Plan Review Notes
Plan Review Notes For Permit 06090315
Permit Number 06090315
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-04 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 2} 210.11(C)(3) BATHROOM BRANCH
 CIRCUITS. IN ADDITION TO THE NUMBER OF
 BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY THE BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO
 OTHER OUTLETS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  