| 2006-11-21 08:18:38 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1}BATHROOM BRANCH CIRCUITS. IN ADDITION TO THE NUMBER |
| | OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS |
| | SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY THE BATHROOM RECEPTACLE OUTLET(S). |
| | SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.INDICATE |
| | SAME ON PANEL SCHEDULE. THIS COMMENT WAS ON THE |
| | PREVIOUS REVIEW. SEE 210.11(C)(3). |
| | |
| | 2} THERE IS NO MENTION OF A NEW SERVICE ON THE |
| | APPLICATION, IF THE SERVICE IS TO BE UPGRADED PLEASE |
| | INDICATE SAME ON PLAN AND APPLICATION. |
| | |
| | 3} THE RISER DIAGRAM INDICATES A 200 AMP DISCONNECT, |
| | BUT IT DOES NOT FEED THE PANEL. THERE IS NO INDICATION |
| | OF THE PANEL BEING A MLO OR AS HAVING A MAIN BREAKER SO |
| | COMPLIANCE WITH 230.70(A)(1) CANNOT BE DETERMINED.IF |
| | THE SERVICE IS EXISTING PLEASE REMOVE THE RISER FROM |
| | THE PLAN, IF ONE IS BEING ADDED PLEASE PROVIDE A CODE |
| | COMPLIANT RISER. |
| | |
| | 4} THE PANEL SCHEDULE IS INCORRECT AND NOT REQUIRED FOR |
| | THIS ADDITION, THE WIRE SIZES AND LOADS ARE INCORRECT. |
| | INDICATE THE REQUIRED BATH CIRCUIT PER 210.11(C)(3), |
| | AND THE BEDROOM ARC FAULT PER 210.12 ON THE PLAN IN |
| | NOTE FORM AND REMOVE THE PANEL SCHEDULE.3 |
| | |
| | 5} THE LOAD CALCULATION DOES NOT COMPLY WITH 220 |
| | SECTION I, OR 220.31, AND IS NOT REQUIRED ON AN |
| | ADDITION OF 500 SQUARE FEET PER 215.5, PLEASE REMOVE OR |
| | COMPLY WITH THE REQUIREMENTS OF ARTICLE 220. |
| | |
| | 6} RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| | SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING SPACE |
| | MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE FLOOR |
| | LINE BY DOORWAYS, FIREPLACES, AND SIMILAR OPENINGS. |
| | 210.52(A)(2). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |