| Date |
Text |
| 2006-11-28 19:57:37 | **** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED WHICH |
| | INDICATE MANUAL ON/OFF CONTROL CHOSEN FOR THE METHOD OF |
| | CONTROLLING LIGHTING. PLEASE CHOOSE AUTO OPTION. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE |
| | MISSING OVER RIDE DEVICES LOCATED IN ALL SPACES |
| | CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS. |
| | PLEASE SEE MISSING THE MAX TIMES PERMITTED FOR TYPE OF |
| | OVER RIDES WHICH ARE NOT SHOWN AT THIS TIME. (30 MINS |
| | MAX FOR OCCUPANT SENSOR TYPE DEVICES, 4HRS MAX FOR |
| | TIMER TYPE.) |
| | PLEASE SEE MISSING OVER RIDE CONTROLS AS THEY ARE |
| | REQUIRED AT THE LOCATIONS OF INGRESS/EGRESS SO THE |
| | OCCUPANT MAY BE ABLE TO CONTROL THE LIGHTS WHICH ARE IN |
| | SIGHT. |
| | PLEASE INDICATE DEVICES AND CORRELATE WITH THE SYMBOL |
| | LEGEND. |
| | PLEASE EXPLAIN NOTE NUMBER #6 ON DRAWING KEY NOTES AS |
| | IT MENTIONS RELAY FOR NOT BEING ABLE TO OPERATE SOME |
| | RECESSED LIGHTING AT THE SAME TIME WITH OTHERS?? |
| | |
| | 2) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4). |
| | PLEASE KNOW, ANY NEW FA DEVICES INSTALLED MUST MEET |
| | THESE MINIMUM LEVELS. THIS WAS NOT IN PREVIOUS REVIEW |
| | AS THIS WAS NOT IN THE SCOPE OF WORK OF ELECTRICAL |
| | REVIEW, HOWEVER IT NOW IS.THE PRIMARY ISSUE IS ITEM |
| | 11-4.28.3(4) WHICH REQUIRES A MIN OF 75 CANDELAS FOR |
| | ANY NEW STROBE DEVICES. |
| | PLEASE INDICATE ON LEGEND. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS, COMMENTS OR IF ANY PART OF |
| | NOTES ABOVE ARE NOT UNDERSTOOD OR TYPED IN A MANNER |
| | WHICH IS NOT CLEAR, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE OR REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |