2007-01-03 13:42:21BUILDING PLAN REVIEW
 PERMIT: 06090366
 ADD: 221 CLEMATIS ST SUITE 201 & 202
 CONT: CASTLE FLORIDA
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) COMPLIED.
  
 3A)2ND REQUEST, PLANS INDICAE A CODE SUMMARY A TYPE
 II-BBUILDING SPRINKLERED AND A ASSEMBLY GROUP A-2.
 TABLE 503 A-2 TYPE II-B ALLOWABLE AREA IS 9,500 SQ FT 2
 STORIES. PLANS INDICATE THE FOOTPRINT OF THE BUILDING
 AS 21,213 SQ FT.
 PLEASE PROVIDE WHAT AREA AND OR HEIGHT INCREASES THAT
 YOU MAY TAKE, ALSO NOTE THIS ISCONSIDERED A (4) STORY
 BUILDING, THE
 3RD AND 4TH FLOORS BEING PROPOSED A BUSINESS
 OCCUPANCY.TABLE 503, 504.2 AUTOMATIC SPRINKLER
 INCREASES.
  
 3B)(1)PLEASE PROVIDE A LIFE SAFETY PLAN OF THE TOTAL
 FIRST FLOOR AND SECOND FLOOR OF THIS ASSEMBLY
 OCCUPANCY. PLEASE INDICATE OCCUPANT LOADS FOR ALL AREAS
 OF THE FLOOR, EXAMPLE BARS ARE TO BE CONSIDERED AS A
 STANDING SPACE 5 NET, DANCE FLOORS 7 NET, TABLE AND
 CHAIRS 15 NET, POOL TABLES 15 NET, FIXED SEATING 1004.7
 AND PROVIDE A TOTAL OCCUPANT LOAD.PLEASE NOTE THE
 EXISTING SUITE 202 IS CONSIDERED A MEZANINE SEE 1004.6
 AS HOW TO HANDLE THE OCCUPANT LOADS, WHERE THIS
 ADDITIONALOCCUPANT LOAD WILL DISCHARGE THROUGH. ALSO
 INDICATE THE DISPERSAL OF THE OCCUPANT LOAD, PROVIDE
 ALLOWABLE OCCUPANT LOADS FOR DOORWAYS AND STAIRS. TABLE
 1005.1.NOTE THE BOTTLE NECKING EFFECT AT ELEVATOR LOBBY
 TO SUITE # 202.
  
 3B)(2)THERE IS ANOTHER ISSUE TO BE CONCERNED WITH,
 THE OCCUPANCY LOAD OF THE NIGHTCLUB, IF OVER 300 1609.5
 THE IMPORTANCE FACTOR
 OF THE BUILDING . THE BUILDING BECOMES A
 BUILDING CATEGORY III, THE IMPORTANCE FACTOR OF
 1.15.PLEASE PROVIDE THE FOLLOWING WIND INFORMATION.
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN WIND
 PRESSURES IN TERMS OF PSF.
  
 3C)(1) PLEASE NOTE THERE IS NO MENTION OF THE EXITS AT
 THE REAR OF THE BUILDING ADJACENT TO THE ALLEY WAY. OUR
 JOBSITE MEETING (LAST
 WEEK OF DEC) REVEALED THE WEST EXIST STAIRS
 TO HAVE SEVERAL CODE VIOLATIONS:
 (1) THE EXIT DOOR TO THE STAIRWAY SWUNG INTO THE
 STAIRWELL, OCCUPANT LOAD > 50.
 (2) THERE APPEARED TO BE A KITHEN EXHAUST DUCK
 CUT INTO THE EXIT.
 (3) THERE ALSO WAS A VESTIBULE AREA DIRECTLY
 BEHIND THE STAIRWELL THE
 EXHAUST DUCK DUMPED INTO, THERE IS ANOTHER
 EXIT DOOR NOT DETERMINED
 WHERE IS AN EXIT FROM
 (4 THE STAIRWELL WAS NOT TRUELY FIRE RATED. (5)
 THERE WAS WINDOWS ON THE PROPERTY LINE. (6) AT
 THE TOP OF THE STAIRWAY NO DOOR OR ENCLOSURE.
 (7) IT APPEARS THAT THERE IS PLUMBING 6"OR 8" AT
 THE TOP OF THE LANDING
 (8) ALSO STAIRS TO THE MEZZANINE LEVEL ALSO HAD
 ISSUES WITH
 ELECTRICAL CONDUCTORS RUNNING THROUGH THE
 STAIRWELL.
 (9) THERE ALSO APPEARS TO BE HEIGTH PROBLEMS,
 MINIMUM HEADROOM
 (10) NO EXIT LIGTS OR DIRECTIONAL SIGNS
  
 3C()2) THE STAIRWELL TO THE EAST END OF THE ASSEMBLY
 OCCUPANCY SUITE# 202ALSO HAD SEVERAL CODE VIOLATIONS
 :
 (1) STORAGE IN THE STAIRWELL
 (2) ELECTRIC PANELS AT EACH FLOOR LEVEL
 (3) NO APPROVED EXIT LIGHTING, OR DIRECTIONAL
 SIGNS
 (4) THE EXIT DOOR ALSO SWINGS OUT OVER THE
 PROPERTY LINE.
 (5) IT APPEARS THERE IS ALSO PLUMBING IN THE
 STAIRWELL.
  
 4) WILL REFER BACK TO 3A) FOR ANSWER.
  
 5)2ND REQUEST, W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE DESIGNER OF RECORD
 INDICATES PRESSURES OF +52/-58 ON
 SHEET A-4 WHERE AS THE PRODUCT APPROVAL IS APPROVED FOR
 A DESIGN LOAD OF +30/-30?
  
 6) 2ND REQUEST, FIRE SPRINKLER PLANS ARE REQUIRED AT
 TIME OF PERMIT APPLICATION,IF THE BUILDING IS
 DESIGNED
 AS A FIRE SPRINKLERED BUILDING AND THE AREA INCREASES
 THAT ARE TAKEN IN TABLE 503 AND 504.2.. THE DESIGNER OF
 RECORD
 WILL DESIGN A SYSTEM AFTER THE PERMIT IS ISSUED, SHOP
 DRAWINGS
 WILL BE SUBMITTED AT THAT TIME. FL S S 553.79(2)
 WHENEVER FIRE
 SPRINKLER PLANS ARE REQUIRED, THEN THE DESIGN OF THOSE
 SYSTEMS
 MUST BE INCLUDED IN THE ORIGINAL PLANS AND
 SPECIFICATIONS FOR
 APPROVAL OF THE PERMIT.
  
 7)2ND REQUEST, THE OCCUPANT LOAD TO BE DETERMINED
 USING THE INFORMATION LISTED IN COMMENT 3B)(1) ABOVE.
  
 8A) 2ND REQUEST, FOR PRODUCT APPROVALS FOR THE
 OVERHEAD
  
 DOORS. PLANS MAY INDICATE LARGE MISSLE RATED GLASS, BUT
 THE
 PRODUCT SUBMITTED
 STATES THE SYSTEM BUILT AND TESTED DOES NOT HAVE LARGE
 MISSLE
 TESTING.1609.1.4(1) PROTECTION OF OPENINGS , GLAZED
 OPENINGS
 LOCATED WITHIN 30FEET OF GRADE SHALL MEET THE
 REQUIREMENTS OF
 THE LARGE MISSLE TEST.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8B) THERE ARE OTHER CRITERIA TO BE REVIEWED BY THE
 DESIGNER OF RECORD
 BEFORE THIS PRODUCT CAN BE APPROVED FOR USE IN THIS
 BUILDING.
 CLOPAY SHEET W5 HAS TWO DESIGN CRITEREA TO CONSIDER,
 THIS REPORT
 INDICATES FOR A 140 MPH WIND ZONE THE MEAN ROOF HEIGHT
 OF 30' AND AN
 IPORTANCE FACTOR OF 1.0. COMMENTS 3B((1) AND 3B)(2)
 BOTH REFER BACK TO THIS ISSUE.
 THE SECOND ISSUE THIS BEING A 4 STORY BUILDING IS
 HEIGHT, ONCE ABOVE 30' THERE
 ARE MULTIPLIERS THAT EFFECT THE PRESSURES, THE BASIC
 WIND PRESSURES WILL SHOW AN
 INCREASEABOVE THE BASE TABLE IN 1609..6.B. THERE IS A
 HEIGHT MULTIPLIER PLUS THE IMPORTANCE MULTIPLIER!!!!!
  
 8C)THE OVERHEADDOOR IN THE OPEN POSITION NEEDS TO
 COMPLY WITH 2405 SLOPED GLAZING.
 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS.
 SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS,
 SUBJECT TO THE LISTED LIMITATIONS.
 1.FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING
 MATERIAL OF THE SINGLE LIGHT OR LAYER SHALL BE
 LAMINATED GLASS WITH A MINIMUM 30-MIL (0.76 MM)
 POLYVINYL BUTYRAL (OR EQUIVALENT) INTERLAYER, WIRED
 GLASS, LIGHT-TRANSMITTING PLASTIC MATERIALS MEETING THE
 REQUIREMENTS OF SECTION 2607 , HEAT-STRENGTHENED GLASS
 OR FULLY TEMPERED GLASS.
 2.FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT
 OR LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS
 SPECIFIED IN ITEM 1 ABOVE.
 ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED
 WITHIN EXCEPTIONS 2 AND 3 OF SECTION 2405.3 .
 FOR ADDITIONAL REQUIREMENTS FOR PLASTIC SKYLIGHTS, SEE
 SECTION 2610 . GLASS-BLOCK CONSTRUCTION SHALL CONFORM
 TO THE REQUIREMENTS OF SECTION 2101.2.5 .
  
 8D) THE ENERGY FORMS NEED TO REFLECT THIS OPENING ON
 THE SOUTH WALL, WITH THE DOORS OPEN, AND WHEN THE DOORS
 ARE CLOSED
 THE TYPE OF DOOR ,IT IS NOT A PAPER HONEYCOMB FILLED
 CORE TYPE OF DOOR!!!!!!
 NOTE THE FIRST FLOOR DOOR IS ALSO A PAIR OF DOORS NOT A
 3'-0" X 7'-0"DOOR.
  
 8E)DETAIL4 SHEET A-3 INDICATES THE NEW OVERHEAD
 DOORS, PLEASE PROVIDE THE THICKNESS OF THE BEAM BELOW
 AND THE CLOSENESS OF THE WINDOWS BELOW, FIRST FLOOR
 WINDOWS. SHEET A-4 INDICATES THE FIRST FLOOR WINDOWS
 BUT THE TRANSOMS ABOVE THE WINDOWS DO NOT APPEAR.
 PLEASE PROVIDE ADDITIONAL DETAIL. PROVIDE COMPLIANCE
 WITH 704.9 VERTICAL SEPERATION.OF OPENINGS.IF USING
 EXCEPTION# 2 AGAIN A COMPLETE SET OF FIRE SPRINKLER
 PLANS FOR THE"BUILDING" WILL NEED TO BE PROVIDED FOR
 THIS EXCEPTION!!!!!
  
 9) GUARDRAILS, THE RESPONCE SHOWS A DETAIL 4/ A-3, THIS
 NEW DETAIL INDICATES A NEW SLAB DETAIL 1'-0" THICK, NO
 STEEL INFORMATION,
 HOW FAR OUT THE SLAB OR HANDRAILPROTRUDE FROM THE
 BUILDING OR IF THEY ARE OVER THE PROPERTY LINE?
 3202.3.2 WINDOWS, BALCONIES, ARCHITECTURAL FEATURES AND
 MECHANICAL EQUIPMENT.
 WHERE THE VERTICAL CLEARANCE ABOVE GRADE TO PROJECTING
 WINDOWS, BALCONIES, ARCHITECTURAL FEATURES OR
 MECHANICAL EQUIPMENT IS MORE THAN 8 FEET (2438 MM), 1
 INCH (25 MM) OF ENCROACHMENT IS PERMITTED FOR EACH
 ADDITIONAL 1 INCH (25 MM) OF CLEARANCE ABOVE 8 FEET
 (2438 MM), BUT THE MAXIMUM ENCROACHMENT SHALL BE 4 FEET
 (1219 MM).
  
 10) 2ND REQUEST, GUARDRAIL DETAIL 4/ A-3 INDICATES A
 HANDRAIL DETAILIS TO SHOW THE MINIMUM DISTANCE FROM
 THE EDGE OF SLAB.
 RESPONCE INDICATES 4" IN LETTER BUT NO COMMENT ON THE
 PLANS!!!
  
 11) 2ND REQUEST, VERTICAL ACCESSIBLITY BETWEEN SUITE
 201 & 202. PLANS INDICATE A LIFT, MUST NOT EMPEDE
 EGRESS ON STAIRS. PLEASE PROVIDE INFORMATION ON THE
 LIFT.11-4.1.6.(1)(K)(III).
 11-4.11 PLATFORM LIFTS (WHEELCHAIR LIFTS). 11-4.11.1
 LOCATION.
 PLATFORM LIFTS (WHEELCHAIR LIFTS) PERMITTED BY SECTION
 11-4.1 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 11-4.11 .
 11-4.11.2 OTHER REQUIREMENTS.
 IF PLATFORM LIFTS (WHEELCHAIR LIFTS) ARE USED, THEY
 SHALL COMPLY WITH SECTIONS 11-4.2.4 , 11-4.5 , 11-4.27
 , AND ASME A17.1, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS , SECTION XX, 1990.
 11-4.11.3 ENTRANCE.
 IF PLATFORM LIFTS ARE USED THEN THEY SHALL FACILITATE
 UNASSISTED ENTRY, OPERATION, AND EXIT FROM THE LIFT IN
 COMPLIANCE WITH SECTION 11-4.11.2 .
  
 12)COMPLIED.
  
 13) COMPLIED.
  
 14) THE PLANS ARE NOT CLEAR ON THE HANDRAIL AND LIFT
 ARE TO COMBINE TO CREATE A OPENING FOR THE LIFT?
  
 15) RESPONCE STATES THE METAL CLAD DOOR (90 MIN RATING)
 IS TO ONLY BE AESTHETIC VALUE TO THE PROJECT, BUT THE
 FIELD MEETING
 INDICATED ON SLOW NIGHTS THIS AREA WILL BE CLOSED OFF,
 HOW WILL THIS OCCUR? WILL EACH AREA EVER BE OPENED
 SEPERATELY,
 SUITE 202 IS CLOSED THERE WILL BE NO VERTICAL MEANS OF
 EGRESS?
  
 16) POSSIBLY COMPLIED DEPENDING ON COMMENT RESPONCE
 15.
  
 17) COMPLIED.
  
 18) 2ND REQUEST,CORRIDOR 110 WILL HAVE ISSUES. THIS
 MAY TRUELY BE A CORRIDOR OR IT MAY END UP BEING
 DESIGNED AS A PART OF AN EXIT
 PASSAGEWAY. IF THE DESIGN IS A CORRIDORTHE ELECTRICAL
 ROOM DOOR WOULD BE ALLOWED. IF DESIGNED AS PART OF THE
 EXIT PASSAGE WAY
 NO ELECTRICAL ROOM DOOR CAN BE IN THIS EXIT. NOTE ALSO
 FROM THE JOBSITE MEETING THE ELECTRIC ROOM DOOR NEEDS
 TO SWING OUT OF THE
 ELECTRICAL ROOM.
  
 19) 2ND REQUEST, HOW MANY STORIES ARE IN THE BUILDING?
 A 1 HR CORRIDOR IS SHOWN. THE RESPONCE STATES THE AREA
 WHERE WORK IS TO OCCUR IS TWO STORIES. PLANS INDICATE
 IN SUITE 202 THE WALL OFTHE MENS RESTROOM THAT BACKS UP
 TO THE 4 STORY STAIR TOWER DOES SHOW A 1 HR RATING
 WHERE THERE SHOULD BE A 2 HR RATING . SHAFTS SEE
 SECTION 707.
  
 20) ELECTRICAL ROOM 108 AS DISCUSSED IN THE JOBSITE
 MEETING THIS DORR DOES NEED TO BE MOVED BEWARE OF THE
 DOOR SWINNG AND THE CLEAR SPACE REQUIRED FOR THE
 CORRIDOR. NOTE ALSO : 008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
  
 21) 2ND REQUEST, PROVIDE INFORMATION IN REGARDS TO EXIT
 DISCHARGE? RESPONCE EXIT DIRECTION IS NOW SHOWN ON
 1/A-1. PLANS DO NOT SHOW THE EXIT AT THE FIRST FLOOR.
 THE JOB MEETING CLEARLY INDICATES PROBLEM AREAS AT BOTH
 THE EAST AND WEST EXITS. SEE COMMENT # 3.
  
 22) COMPLIED.
  
 23) COMPLIED.
  
 24) COMPLIED.
  
 25) COMPLIED.
  
 ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT REVIEW AS A
 RESULT TO COMMENT RESPONCE TO THIS REVIEW AND NEW
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  