Plan Review Notes
Plan Review Notes For Permit 06090366
Permit Number 06090366
Review Stop P
Sequence Number 2
Notes
Date Text
2007-01-17 14:43:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. PERMIT APPLICATION STATES GROSS
 SQUARE FOOTAGE AS 5423SF. COVER SHEET
 INDICATES 54243SF BAR, AND 3571SF POOL
 HALL. PLEASE CLARIFY. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. ALL ARCHITECTURAL SHEETS. THE ADDRESS
 ON THE TITLE BLOCK DOES NOT RELFECT THE INFORMATION FOR
 THE ADDRESS ON THE DBPR
 WEBSITE. PLEASE CLARIFY. (SEE ATTACHED
 SHEET). FAC 61G1-16.004(1) FS 481.219.
 ****NO RESPONSE, NOT ADDRESSED.
  
 3. SHT A-1 SUITE 202 DEMO NOTES. IN THE
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS ARE PROHIBITED.
 SECTION 704.5. SUBMIT AN EXISTING FLOOR
 PLAN TO DETERMINE THE LOCATION OF ALL
 DEMO'D PLUMBING SYSTEMS, AND TO VERIFY
 THE EXTENT OF THE DEMOLITION. SECTION
 106.1.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH FOR REVIEW PRIOR SO RESUBMITTING
 TO THE CITY WPB FOR REVIEW. A MINIMUM OF
 2 SETS OF PLANS SHALL BE STAMPED AS
 REVIEWED BY THE HEALTH DEPT. SECTION
 102.2.1.
 ****NO RESPONSE, NOT ADDRESSED
  
 10. SHT P-1 KEY NOTE #4, AND SHT P-3
 SANT. RISER DIAGRAM. EVERY DRY VENT
 SHALL RISE VERTICALLY TO A MINIMUM OF 6"
 ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST
 TRAP OR TRAPPED FIXTURE BEING VENTED.
 SECTION 905.4.
 ****RESPONSE NOTED, BUT THE VENTS ARE STILL SHOWN ON
 SHT P-3. THESE VENTS BETWEEN THE W/C'S ARE NOT
 REQUIRED, AND DO NOT MEET THE CODE REQUIREMENTS OF
 SECTION 905.4.
  
 11. OK
 12. OK
  