Plan Review Notes
Plan Review Notes For Permit 06090366
Permit Number 06090366
Review Stop M
Sequence Number 2
Notes
Date Text
2006-12-19 18:21:01PLAN DENIED
 1) PLEASE PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS FOR EVR 1& 2.
 2) PLEASE PROVIDE A CURB TO ROOF TIE DOWN DETAIL ON
 PLANS.
 3) YOU CAN NOT USE GALVANIZED STRAP OVER THE RTU FOR
 TIE DOWN. SEE SECTION 306.5 EQUIPMENT AND APPLIANCES ON
 ROOFS FBC (M ) 2004
 PLAN REVIEW BY HAROLD MOSER 561-805-6732