Date Text
2006-09-21 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE MANUFACTURERS
 SPECIFICATIONS/RECOMMENDATION, REGARDING
 CLEARANCES.
  
 2} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 3} PROVIDE A CALCULATION FOR THE LOAD
 BEING SERVED BY THE GENERATOR. SEE
 700.15 LOADS ON EMERGENCY BRANCH
 CIRCUITS.
  
 4} INDICATE HOW THE TRANSFER SWITCH IS
 FED FROM THE PANEL.THERE MUST BE A
 MAIN IN THIS PANEL OR OCP IN THE MAIN
 PANEL.
  
 5} THE PLAN INDICATES A 25 KW GENERATOR
 AND THE SPECS INDICATE A 20 KW, PLEASE
 CORRELATE.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  