2006-10-03 00:00:00******DENIED******
 REFERENCE: FBC-2004 SEC. 424.2 OR
 FBRC-2004 SEC.4101 SWIMMING POOLS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1) FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1-1/2" PVC VENT PIPE, FROM WHERE
 IT STARTS TO WHERE IT ENDS UP, COMPLYING
 WITH THE THREE SECOND RELEASE. PLEASE
 REFERENCE THE ATTACHED EXAMPLE FOR
 RESUBMITTAL.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  