Plan Review Notes
Plan Review Notes For Permit 06090315
Permit Number 06090315
Review Stop P
Sequence Number 2
Notes
Date Text
2006-11-30 11:55:29UNSAT 2ND TIME
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE SANITARY RISER DIAGRAM ON SHEET A-1 DOES NOT
 REFLECT THE FLOOR PLAN. THE RESIDENCE IS A SINGLE STORY
 BUILDING BUT THE ISOMTRIC IS INDICATING A 3" SOIL STACK
 WHICH IS NOT NEEDED. PLEASE REFERENCE THE CORRECTED
 SANITARY RISER DIAGRAM IN RED INK OF THE PROPOSED NEW
 BATHROOM PLUMBING AND TIE IN TO THE EXISTING PLUMBING.
  
 2. THE WATER CLOSET INDICATED ON SHEET A-1 SANITARY
 RISER DIAGRAM IS SHOWN WITH A TRAP. PLEASE NOTE THAT A
 WATER CLOSET HAS AN INTREGRAL TRAP AND ONE IS NOT
 NEEDED TO BE INDICATED FOR ON THE DRAWING. PER FBC-2004
 PLUMBING, SECTION 1002.1 FIXTURES SHALL NOT BE DOUBLE
 TRAPPED.
  
 3. PLEASE NOTE THAT THE NEW SEWER CONNECTION IS
 INDICATED WRONG ON SHEET A-1 SITE PLAN. PLEASE CORRECT
 FOR THE RESUBMITTAL AND PLEASE LABEL THE PIPING AS IT
 IS LABELED IN RED INK ON THE CORRECTED DRAWING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721