Plan Review Notes
Plan Review Notes For Permit 06090366
Permit Number 06090366
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-23 13:17:47** UNSAT 2ND REVIEW **
  
 ** A FIELD MEETING WITH THE CONTRACTOR/ARCHITECT SHALL
 BE SCHEDULE AT THE EARLIEST POSSIBLE TIME TO VISIT
 SITE. THERE ARE SOME AREAS OF CONCERN WITH THE CREATION
 ONE NEW SPACE AND ADJOINING THE EXISTING SPACE TO
 BUILDING ADJACENT.
  
 THERE MAY ALSO BE ELECTRICAL COMMENTS TO FOLLOW AFTER
 FIELD MEETING IS HELD.
 PLEASE CONTACT THIS OFFICE AS SOON AS POSSIBLE TO SET
 UP A TIME. IF POSSIBLE BEFORE THE NEW YEAR. 26TH -28TH
 OF DECEMBER. THIS WILL HELP IN THE REVIEW OF SAID PLANS
 AND TO CLERIFY ITEMS AS SHOWN ON PLANS.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM THE
 PREVIOUS REVIEW WITH A NO OR OK FOR THE SAME NUMERICAL
 DESIGNATION AS PREVIOUS REVIEW. PLEASE SEE SOME MAY
 CONTAIN A NO/OK, AS PART OF A COMMENT MAY HAVE BEEN
 ADDRESSED HOWEVER NOT FULLY.
  
 ** PLEASE SEE ANY NEW COMMENTS BASED ON PLANS SUBMITTED
 MAY BE AT THE END OF THE PREVIOUS REVIEW NOTES.
  
  
  
  
 1) NOTE: OK.
  
 2) NOTE: NO. PLEASE KNOW BASED ON WORK AS SHOWN AND
 WILL BE REQUIRED THE VALUE IS SUBSTANTIALLY LOW AND ONE
 WILL BE ASSESSED IF NOT ADJUSTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SHALL BE
 BASED ON ALL LABOR AND MATERIALS EVEN IF ANY MATERIALS
 ARE OWNER SUPPLIED. PLEASE KNOW, WHEN A VALUE IS LOW,
 ONE WILL BE ASSESSED PER FBC 108.3 USING THE
 MARSHALL'S& SWIFT
 GUIDE AS ADOPTED BY THE FLORIDA BUILDING CODE.
  
 3) NOTE:NO, PLEASE SEE THE OVERVIEW FOR THE CONDUITS
 BEING ENCASED DOES NOT PROVIDE THE DETAIL AS NEED FOR
 ALL CLEARANCES ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE BUILDING REVIEW NOTES AS 2ND FLOOR GARAGE
 DOOR.
 PLEASE SEE EXIT STAIRS MENTIONS TO ENCASED CONDUIT
 COMING IN THROUGH STAIRS, MUST PROVIDE COMPLETE
 ARCHITECTURAL DETAIL FOR DEPTH, DISTANCES, HEADROOM
 ETC.
 PLEASE ALSO SEE NO MORE THAN 8' OF UNDER PROTECTED
 CONDUCTORS ARE PERMITTED INSIDE THE BUILDING. THIS MAY
 ALSO INCLUDE ENCASEMENT OF CONDUITS IN MAIN ELECTRICAL
 ROOM.
 PLEASE SEE 230.70, 240.6
  
 4) NOTE: NO, PLEASE KNOW AT THIS TIME THE NEW PROPOSED
 SERVICE IS NOT GRANTED BY SPECIAL PERMISSION AS
 REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE SIZES AND VOLTAGES FOR ALL EXISTING
 SERVICES.
 PLEASE SEE 230.2 AS AT THIS TIME THIS NEW SERVICE IS
 NOT GRANTED. AS PLANS SHOW, THIS SEEMS BE ADDING
 ADDITIONAL SERVICES WHERE NOT ALL INFORMATION IS
 PROVIDED TO POSSIBLY GRANT ANY SPECIAL PERMISSION.
  
 5) NOTE: NO, PLEASE SEE ENERGY CALCULATIONS STILL
 INDICATE MANUAL CONTROLS.
 PLEASE SEE NO SYSTEM IS BEING SHOWN IN DETAIL.
 PLEASE SEE NO TIMES FOR SCHEDULING.
 PLEASE SEE NO TIMES ON OVER RIDE DEVICES REQUIRED.
 PLEASE SEE NO DEVICES LOCATED IN SEPARATE SPACES.
 PLEASE SEE SECTIONS AS GIVEN IN PREVIOUS REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2,
 .1.3,.
 PLEASE SEE 13-415.1.B, 13-415.2,
 13-415.2.ABC.1, TABLES 415.2.C.1,
 415.2. B.1
 PLEASE COMPLY WITH THIS.
  
 6) NOTE: OK/NO, PLEASE SEE ADDRESSING ON SOME SHEETS DO
 NOT CORRELATE.
 PLEASE SEE E-4.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL SUITE NUMBERS ON TITLE BLOCKS ON
 PLANS AS REQUIRED ON ALL SHEETS.
 FAC 61G1-16.004, 61G15-23.002
  
 7) NOTE: NO, NO INFORMATION SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2, AS A MIN OF 10FT
 CANDLES IS REQUIRED UNDER NORMAL AND 1FT CANDLE MIN
 UNDER EM PWR.
 PLEASE PROVIDE LIGHTING LEVELS.
  
 8) NOTE:NO/OK, SOME SHOWN, HOWEVER AS LIGHTING LEVELS
 HAVE NOT BEEN PROVIDED ADDITIONAL FIXTURES MAY BE
 REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 ALONG WITH NOTE #7 ABOVE PLEASE INDICATE ALL EXISTING
 OTHER EMERGENCY LIGHTING AND EXIT LIGHTING AS THIS
 SPACE IS BEING INTRODUCED INTO THE 2ND FLR AND IF
 EXISTING DOES NOT MEET CODE, THEN THEY WILL BE
 REQUIRED.
 LS 101 7.8, 7.9, 700.12E.
  
 9) NOTE: NO, PLEASE SEE ONLY TWO ITEMS ON ONE PANEL ARE
 BEING NOTED FOR THIS. PLEASE SEE ALL CONTINUOUS SHALL
 BE INDICATED AS SUCH.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125% 215.3,
 230.42 ETC.
  
 10) NOTE: NO, PLEASE KNOW BASED ON THE LAYOUT FOR
 SPACES AND WHICH TENANT IS WHICH AND REQUIRED
 SEPARATION REQUIREMENTS, THERE MAY BE OTHER ELECTRICAL
 WHICH WILL NEED TO BE SHOWN. PLEASE KNOW BASED ON SITE
 MEETING AND NOTES ABOVE, THE SERVICE AND EQUIPMENT AS
 SHOWN IS NOT YET GRANTED OR APPROVED FOR REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL ELECTRICAL PANELS ON POWER PLANS.
  
 11) NOTE: OK.
  
 12) NOTE: NO/OK. SOME ITEMS CAN NOT BE VERIFIED FOR
 CODE COMPLIANCE AT THIS TIME. PLEASE KNOW SINCE NOTED
 ABOVE FOR A REQUIRED SITE MEETING THERE MAY BE CHANGES
 WHICH WILL AFFECT THE ELECTRICAL PLANS AS SHOWN.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE BLDG REVIEW COMMENTS AS DOOR FROM MAIN
 ELECTRICAL ROOM IS SHOWN IMPEDING THE EGRESS OF
 OCCUPANTS. PLEASE SEE THE DOOR REQUIREMENTS MAY
 CHANGE.
  
 13) NOTE: NO. SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL SCHEDULE SHALL BE SPECIFIC TO ROOMS
 AND AREAS IN WHICH LTS AND RECEPTS FEEDS. IE; BATH LTS,
 POOL AREA ETC.
 ** IT IS KNOWN, THAT THESE WILL MOST LIKELY CHANGE
 DURING THE CONSTRUCTION.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE INDICATE ALL LIGHTING AND SOUND LEVELS
 FOR FIRE HORN AND STROBE DEVICES. PLEASE SEE FBC
 11-4.28.1, .2, .3(4). THIS HAS NOW BECOME A REQUIREMENT
 FOR ELECTRICAL PLAN REVIEW.
 PLEASE INDICATE BASE REQUIRED SYSTEM AND SUBMIT PLANS.
 FBC 106.3.5.1.1 ADMIN SECTION
  
 2) NOTE: PLEASE KNOW DUE TO SOME AREAS OF CONCERN ON
 PLANS NOT YET CLEAR FOR REVIEW, THERE MAY BE FURTHER
 COMMENTS.
  
 3) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-21 20:48:00IN ELEC FOR REVIEW