| 2008-12-18 13:46:12 | ** DENIED/PASSED REVIEW OF REVISIONS** |
| | |
| | 1) NOTE: PLEASE SUBMIT REVISED LIGHTING PERFORMANCE |
| | CALCULATIONS FOR COMPLIANCE WITH FBC |
| | 13-415.2,13-415.2.ABC.1.1,.1.2. SAME NOTE AS PREVIOUS |
| | REVIEW. PLEASE SEE TABLES 13-415.2.B (PRESCRIPTIVE) |
| | 13-415.2.C (PRESCRIPTIVE) |
| | PLEASE SEE13-400.0.C.4 FOR RENOVATED BUILDINGS. |
| | RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION |
| | 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR |
| | COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE |
| | ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR |
| | THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT |
| | MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW |
| | HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING |
| | SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE |
| | MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE |
| | SYSTEM(S) BEING CHANGED. |
| | THE SECTION 202 REFERENCE IS FOR 30% OR MORE OF THE |
| | BUILDING. AS THE SCOPE OF WORK DOES NOT MEET THIS |
| | PLEASE MEET PRESCRIPTIVE AS STATED. |
| | THE PREVIOUS METHOD B FLA-COM WAS GIVEN BACK AS N/A. |
| | THE TYPE IS ALSO SHOWN AS RETAIL WHICH THIS SPACE IS |
| | NOT. PLEASE SEE TABLE B, TABLE C FOR USE. |
| | |
| | ** A CALL WAS PLACED AND A MESSAGE WAS LEFT ON THE |
| | ANSWERING MACHINE OF THE ENGINEER. |
| | |
| | ** SEE PREVIOUS NOTES WHICH WERE THE SAME. ONCE |
| | CALCULATIONS HAVE BEEN ADDRESSED THE REVIEW OF PLANS |
| | AND CALCULATIONS WILL BE COORDINATED. REVIEW WILL THEN |
| | GO INTO A FINAL PASSED STATUS WITHOUT ANY OUTSTANDING |
| | COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |