2006-10-20 13:08:19***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) KNOX BOX APPLICATIONS MAY BE OBTAINED AT THE BUREAU
 OF FIRE PREVENTION, (561) 804-4724.
  
 3) FIRE EXTINGUISHERS SHALL BE 2A-10B,C RATED AND
 MOUNTED MOUNTED NOT TO EXCEED 75' TRAVEL DISTANCE.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) ALL EXIT DOORS AND DOORS THAT ARE PART OF THE
 REQUIRED MEANS OF EGRESS SHALL SWING IN THE DIRECTION
 OF TRAVEL.
  
 6) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN ACCORDANCE
 WITH NFPA 101, CHAPTER 10.
  
 7) OCCUPANT LOAD SIGNS WILL BE REQUIRED PRIOR TO FIRE
 FINAL.
  
 8) STAIS SHALL COMPLY WITH NFPA 101, SECTION 7.2.2.2.1
 (A).
  
 9) NO COMBUSTIBLE PERMITTED ABOVE CEILING IF BEING USED
 AS RETURN AIR PLENUM.
  
 10) PENETRATIONS AND OPENINGS ARE PROHIBITED INTO EXIT
 ENCLOSURES UNLESS PERMITTED IN NFPA 101, SECTION
 7.1.3.2.1 (6). PLEASE SEE CONDUITS THROUGH EXIT STAIRS
 ON SHEET E-1.
  
 11) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHT E-3 FA
 NOTE (7)
  
 12) SEPARATE SHOP DRAWINGS AND PERMITS IN ADDITION TO
 FIRE SPRINKLER REMODEL WILL BE REQUIRED FOR FIRE ALARM
 SYSTEM.
  
 13) PLEASE PROVIDE MORE INFORMATION IN REFERENCE TO
 PROPOSED VOICE ALARM. (MESSAGE)
  
 14) HANDRAILS ARE REQUIRED FOR BOTH SIDES OF STAIRS.
  
 15) PLANS DON'T SHOW A SMOKE DETECTOR IN ELEVATOR
 LOBBY. E SHEETS
  
 16) AN EXIT SIGN IS SHOWN ON E-2 DIRECTING PERSONS FROM
 VESTIBULE 100. FROM THAT POINT IT IS UNCLEAR WHERE
 PERSONS CONTINUE TO EXIT.
  
 17) THERE APPEARS TO BE AN EXIT SIGN MISSING IN
 ELEVATOR 111. SHT E-2
  
 18) PLEASE CLEARLY ILLUSTRATE THE DOOR SWING OR
 OPERATION OF THE REPAIR OR REPLACE METAL CLAD 90 MIN
 DOOR BETWEEN SUITES 201 AND 202.
  
 19) WHERE DO PERSONS EXIT AFTER THEY ENTER THE EXIT
 ENCLOSURE ASSEMBLIES? PLEASE SHOW EXIT DISCHARGE AS IT
 RELATES TO THIS PROJECT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722