2006-10-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT WILL BE
 REQUIRED PRIOR TO PERMIT PICKUP,
 FS713.13.
  
 2.)INCLUDE FBC EB IN GOVERNING CODE.
 DECLARE LEVEL OF ALTERATION, FBC EB 3.
 DOES THIS INVOLVE A CHANGE OF OCCUPANCY?
 IF IT DOES, INCLUDE COMPLIANCE WITH FBC
 8.
  
 3.)INCLUDE A CODE SUMMARY ABOUT THE
 EXISTING BUILDING; (REVISE) BUILDING
 TYPE FBC6, BUILDING HEIGHT AND AREA
 FBC5, OCCUPANCY CLASSIFICATION FBC 3 AND
 AREA PER OCCUPANCY.OCCUPANCY
 CLASSIFICATION HAS BEEN DECLARED, A2,
 FOR THE RENOVATED SPACE, BUT PLEASE
 PROVIDE INFORMATION IN REGARDS TO THE
 REST OF THE BUILDING.
  
 4.)SHEET A1 STATES THAT THE BUILDING
 IS TYPE IV UNPROTECTED.SEE FBC 6, TYPE
 IV IS HEAVY TIMBER.TO MY KNOWLEDGE
 THIS IS NOT A HEAVY TIMBER BUILDING.
 PLEASE REVISE, AND INCLUDE A OR B.
  
 5.)PRODUCT APPROVALS TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC*106.3.3.
  
 6.)FIRE SPRINKLER PLANS REQUIRED,
 FBC*106.3.5.1.1(5), FS553.79(2).ALSO
 SEE ATTACHED LETTER FROM DCA.
  
 7.)A1, OCCUPANT LOAD IS TO BE NOT LESS
 THAN SPECIFIED IN FBC TABLE 1004.1.2,
 FBC 1004.1.2 (ROUND UP RATHER THAN ROUND
 DOWN).
  
 8.)THE PRODUCT APPROVAL FOR THE
 OVERHEAD DOOR REQUIRES IMPACT PROTECTION
 FOR THE OPTIONAL GLASS. REMOVABLE
 SHUTTERS NOT ALLOWED ABOVE THE FIRST
 FLOOR.SEE ATTACHED POLICY IN REGARDS
 TO IMPACT PROTECTION.PLEASE CONTACT ME
 TO DISCUSS AND PLEASE RESOLVE THIS ISSUE
 PRIOR TO RESUBMITTAL.
  
 9.)GUARDRAIL REQUIRED AT THE OVERHEAD
 DOOR, FBC1012.1.
  
 10.)GUARDRAIL DETAIL, 4-A3, AND
 HANDRAIL DETAIL, SHOW MINIMUM DISTANCE
 FROM THE EDGE OF SLAB.
  
 11.)VERTICAL ACCESSIBILITY REQUIRED,
 FBC11-4.1.6. IT IS NOT CLEAR IF THE
 ELEVATOR IS DESIGNED TO COMMUNICATE
 BETWEEN SUITE 201 AND SUITE 202, NOTE ON
 THE PLAN.
  
 12.)PROVIDE A DETAIL FOR THE EXISTING
 STAIR BETWEEN SUITE 201 AND SUITE 202.
 THE NOTE STATES TO REPAIR AS NECESSARY,
 PROVIDE A DETAIL.
  
 13.)THE STAIR IS TO COMPLY WITH
 FBC1009.PROVIDE A DETAIL FOR BOTH
 STAIRS BETWEEN SUITE 201 AND SUITE 202.
  
 14.)PROVIDE A DETAIL FOR THE STAIR
 RAILS.HANDRAILS REQUIRED ON BOTH SIDES
 OF THE STAIR, FBC1009.11.PROVIDE A
 DETAIL AND SHOW ALL HANDRAILS ON THE
 PLAN.SHOW COMPLIANCE WITH FBC1607.7.
 SEE ALSO FBC11-4.26.
  
 15.)THE NOTE STATES TO REPAIR/REPLACE
 METAL CLAD DOOR 90 MINUTE (STAIR BETWEEN
 SUITE 201 AND SUITE 202).A DOOR IS NOT
 SHOWN GRAPHICALLY, WHAT IS SHOWN THERE
 ON EACH SIDE OF THE WALL?
  
 16.)LANDINGS REQUIRED AT THE STAIRS,
 FBC1009.4 AND AT DOORS FBC1008.1.5.
 NONE IS SHOWN AT THE EXISTING STAIRS TO
 BE REPAIRED.DOOR LOCATION AND SWING IS
 NOT CLEAR FROM THE PLAN.
  
 17.)IT APPEARS THAT THERE WAS A WALL
 BETWEEN SUITE 201 AND SUITE 202, TENANT
 SEPARATION.A 2 HOUR EXIT ENCLOSURE IS
 SHOWN.THE PURPOSE OF THE 90 MINUTE
 DOOR IS NOT CLEAR; IS THIS ONE TENANT
 SPACE OR TWO?
  
 18.)CORRIDOR 110, SHOW ANY REQUIRED
 FIRE RATING FOR THIS WALL.20MIN DOORS
 ARE NOTED ON THE PLAN, DOORS C.NO FIRE
 RATING SHOWN FOR THE ELECTRICAL 108
 DOOR.THIS APPEARS TO BE AN EXIT
 CORRIDOR; IS THE STAIR SHOWN AN EXIT FOR
 ANOTHER TENANT SPACE?YOU ARE REMOVING
 A DOOR AND INCORPORATING A STORAGE AREA
 INTO THE STAIRWAY, CANNOT USE ANEXIT
 ENCLOSURE FOR ANY OTHER PURPOSE,
 FBC1019.
  
 19.)HOW MANY STORIES IS THIS BUILDING?
 A 1 HOUR CORRIDOR WALL IS SHOWN, NO
 OTHER RATING SHOWN FOR THE STAIRS
 ADJACENT TO ELECTRICAL 108.2 HOUR
 REQUIRED FOR FOUR STORIES OR MORE,
 FBC1019.
  
 20.)PROVIDE DIMENSIONS THE ELECTRICAL
 108 DOOR.IT APPEARS CODE COMPLIANT
 WHEN SCALED; SEE FBC1005.2 AND SHOW
 COMPLIANCE ON THE PLAN.
  
 21.)PROVIDE INFORMATION IN REGARDS TO
 EXIT DISCHARGE; NONE SHOWN ON THE PLAN.
  
  
 22.)THERE ARE FOUR ITEMS SHOWN
 GRAPHICALLY ON THE PLAN AS RECTANGLES
 WITH AN X.TWO APPEAR TO BE ELEVATORS
 (AS THEY ARE LOCATED IN THE ELEVATOR
 LOBBY); WHAT ARE OTHER TWO?
  
 23.)PROVIDE A DETAIL FOR SIGNAGE FOR
 THE ELEVATORS, FBC11-4.10.
  
 24.)A WALL IS BEING REMOVED; DOES THIS
 WALL SERVE AS A TENANT AND/OR OCCUPANCY
 SEPARATION?THERE IS ALSO A STAIR FROM
 SUITE 202 GOING DOWNSTAIRS.WHAT IS IN
 THE AREA BELOW?IS IT A PART OF THIS
 SPACE OR IS IT ANOTHER TENANT SPACE?
  
 25.)SEE FBC11-5.2 REGARDING COUNTERS
 EXCEEDING 34INCHES, SHOW ACCESSIBLE
 SEATING ON THE PLAN (BARS 1, 2, AND 3).
  
 26.)A RESPONSE LETTER WHEN
 RESUBMITTING WILL HELP EXPEDITE PLAN
 REVIEW.ALL CHANGES TO THE PLAN ARE TO
 BE CLOUDED.
  
 27.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 28.)PROVIDE WIND DESIGN CRITERIA,
 FBC1603.1.4.