| 2007-01-17 14:43:59 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. PERMIT APPLICATION STATES GROSS |
| | SQUARE FOOTAGE AS 5423SF. COVER SHEET |
| | INDICATES 54243SF BAR, AND 3571SF POOL |
| | HALL. PLEASE CLARIFY. SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 2. ALL ARCHITECTURAL SHEETS. THE ADDRESS |
| | ON THE TITLE BLOCK DOES NOT RELFECT THE INFORMATION FOR |
| | THE ADDRESS ON THE DBPR |
| | WEBSITE. PLEASE CLARIFY. (SEE ATTACHED |
| | SHEET). FAC 61G1-16.004(1) FS 481.219. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 3. SHT A-1 SUITE 202 DEMO NOTES. IN THE |
| | REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS ARE PROHIBITED. |
| | SECTION 704.5. SUBMIT AN EXISTING FLOOR |
| | PLAN TO DETERMINE THE LOCATION OF ALL |
| | DEMO'D PLUMBING SYSTEMS, AND TO VERIFY |
| | THE EXTENT OF THE DEMOLITION. SECTION |
| | 106.1.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 9. ROUTE PLANS TO THE PALM BEACH COUNTY |
| | HEALTH UNIT DIVISION OF ENVIRONMENTAL |
| | HEALTH FOR REVIEW PRIOR SO RESUBMITTING |
| | TO THE CITY WPB FOR REVIEW. A MINIMUM OF |
| | 2 SETS OF PLANS SHALL BE STAMPED AS |
| | REVIEWED BY THE HEALTH DEPT. SECTION |
| | 102.2.1. |
| | ****NO RESPONSE, NOT ADDRESSED |
| | |
| | 10. SHT P-1 KEY NOTE #4, AND SHT P-3 |
| | SANT. RISER DIAGRAM. EVERY DRY VENT |
| | SHALL RISE VERTICALLY TO A MINIMUM OF 6" |
| | ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST |
| | TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | SECTION 905.4. |
| | ****RESPONSE NOTED, BUT THE VENTS ARE STILL SHOWN ON |
| | SHT P-3. THESE VENTS BETWEEN THE W/C'S ARE NOT |
| | REQUIRED, AND DO NOT MEET THE CODE REQUIREMENTS OF |
| | SECTION 905.4. |
| | |
| | 11. OK |
| | 12. OK |
| | |