Plan Review Notes
Plan Review Notes For Permit 06090366
Permit Number 06090366
Review Stop M
Sequence Number 1
Notes
Date Text
2006-10-14 08:54:051)PLEASE PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS FOR ERV #1 & #2 WITH PLANS.
 2)PLEASE PROVIDE A DETAIL ON THE CURB TO ROOF TIEDOWN
 ON THE PLANS.
 3)PLEASE PROVIDE A DETAIL ON RTU TO CURB TIEDOWN ON
 THE OPANS.
 4)PLEASE SHOW A CONTINUATION OF BATHROOM EXHAUST DUCT
 ON PLANS.
 5) PLEASE PROVIDE RETURN AIR SIZE AND CFM ON EXISTING
 20 TON EQUIPMENT.
 6) PLEASE REFER TO SECTION 306.4.1 SUPERVISON FBC (M)
 2004.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732