| Plan Review Notes For Permit 06090324 |
| Permit Number |
06090324 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-01-23 15:52:04 | | | | | | | | | | | | | DENIED | | | | | | THE LOAD CALCULATION FOR THE PANEL SERVED BY THE | | | GENERATOR EXCEEDS THE GENERATOR OUTPUT. NONCOMPLIANT | | | WITH 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY | | | SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE | | | SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE | | | TIME. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH |
|