| 2006-09-29 00:00:00 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE STATE THE FOLLOWING |
| | RELEVANT CODES (WHICH ARE ON PLANS) |
| | HOWEVER PLEASE GIVE YEAR EDITIONS |
| | CURRENTLY INEFFECT FOR THE DESIGN. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101. |
| | |
| | |
| | 2) NOTE: PLEASE EXPLAIN SERVICE |
| | SCENARIO, IT IS UNCLEAR AT THIS TIME. IT |
| | SEEMS LIGHTING ETC IS BEING NOTED AND |
| | SHOWNFROM A SERVICE WHICH ALSO |
| | FEEDS THE REST OF THE FLOOR?? |
| | IS THIS NOT A SEPARATE TENANT? PLANS |
| | INDICATE ADJACENT TENANT SPACES, HOWEVER |
| | MAY NOT HAVE A SERVICE WHICH FEEDS ONE |
| | TEANT FEED ANOTHER. PLEASE VERIFY AND |
| | SHOW THE LOCATION OF THE OTHER |
| | ELECTRICAL EQUIPMENT/SERVICE. NOT ABLE |
| | TO DETERMINE SOME ITEMS AT THIS TIME. |
| | 110.26,240.24,210.25 ETC. |
| | |
| | 3) NOTE: PLEASE SEE FBC CHAPTER 13 FOR |
| | NEW BUILD OUTS OF TENANT SPACES AND |
| | LIGHTING CONTROLS REQUIRED. |
| | 13-415.1.ABC.1.1,.1.2,.1.3. |
| | PLEASE SEE CALCULAITONS FOR 13-415.2, 13-415.2.ABC.1, |
| | TABLES 415.2.C.1, AND |
| | 415.2.B.1. |
| | DEPENDING ON WHAT WORK IS BEING DONE, IT |
| | SEEMS THESE REQUIREMENTS FOR LIGHTING |
| | CONTROLS ARE REQUIRED AND LPD'S ARE |
| | REQUIRED ALSO. |
| | |
| | 4) NOTE: PLEASE SEE A COUPLE OF OUTSIDE |
| | OFFICES IN TENANT SPACE WHICH DO NOT |
| | INDICATE ANY LIGHTING?? |
| | |
| | 5) NOTE: PLEASE SEE BLDG AND POSSIBLE |
| | FIRE REVIEW COMMENTS AS THE SEEMS TO |
| | SHOW AN EGRESS DOOR ON THE EXIT STAIR |
| | TOWERS WHICH OPENS IN. ?? IT IS KNOWN |
| | THAT THIS MAY NOT BE A PART OF THIS BLD |
| | OUT HOWEVER IF THIS IS SHOWN ON |
| | ARCHITECURAL AND MEP PLANS, DOOR SWING |
| | SHOULD BE VERIFIED. THIS WAS |
| | HIGH-LIGHTED ON PLANS. |
| | |
| | |
| | ** PLEASE SEE ANY COMMENTS WHICH MAY |
| | AFFECT THE ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |