| 2006-12-23 13:17:47 | ** UNSAT 2ND REVIEW ** |
| | |
| | ** A FIELD MEETING WITH THE CONTRACTOR/ARCHITECT SHALL |
| | BE SCHEDULE AT THE EARLIEST POSSIBLE TIME TO VISIT |
| | SITE. THERE ARE SOME AREAS OF CONCERN WITH THE CREATION |
| | ONE NEW SPACE AND ADJOINING THE EXISTING SPACE TO |
| | BUILDING ADJACENT. |
| | |
| | THERE MAY ALSO BE ELECTRICAL COMMENTS TO FOLLOW AFTER |
| | FIELD MEETING IS HELD. |
| | PLEASE CONTACT THIS OFFICE AS SOON AS POSSIBLE TO SET |
| | UP A TIME. IF POSSIBLE BEFORE THE NEW YEAR. 26TH -28TH |
| | OF DECEMBER. THIS WILL HELP IN THE REVIEW OF SAID PLANS |
| | AND TO CLERIFY ITEMS AS SHOWN ON PLANS. |
| | |
| | ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM THE |
| | PREVIOUS REVIEW WITH A NO OR OK FOR THE SAME NUMERICAL |
| | DESIGNATION AS PREVIOUS REVIEW. PLEASE SEE SOME MAY |
| | CONTAIN A NO/OK, AS PART OF A COMMENT MAY HAVE BEEN |
| | ADDRESSED HOWEVER NOT FULLY. |
| | |
| | ** PLEASE SEE ANY NEW COMMENTS BASED ON PLANS SUBMITTED |
| | MAY BE AT THE END OF THE PREVIOUS REVIEW NOTES. |
| | |
| | |
| | |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: NO. PLEASE KNOW BASED ON WORK AS SHOWN AND |
| | WILL BE REQUIRED THE VALUE IS SUBSTANTIALLY LOW AND ONE |
| | WILL BE ASSESSED IF NOT ADJUSTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SHALL BE |
| | BASED ON ALL LABOR AND MATERIALS EVEN IF ANY MATERIALS |
| | ARE OWNER SUPPLIED. PLEASE KNOW, WHEN A VALUE IS LOW, |
| | ONE WILL BE ASSESSED PER FBC 108.3 USING THE |
| | MARSHALL'S& SWIFT |
| | GUIDE AS ADOPTED BY THE FLORIDA BUILDING CODE. |
| | |
| | 3) NOTE:NO, PLEASE SEE THE OVERVIEW FOR THE CONDUITS |
| | BEING ENCASED DOES NOT PROVIDE THE DETAIL AS NEED FOR |
| | ALL CLEARANCES ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE BUILDING REVIEW NOTES AS 2ND FLOOR GARAGE |
| | DOOR. |
| | PLEASE SEE EXIT STAIRS MENTIONS TO ENCASED CONDUIT |
| | COMING IN THROUGH STAIRS, MUST PROVIDE COMPLETE |
| | ARCHITECTURAL DETAIL FOR DEPTH, DISTANCES, HEADROOM |
| | ETC. |
| | PLEASE ALSO SEE NO MORE THAN 8' OF UNDER PROTECTED |
| | CONDUCTORS ARE PERMITTED INSIDE THE BUILDING. THIS MAY |
| | ALSO INCLUDE ENCASEMENT OF CONDUITS IN MAIN ELECTRICAL |
| | ROOM. |
| | PLEASE SEE 230.70, 240.6 |
| | |
| | 4) NOTE: NO, PLEASE KNOW AT THIS TIME THE NEW PROPOSED |
| | SERVICE IS NOT GRANTED BY SPECIAL PERMISSION AS |
| | REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE SIZES AND VOLTAGES FOR ALL EXISTING |
| | SERVICES. |
| | PLEASE SEE 230.2 AS AT THIS TIME THIS NEW SERVICE IS |
| | NOT GRANTED. AS PLANS SHOW, THIS SEEMS BE ADDING |
| | ADDITIONAL SERVICES WHERE NOT ALL INFORMATION IS |
| | PROVIDED TO POSSIBLY GRANT ANY SPECIAL PERMISSION. |
| | |
| | 5) NOTE: NO, PLEASE SEE ENERGY CALCULATIONS STILL |
| | INDICATE MANUAL CONTROLS. |
| | PLEASE SEE NO SYSTEM IS BEING SHOWN IN DETAIL. |
| | PLEASE SEE NO TIMES FOR SCHEDULING. |
| | PLEASE SEE NO TIMES ON OVER RIDE DEVICES REQUIRED. |
| | PLEASE SEE NO DEVICES LOCATED IN SEPARATE SPACES. |
| | PLEASE SEE SECTIONS AS GIVEN IN PREVIOUS REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2, |
| | .1.3,. |
| | PLEASE SEE 13-415.1.B, 13-415.2, |
| | 13-415.2.ABC.1, TABLES 415.2.C.1, |
| | 415.2. B.1 |
| | PLEASE COMPLY WITH THIS. |
| | |
| | 6) NOTE: OK/NO, PLEASE SEE ADDRESSING ON SOME SHEETS DO |
| | NOT CORRELATE. |
| | PLEASE SEE E-4. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE ALL SUITE NUMBERS ON TITLE BLOCKS ON |
| | PLANS AS REQUIRED ON ALL SHEETS. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 7) NOTE: NO, NO INFORMATION SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2, AS A MIN OF 10FT |
| | CANDLES IS REQUIRED UNDER NORMAL AND 1FT CANDLE MIN |
| | UNDER EM PWR. |
| | PLEASE PROVIDE LIGHTING LEVELS. |
| | |
| | 8) NOTE:NO/OK, SOME SHOWN, HOWEVER AS LIGHTING LEVELS |
| | HAVE NOT BEEN PROVIDED ADDITIONAL FIXTURES MAY BE |
| | REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | ALONG WITH NOTE #7 ABOVE PLEASE INDICATE ALL EXISTING |
| | OTHER EMERGENCY LIGHTING AND EXIT LIGHTING AS THIS |
| | SPACE IS BEING INTRODUCED INTO THE 2ND FLR AND IF |
| | EXISTING DOES NOT MEET CODE, THEN THEY WILL BE |
| | REQUIRED. |
| | LS 101 7.8, 7.9, 700.12E. |
| | |
| | 9) NOTE: NO, PLEASE SEE ONLY TWO ITEMS ON ONE PANEL ARE |
| | BEING NOTED FOR THIS. PLEASE SEE ALL CONTINUOUS SHALL |
| | BE INDICATED AS SUCH. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE ALL CONTINUOUS LOADS AT 125% 215.3, |
| | 230.42 ETC. |
| | |
| | 10) NOTE: NO, PLEASE KNOW BASED ON THE LAYOUT FOR |
| | SPACES AND WHICH TENANT IS WHICH AND REQUIRED |
| | SEPARATION REQUIREMENTS, THERE MAY BE OTHER ELECTRICAL |
| | WHICH WILL NEED TO BE SHOWN. PLEASE KNOW BASED ON SITE |
| | MEETING AND NOTES ABOVE, THE SERVICE AND EQUIPMENT AS |
| | SHOWN IS NOT YET GRANTED OR APPROVED FOR REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE ALL ELECTRICAL PANELS ON POWER PLANS. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: NO/OK. SOME ITEMS CAN NOT BE VERIFIED FOR |
| | CODE COMPLIANCE AT THIS TIME. PLEASE KNOW SINCE NOTED |
| | ABOVE FOR A REQUIRED SITE MEETING THERE MAY BE CHANGES |
| | WHICH WILL AFFECT THE ELECTRICAL PLANS AS SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE BLDG REVIEW COMMENTS AS DOOR FROM MAIN |
| | ELECTRICAL ROOM IS SHOWN IMPEDING THE EGRESS OF |
| | OCCUPANTS. PLEASE SEE THE DOOR REQUIREMENTS MAY |
| | CHANGE. |
| | |
| | 13) NOTE: NO. SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PANEL SCHEDULE SHALL BE SPECIFIC TO ROOMS |
| | AND AREAS IN WHICH LTS AND RECEPTS FEEDS. IE; BATH LTS, |
| | POOL AREA ETC. |
| | ** IT IS KNOWN, THAT THESE WILL MOST LIKELY CHANGE |
| | DURING THE CONSTRUCTION. |
| | |
| | ** NEW NOTE ** |
| | |
| | 1) NOTE: PLEASE INDICATE ALL LIGHTING AND SOUND LEVELS |
| | FOR FIRE HORN AND STROBE DEVICES. PLEASE SEE FBC |
| | 11-4.28.1, .2, .3(4). THIS HAS NOW BECOME A REQUIREMENT |
| | FOR ELECTRICAL PLAN REVIEW. |
| | PLEASE INDICATE BASE REQUIRED SYSTEM AND SUBMIT PLANS. |
| | FBC 106.3.5.1.1 ADMIN SECTION |
| | |
| | 2) NOTE: PLEASE KNOW DUE TO SOME AREAS OF CONCERN ON |
| | PLANS NOT YET CLEAR FOR REVIEW, THERE MAY BE FURTHER |
| | COMMENTS. |
| | |
| | 3) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-12-21 20:48:00 | IN ELEC FOR REVIEW |