| Plan Review Notes For Permit 06090324 |
| Permit Number |
06090324 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-21 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE MANUFACTURERS | | | SPECIFICATIONS/RECOMMENDATION, REGARDING | | | CLEARANCES. | | | | | | 2} PROVIDE SPECIFICATIONS FOR THE | | | TRANSFER SWITCH. | | | | | | 3} PROVIDE A CALCULATION FOR THE LOAD | | | BEING SERVED BY THE GENERATOR. SEE | | | 700.15 LOADS ON EMERGENCY BRANCH | | | CIRCUITS. | | | | | | 4} INDICATE HOW THE TRANSFER SWITCH IS | | | FED FROM THE PANEL.THERE MUST BE A | | | MAIN IN THIS PANEL OR OCP IN THE MAIN | | | PANEL. | | | | | | 5} THE PLAN INDICATES A 25 KW GENERATOR | | | AND THE SPECS INDICATE A 20 KW, PLEASE | | | CORRELATE. | | | | | | 6} THE PERSON TAKING RESPONSIBILITY FOR | | | THE PLAN/DRAWINGS, SHALL PRINT AND SIGN | | | THEIR NAME ON THE SHEETS THEY DRAW. | | | PLEASE DO THIS PRIOR TO RESUBMITTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | |
|