| Plan Review Notes For Permit 06090315 |
| Permit Number |
06090315 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-04 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR | | | THE DESIGN MUST PRINT AND SIGN THEIR | | | NAME TO SAME PER 106.3.4.2. | | | | | | 2} 210.11(C)(3) BATHROOM BRANCH | | | CIRCUITS. IN ADDITION TO THE NUMBER OF | | | BRANCH CIRCUITS REQUIRED BY OTHER PARTS | | | OF THIS SECTION, AT LEAST ONE 20-AMPERE | | | BRANCH CIRCUIT SHALL BE PROVIDED TO | | | SUPPLY THE BATHROOM RECEPTACLE | | | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO | | | OTHER OUTLETS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | |
|