2007-07-17 20:44:28BUILDING PLAN REVIEW
 PERMIT: 06090366
 ADD: 221 CLEMATIS ST SUITE 201 & 202
 CONT: CASTLE FLORIDA
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) COMPLIED.
  
 3A)3RD REQUEST, PLANS INDICAE A CODE SUMMARY A TYPE
 II-BBUILDING SPRINKLERED AND A ASSEMBLY GROUP A-2.
 TABLE 503 A-2 TYPE II-B ALLOWABLE AREA IS 9,500 SQ FT 2
 STORIES. PLANS INDICATE THE FOOTPRINT OF THE BUILDING
 AS 21,213 SQ FT.
 PLEASE PROVIDE WHAT AREA AND OR HEIGHT INCREASES THAT
 YOU MAY TAKE, ALSO NOTE THIS ISCONSIDERED A (4) STORY
 BUILDING, THE
 3RD AND 4TH FLOORS BEING PROPOSED A BUSINESS
 OCCUPANCY.TABLE 503, 504.2 AUTOMATIC SPRINKLER
 INCREASES.
 NEW COMMENT: YES THE SPRINKLER AND FRONTAGE INCREASES
 WILL PROVIDE THE AREA FOR A TYPE II-B BUILDING, THE
 **HEIGHT** INCREASE IS ONLY ONE ADDITIONAL STORY. THE
 DESIGN TEAM WILL NEED TO EVALUATE IF THE TYPE IIA WILL
 MAKE THE REQUIREMENTS OF TABLE 503FOR A FULLY
 SPRINKLERED BUILDING. NOTE THIS WILL MEAN THE TOTAL
 BUILDINGS COLUMNS TO BE 1 HR FIRE RATED, FLOOR
 ASSEMBLIES SEE TABLE 601.
  
 3B)(1)COMPLIED.
  
 3B)(2)COMPLIED, NOT GOING TO CHANGE THE EXTERIOR OF
 THE BUILDING.
  
 3C)(1) COMPLIED, REMOVED FROM THIS PERMIT, UNDER
 SEPERATE PERMIT.
 PLEASE NOTE THERE IS NO MENTION OF THE EXITS AT
 THE REAR OF THE BUILDING ADJACENT TO THE ALLEY WAY. OUR
 JOBSITE MEETING (LAST
 WEEK OF DEC) REVEALED THE WEST EXIST STAIRS
 TO HAVE SEVERAL CODE VIOLATIONS:
 (1) THE EXIT DOOR TO THE STAIRWAY SWUNG INTO THE
 STAIRWELL, OCCUPANT LOAD > 50.
 (2) THERE APPEARED TO BE A KITHEN EXHAUST DUCK
 CUT INTO THE EXIT.
 (3) THERE ALSO WAS A VESTIBULE AREA DIRECTLY
 BEHIND THE STAIRWELL THE
 EXHAUST DUCK DUMPED INTO, THERE IS ANOTHER
 EXIT DOOR NOT DETERMINED
 WHERE IS AN EXIT FROM
 (4 THE STAIRWELL WAS NOT TRUELY FIRE RATED. (5)
 THERE WAS WINDOWS ON THE PROPERTY LINE. (6) AT
 THE TOP OF THE STAIRWAY NO DOOR OR ENCLOSURE.
 (7) IT APPEARS THAT THERE IS PLUMBING 6"OR 8" AT
 THE TOP OF THE LANDING
 (8) ALSO STAIRS TO THE MEZZANINE LEVEL ALSO HAD
 ISSUES WITH
 ELECTRICAL CONDUCTORS RUNNING THROUGH THE
 STAIRWELL.
 (9) THERE ALSO APPEARS TO BE HEIGTH PROBLEMS,
 MINIMUM HEADROOM
 (10) NO EXIT LIGTS OR DIRECTIONAL SIGNS
  
 3C()2)COMPLIED, UNDER A SEPERATE PERMIT.
 THE STAIRWELL TO THE EAST END OF THE ASSEMBLY
 OCCUPANCY SUITE# 202ALSO HAD SEVERAL CODE VIOLATIONS
 :
 (1) STORAGE IN THE STAIRWELL
 (2) ELECTRIC PANELS AT EACH FLOOR LEVEL
 (3) NO APPROVED EXIT LIGHTING, OR DIRECTIONAL
 SIGNS
 (4) THE EXIT DOOR ALSO SWINGS OUT OVER THE
 PROPERTY LINE.
 (5) IT APPEARS THERE IS ALSO PLUMBING IN THE
 STAIRWELL.
  
 4) WILL REFER BACK TO 3A) FOR ANSWER.
  
 5) COMPLIED, REMOVED FROM SCOPE OF WORK.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8A)COMPLIED, REMOVED FROM SCOPE OF WORK.
  
 8B)COMPLIED. REMOVED FROM THE SCOPE OF WORK.
  
 8C)COMPLIED. REMOVED FROM THE SCOPE OF WORK.
  
 8D) COMPLIED, REMOVEDFROM THE SCOPE OF WORK.
  
 8E)COMPLIED, REMOVED FROM SCOPE OF WORK.
  
 9) COMPLIED.
  
 10) COMPLIED, REMOVED FROM THE SCOPE OF WORK.
  
 11) COMPLIED.
  
 12)COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18)COMPLIED.
  
 19) COMPLIED, THE EAST EXIT IS IN A 2HR RATED SHAFT,
 4STORY BUILDING .
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) COMPLIED.
  
 23) COMPLIED.
  
 24) COMPLIED.
  
 25) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]