2007-01-23 15:52:04 
  
  
  
 DENIED
  
 THE LOAD CALCULATION FOR THE PANEL SERVED BY THE
 GENERATOR EXCEEDS THE GENERATOR OUTPUT. NONCOMPLIANT
 WITH 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY
 SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE
 TIME.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH