Plan Review Notes
Plan Review Notes For Permit 06090366
Permit Number 06090366
Review Stop P
Sequence Number 1
Notes
Date Text
2006-10-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PERMIT APPLICATION STATES GROSS
 SQUARE FOOTAGE AS 5423SF. COVER SHEET
 INDICATES 54243SF BAR, AND 3571SF POOL
 HALL. PLEASE CLARIFY. SECTION 106.1.1.
  
 2. ALL ARCHITECTURAL SHEETS. THE ADDRESS
 ON THE TITLE BLOCK DOES NOT RELFECT THE INFORMATION FOR
 THE ADDRESS ON THE DBPR
 WEBSITE. PLEASE CLARIFY. (SEE ATTACHED
 SHEET). FAC 61G1-16.004(1) FS 481.219.
  
 3. SHT A-1 SUITE 202 DEMO NOTES. IN THE
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS ARE PROHIBITED.
 SECTION 704.5. SUBMIT AN EXISTING FLOOR
 PLAN TO DETERMINE THE LOCATION OF ALL
 DEMO'D PLUMBING SYSTEMS, AND TO VERIFY
 THE EXTENT OF THE DEMOLITION. SECTION
 106.1.2.
  
 4. SHT A-2 DETAILS 1 & 2. TURNING AREA
 TO BE SHOWN IN THE TOILET ROOM, NOT IN
 THE ACCESSIBLE STALL. SECTION 11-4.22.3.
  
 5. SHT A-2 DETAIL 6 INDICATES 2 HEIGHTS
 FOR THE WATER CLOSETS. BOTH INDICATE
 STANDARD HEIGHT. ONE, (19"), SHALL BE
 INDICATED AS ACCESSIBLE HEIGHT. SECTIONS
 106.1.1, AND 11-4.16.3.
  
 6. SHT A-2 DETAIL 6 GRAB BAR ON THE SIDE
 OF THE W/C SHALL BE 42" MINIMUM. SEE
 FIGURES 11-29 & 11-30.
  
 7. SHT A-2 DETAIL 6 FLUSH CONTROLS TO
 COMPLY WITH SECTION 11-4.16.5.
  
 8. SHT A-2 SUBMIT A DETAIL FOR THE
 URINALS SHOWING COMPLIANCE WITH:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
  
 9. ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH FOR REVIEW PRIOR SO RESUBMITTING
 TO THE CITY WPB FOR REVIEW. A MINIMUM OF
 2 SETS OF PLANS SHALL BE STAMPED AS
 REVIEWED BY THE HEALTH DEPT. SECTION
 102.2.1.
  
 10. SHT P-1 KEY NOTE #4, AND SHT P-3
 SANT. RISER DIAGRAM. EVERY DRY VENT
 SHALL RISE VERTICALLY TO A MINIMUM OF 6"
 ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST
 TRAP OR TRAPPED FIXTURE BEING VENTED.
 SECTION 905.4.
  
 11. SHT P-2 WATER HEATER PIPING DIAGRAM
 SHOWS A 2" HUB DRAIN FOR THE INDIRECT
 WASTE OF THE PAN DRAIN, P/T DISCHARGE,
 AND THE THERMAL EXPANSION VALVE. THIS IS
 NOT SHOWN ON THE FLOOR PLAN, NOR ON THE
 SANT. RISER DIAGRAM. IS THIS HUB DRAIN
 EXISTING? PLEASE CLARIFY. SECTION
 106.1.1.
  
 12. ALL INDIRECT WASTE SHALL DRAIN INTO
 A FLOOR SINK OR A HUB DRAIN. SECTIONS
 802.3 & 802.3.2. FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]