| 2006-09-29 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE ALL OF THE FOLLOWING |
| | RELEVANT CODES IN EFFECT SHALL BE STATED |
| | ON PLANS. |
| | 2002 NFPA-70(NEC), 2002 NFPA-72, 2003 |
| | NFPA-101 AND 2004 FBC. |
| | |
| | |
| | 2)PLEASE SEE VALUE FOR COMPLETE SCOPE OF |
| | WORK SHALL BE BASED ON ALL LABOUR AND |
| | MATERIALS EVEN IF ANY MATERIALS ARE |
| | OWNER SUPPLIED. PLEASE KNOW, WHEN A |
| | VALUE IS LOW, ONE WILL BE ASSESSED PER |
| | FBC 108.3 USING THE MARSHALL'S& SWIFT |
| | GUIDE AS ADOPTED BY THE FLORIDA BUILDING |
| | CODE. |
| | |
| | 3) NOTE: PLEASE SEE BUILDING REVIEW |
| | NOTES AS 2ND FLR GARAGE DOOR. |
| | PLEASE SEE EXIT STAIRS MENTIONS TO |
| | ENCASED CONDUIT COMING IN THROUGH |
| | STAIRS, MUST PROVIDE COMPLETE |
| | ARCHITECTURAL DETAIL FOR DEPTH, |
| | DISTANCES, HEADROOM ETC ETC. |
| | PLEASE ALSO SEE NO MORE THAN 8' OF UNDER |
| | PROTECTED CONDUCTORS ARE PERMITTED |
| | INSIDE THE BUILDING. THIS MAY ALSO |
| | INCLUDE ENCASEMENT OF CONDUITS IN MAIN |
| | ELECTRICAL ROOM. |
| | PLEASE SEE 230.70, 240.6 |
| | |
| | 4) NOTE: PLEASE PROVIDE SIZES AND |
| | VOLTAGES FOR ALL EXISTING SERVICES. |
| | PLEASE SEE 230.2 AS AT THIS TIME THIS |
| | NEW SERVICE IS NOT GRANTED. AS PLANS |
| | SHOW, THIS SEEMS BE ADDING ADDITIONAL |
| | SERVICES WHERE NOT ALL INFORMATION IS |
| | PROVIDED TO POSSIBLY GRANT ANY SPECIAL PERMISSION. |
| | |
| | 5) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| | .1.2, .1.3,. |
| | PLEASE SEE 13-415.1.B, 13-415.2, |
| | 13-415.2.ABC.1, TABLES 415.2.C.1, |
| | 415.2.B.1 |
| | PLEASE COMPLY WITH THIS. |
| | |
| | 6) NOTE: PLEASE INDICATE ALL SUITE |
| | NUMBERS ON TITLE BLOCKS ON PLANS AS |
| | REQUIRED ON ALL SHEETS. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 7) NOTE: PLEASE SEE NFPA-101 7.8.1.3, |
| | 7.9.2.2, AS A MIN OF 10FT CANDLES IS |
| | REQUIRED UNDER NORMAL AND 1FT CANDLE MIN |
| | UNDER EM PWR. |
| | PLEASE PROVIDE LIGHTING LEVELS. |
| | |
| | 8)NOTE: ALONG WITH NOTE #7 ABOVE PLEASE |
| | INDICATE ALL EXISTING OTHER EMERGENCY |
| | LIGHTING AND EXIT LIGHTING AS THIS SPACE |
| | IS BEING INTRODUCED INTO THE 2ND FLR AND |
| | IF EXISTING DOES NOT MEET CODE , THEN |
| | THEY WILL BE REQUIRED. |
| | LS 101 7.8, 7.9, 700.12E. |
| | |
| | 9) NOTE: PLEASE INDICATE ALL CONTINUOUS |
| | LOADS AT 125% 215.3, 230.42 ETC. |
| | |
| | 10) NOTE: PLEASE INDICATE ALL |
| | ELECTRICAL PANELS ON POWER PLANS. |
| | |
| | 11) NOTE: PLEASE CLARIFY LIGHTING FOR |
| | MAIN ELECTRICAL ROOM. IS THIS ROOM ON |
| | THE FIRST FLR? PLEASE KNOW, IF AN EM |
| | BACK UP LT IS NOT EIXSITING, ONE WILL BE |
| | REQUIRED FOR LIFE SAFTEY AND FIRE DEPT |
| | PERSONEL. |
| | LS101 7.8, 7.9, 700.12E. |
| | |
| | 12) NOTE: PLEASE SEE BLDG REVIEW |
| | COMMENTS AS DOOR FROM MAIN ELECTRICAL |
| | ROOM IS SHOWN IMPEDING THE EGRESS OF |
| | OCCUPANTS. PLEASE SEE THE DOOR |
| | REQUIREMENTS MAY CHANGE. |
| | |
| | 13) NOTE: PLEASE SEE PANEL SCHEDULE |
| | SHALL BE SPECIFIC TO ROOMS AND AREAS IN |
| | WHICH LTS AND RECEPTS FEED. |
| | IE; BATH LTS, POOL AREA ETC. |
| | ** IT IS KNOWN, THAT THESE WILL MOST |
| | LIKELY CHANGE DURING THE CONSTRUCTION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |