| 2006-10-06 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE |
| | REQUIRED PRIOR TO PERMIT PICKUP, |
| | FS713.13. |
| | |
| | 2.)INCLUDE FBC EB IN GOVERNING CODE. |
| | DECLARE LEVEL OF ALTERATION, FBC EB 3. |
| | DOES THIS INVOLVE A CHANGE OF OCCUPANCY? |
| | IF IT DOES, INCLUDE COMPLIANCE WITH FBC |
| | 8. |
| | |
| | 3.)INCLUDE A CODE SUMMARY ABOUT THE |
| | EXISTING BUILDING; (REVISE) BUILDING |
| | TYPE FBC6, BUILDING HEIGHT AND AREA |
| | FBC5, OCCUPANCY CLASSIFICATION FBC 3 AND |
| | AREA PER OCCUPANCY.OCCUPANCY |
| | CLASSIFICATION HAS BEEN DECLARED, A2, |
| | FOR THE RENOVATED SPACE, BUT PLEASE |
| | PROVIDE INFORMATION IN REGARDS TO THE |
| | REST OF THE BUILDING. |
| | |
| | 4.)SHEET A1 STATES THAT THE BUILDING |
| | IS TYPE IV UNPROTECTED.SEE FBC 6, TYPE |
| | IV IS HEAVY TIMBER.TO MY KNOWLEDGE |
| | THIS IS NOT A HEAVY TIMBER BUILDING. |
| | PLEASE REVISE, AND INCLUDE A OR B. |
| | |
| | 5.)PRODUCT APPROVALS TO BE REVIEWED BY |
| | DESIGNER OF RECORD, FBC*106.3.3. |
| | |
| | 6.)FIRE SPRINKLER PLANS REQUIRED, |
| | FBC*106.3.5.1.1(5), FS553.79(2).ALSO |
| | SEE ATTACHED LETTER FROM DCA. |
| | |
| | 7.)A1, OCCUPANT LOAD IS TO BE NOT LESS |
| | THAN SPECIFIED IN FBC TABLE 1004.1.2, |
| | FBC 1004.1.2 (ROUND UP RATHER THAN ROUND |
| | DOWN). |
| | |
| | 8.)THE PRODUCT APPROVAL FOR THE |
| | OVERHEAD DOOR REQUIRES IMPACT PROTECTION |
| | FOR THE OPTIONAL GLASS. REMOVABLE |
| | SHUTTERS NOT ALLOWED ABOVE THE FIRST |
| | FLOOR.SEE ATTACHED POLICY IN REGARDS |
| | TO IMPACT PROTECTION.PLEASE CONTACT ME |
| | TO DISCUSS AND PLEASE RESOLVE THIS ISSUE |
| | PRIOR TO RESUBMITTAL. |
| | |
| | 9.)GUARDRAIL REQUIRED AT THE OVERHEAD |
| | DOOR, FBC1012.1. |
| | |
| | 10.)GUARDRAIL DETAIL, 4-A3, AND |
| | HANDRAIL DETAIL, SHOW MINIMUM DISTANCE |
| | FROM THE EDGE OF SLAB. |
| | |
| | 11.)VERTICAL ACCESSIBILITY REQUIRED, |
| | FBC11-4.1.6. IT IS NOT CLEAR IF THE |
| | ELEVATOR IS DESIGNED TO COMMUNICATE |
| | BETWEEN SUITE 201 AND SUITE 202, NOTE ON |
| | THE PLAN. |
| | |
| | 12.)PROVIDE A DETAIL FOR THE EXISTING |
| | STAIR BETWEEN SUITE 201 AND SUITE 202. |
| | THE NOTE STATES TO REPAIR AS NECESSARY, |
| | PROVIDE A DETAIL. |
| | |
| | 13.)THE STAIR IS TO COMPLY WITH |
| | FBC1009.PROVIDE A DETAIL FOR BOTH |
| | STAIRS BETWEEN SUITE 201 AND SUITE 202. |
| | |
| | 14.)PROVIDE A DETAIL FOR THE STAIR |
| | RAILS.HANDRAILS REQUIRED ON BOTH SIDES |
| | OF THE STAIR, FBC1009.11.PROVIDE A |
| | DETAIL AND SHOW ALL HANDRAILS ON THE |
| | PLAN.SHOW COMPLIANCE WITH FBC1607.7. |
| | SEE ALSO FBC11-4.26. |
| | |
| | 15.)THE NOTE STATES TO REPAIR/REPLACE |
| | METAL CLAD DOOR 90 MINUTE (STAIR BETWEEN |
| | SUITE 201 AND SUITE 202).A DOOR IS NOT |
| | SHOWN GRAPHICALLY, WHAT IS SHOWN THERE |
| | ON EACH SIDE OF THE WALL? |
| | |
| | 16.)LANDINGS REQUIRED AT THE STAIRS, |
| | FBC1009.4 AND AT DOORS FBC1008.1.5. |
| | NONE IS SHOWN AT THE EXISTING STAIRS TO |
| | BE REPAIRED.DOOR LOCATION AND SWING IS |
| | NOT CLEAR FROM THE PLAN. |
| | |
| | 17.)IT APPEARS THAT THERE WAS A WALL |
| | BETWEEN SUITE 201 AND SUITE 202, TENANT |
| | SEPARATION.A 2 HOUR EXIT ENCLOSURE IS |
| | SHOWN.THE PURPOSE OF THE 90 MINUTE |
| | DOOR IS NOT CLEAR; IS THIS ONE TENANT |
| | SPACE OR TWO? |
| | |
| | 18.)CORRIDOR 110, SHOW ANY REQUIRED |
| | FIRE RATING FOR THIS WALL.20MIN DOORS |
| | ARE NOTED ON THE PLAN, DOORS C.NO FIRE |
| | RATING SHOWN FOR THE ELECTRICAL 108 |
| | DOOR.THIS APPEARS TO BE AN EXIT |
| | CORRIDOR; IS THE STAIR SHOWN AN EXIT FOR |
| | ANOTHER TENANT SPACE?YOU ARE REMOVING |
| | A DOOR AND INCORPORATING A STORAGE AREA |
| | INTO THE STAIRWAY, CANNOT USE ANEXIT |
| | ENCLOSURE FOR ANY OTHER PURPOSE, |
| | FBC1019. |
| | |
| | 19.)HOW MANY STORIES IS THIS BUILDING? |
| | A 1 HOUR CORRIDOR WALL IS SHOWN, NO |
| | OTHER RATING SHOWN FOR THE STAIRS |
| | ADJACENT TO ELECTRICAL 108.2 HOUR |
| | REQUIRED FOR FOUR STORIES OR MORE, |
| | FBC1019. |
| | |
| | 20.)PROVIDE DIMENSIONS THE ELECTRICAL |
| | 108 DOOR.IT APPEARS CODE COMPLIANT |
| | WHEN SCALED; SEE FBC1005.2 AND SHOW |
| | COMPLIANCE ON THE PLAN. |
| | |
| | 21.)PROVIDE INFORMATION IN REGARDS TO |
| | EXIT DISCHARGE; NONE SHOWN ON THE PLAN. |
| | |
| | |
| | 22.)THERE ARE FOUR ITEMS SHOWN |
| | GRAPHICALLY ON THE PLAN AS RECTANGLES |
| | WITH AN X.TWO APPEAR TO BE ELEVATORS |
| | (AS THEY ARE LOCATED IN THE ELEVATOR |
| | LOBBY); WHAT ARE OTHER TWO? |
| | |
| | 23.)PROVIDE A DETAIL FOR SIGNAGE FOR |
| | THE ELEVATORS, FBC11-4.10. |
| | |
| | 24.)A WALL IS BEING REMOVED; DOES THIS |
| | WALL SERVE AS A TENANT AND/OR OCCUPANCY |
| | SEPARATION?THERE IS ALSO A STAIR FROM |
| | SUITE 202 GOING DOWNSTAIRS.WHAT IS IN |
| | THE AREA BELOW?IS IT A PART OF THIS |
| | SPACE OR IS IT ANOTHER TENANT SPACE? |
| | |
| | 25.)SEE FBC11-5.2 REGARDING COUNTERS |
| | EXCEEDING 34INCHES, SHOW ACCESSIBLE |
| | SEATING ON THE PLAN (BARS 1, 2, AND 3). |
| | |
| | 26.)A RESPONSE LETTER WHEN |
| | RESUBMITTING WILL HELP EXPEDITE PLAN |
| | REVIEW.ALL CHANGES TO THE PLAN ARE TO |
| | BE CLOUDED. |
| | |
| | 27.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC. |
| | |
| | 28.)PROVIDE WIND DESIGN CRITERIA, |
| | FBC1603.1.4. |