Plan Review Notes
Plan Review Notes For Permit 06090366
Permit Number 06090366
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-29 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE ALL OF THE FOLLOWING
 RELEVANT CODES IN EFFECT SHALL BE STATED
 ON PLANS.
 2002 NFPA-70(NEC), 2002 NFPA-72, 2003
 NFPA-101 AND 2004 FBC.
  
  
 2)PLEASE SEE VALUE FOR COMPLETE SCOPE OF
 WORK SHALL BE BASED ON ALL LABOUR AND
 MATERIALS EVEN IF ANY MATERIALS ARE
 OWNER SUPPLIED. PLEASE KNOW, WHEN A
 VALUE IS LOW, ONE WILL BE ASSESSED PER
 FBC 108.3 USING THE MARSHALL'S& SWIFT
 GUIDE AS ADOPTED BY THE FLORIDA BUILDING
 CODE.
  
 3) NOTE: PLEASE SEE BUILDING REVIEW
 NOTES AS 2ND FLR GARAGE DOOR.
 PLEASE SEE EXIT STAIRS MENTIONS TO
 ENCASED CONDUIT COMING IN THROUGH
 STAIRS, MUST PROVIDE COMPLETE
 ARCHITECTURAL DETAIL FOR DEPTH,
 DISTANCES, HEADROOM ETC ETC.
 PLEASE ALSO SEE NO MORE THAN 8' OF UNDER
 PROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING. THIS MAY ALSO
 INCLUDE ENCASEMENT OF CONDUITS IN MAIN
 ELECTRICAL ROOM.
 PLEASE SEE 230.70, 240.6
  
 4) NOTE: PLEASE PROVIDE SIZES AND
 VOLTAGES FOR ALL EXISTING SERVICES.
 PLEASE SEE 230.2 AS AT THIS TIME THIS
 NEW SERVICE IS NOT GRANTED. AS PLANS
 SHOW, THIS SEEMS BE ADDING ADDITIONAL
 SERVICES WHERE NOT ALL INFORMATION IS
 PROVIDED TO POSSIBLY GRANT ANY SPECIAL PERMISSION.
  
 5) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2, .1.3,.
 PLEASE SEE 13-415.1.B, 13-415.2,
 13-415.2.ABC.1, TABLES 415.2.C.1,
 415.2.B.1
 PLEASE COMPLY WITH THIS.
  
 6) NOTE: PLEASE INDICATE ALL SUITE
 NUMBERS ON TITLE BLOCKS ON PLANS AS
 REQUIRED ON ALL SHEETS.
 FAC 61G1-16.004, 61G15-23.002
  
 7) NOTE: PLEASE SEE NFPA-101 7.8.1.3,
 7.9.2.2, AS A MIN OF 10FT CANDLES IS
 REQUIRED UNDER NORMAL AND 1FT CANDLE MIN
 UNDER EM PWR.
 PLEASE PROVIDE LIGHTING LEVELS.
  
 8)NOTE: ALONG WITH NOTE #7 ABOVE PLEASE
 INDICATE ALL EXISTING OTHER EMERGENCY
 LIGHTING AND EXIT LIGHTING AS THIS SPACE
 IS BEING INTRODUCED INTO THE 2ND FLR AND
 IF EXISTING DOES NOT MEET CODE , THEN
 THEY WILL BE REQUIRED.
 LS 101 7.8, 7.9, 700.12E.
  
 9) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125% 215.3, 230.42 ETC.
  
 10) NOTE: PLEASE INDICATE ALL
 ELECTRICAL PANELS ON POWER PLANS.
  
 11) NOTE: PLEASE CLARIFY LIGHTING FOR
 MAIN ELECTRICAL ROOM. IS THIS ROOM ON
 THE FIRST FLR? PLEASE KNOW, IF AN EM
 BACK UP LT IS NOT EIXSITING, ONE WILL BE
 REQUIRED FOR LIFE SAFTEY AND FIRE DEPT
 PERSONEL.
 LS101 7.8, 7.9, 700.12E.
  
 12) NOTE: PLEASE SEE BLDG REVIEW
 COMMENTS AS DOOR FROM MAIN ELECTRICAL
 ROOM IS SHOWN IMPEDING THE EGRESS OF
 OCCUPANTS. PLEASE SEE THE DOOR
 REQUIREMENTS MAY CHANGE.
  
 13) NOTE: PLEASE SEE PANEL SCHEDULE
 SHALL BE SPECIFIC TO ROOMS AND AREAS IN
 WHICH LTS AND RECEPTS FEED.
 IE; BATH LTS, POOL AREA ETC.
 ** IT IS KNOWN, THAT THESE WILL MOST
 LIKELY CHANGE DURING THE CONSTRUCTION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  