| | IF A VALUE IS NOT PROVIDED, ONE WILL BE ASSESSED BASED |
| | ON PLANS AND VALUATION TABLES IN THE FBC AND ADOPTED |
| | REFERENCES FOR VALUATION GUIDES. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH. |
| | 561-805-6717 |