| 2006-10-20 13:08:19 | ***DENIED*** |
| | |
| | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 |
| | EDITION. |
| | |
| | 2) KNOX BOX APPLICATIONS MAY BE OBTAINED AT THE BUREAU |
| | OF FIRE PREVENTION, (561) 804-4724. |
| | |
| | 3) FIRE EXTINGUISHERS SHALL BE 2A-10B,C RATED AND |
| | MOUNTED MOUNTED NOT TO EXCEED 75' TRAVEL DISTANCE. |
| | |
| | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 5) ALL EXIT DOORS AND DOORS THAT ARE PART OF THE |
| | REQUIRED MEANS OF EGRESS SHALL SWING IN THE DIRECTION |
| | OF TRAVEL. |
| | |
| | 6) PLEASE PROVIDE MINIMUM INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS IN ACCORDANCE |
| | WITH NFPA 101, CHAPTER 10. |
| | |
| | 7) OCCUPANT LOAD SIGNS WILL BE REQUIRED PRIOR TO FIRE |
| | FINAL. |
| | |
| | 8) STAIS SHALL COMPLY WITH NFPA 101, SECTION 7.2.2.2.1 |
| | (A). |
| | |
| | 9) NO COMBUSTIBLE PERMITTED ABOVE CEILING IF BEING USED |
| | AS RETURN AIR PLENUM. |
| | |
| | 10) PENETRATIONS AND OPENINGS ARE PROHIBITED INTO EXIT |
| | ENCLOSURES UNLESS PERMITTED IN NFPA 101, SECTION |
| | 7.1.3.2.1 (6). PLEASE SEE CONDUITS THROUGH EXIT STAIRS |
| | ON SHEET E-1. |
| | |
| | 11) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHT E-3 FA |
| | NOTE (7) |
| | |
| | 12) SEPARATE SHOP DRAWINGS AND PERMITS IN ADDITION TO |
| | FIRE SPRINKLER REMODEL WILL BE REQUIRED FOR FIRE ALARM |
| | SYSTEM. |
| | |
| | 13) PLEASE PROVIDE MORE INFORMATION IN REFERENCE TO |
| | PROPOSED VOICE ALARM. (MESSAGE) |
| | |
| | 14) HANDRAILS ARE REQUIRED FOR BOTH SIDES OF STAIRS. |
| | |
| | 15) PLANS DON'T SHOW A SMOKE DETECTOR IN ELEVATOR |
| | LOBBY. E SHEETS |
| | |
| | 16) AN EXIT SIGN IS SHOWN ON E-2 DIRECTING PERSONS FROM |
| | VESTIBULE 100. FROM THAT POINT IT IS UNCLEAR WHERE |
| | PERSONS CONTINUE TO EXIT. |
| | |
| | 17) THERE APPEARS TO BE AN EXIT SIGN MISSING IN |
| | ELEVATOR 111. SHT E-2 |
| | |
| | 18) PLEASE CLEARLY ILLUSTRATE THE DOOR SWING OR |
| | OPERATION OF THE REPAIR OR REPLACE METAL CLAD 90 MIN |
| | DOOR BETWEEN SUITES 201 AND 202. |
| | |
| | 19) WHERE DO PERSONS EXIT AFTER THEY ENTER THE EXIT |
| | ENCLOSURE ASSEMBLIES? PLEASE SHOW EXIT DISCHARGE AS IT |
| | RELATES TO THIS PROJECT. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW (561) 805-6722 |