| 2007-05-21 15:23:31 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK |
| | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 |
| | FAC. |
| | |
| | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 3} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14,RECEPTACLE PER 210.63. |
| | |
| | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.8(A)(6) GFI. |
| | |
| | 5} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). |
| | |
| | 6} INDICATE IF THE SERVISE SHOWN ON THE RISER IS |
| | RELOCATED (NEW) AND PART OF THIS APPLICATION OR IF |
| | EXISTING. |
| | |
| | 7} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| | TO THAT CODE. PLEASENOTE SAME ON PLAN. |
| | |
| | 8} NOTE #3 INCORRECTLY REFERENCES 210.72, ARTICLE 210 |
| | 70 SHOULD BE THE REFERENCE. |
| | |
| | 9} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 |
| | NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID |
| | CONFUSION IN THE FIELD. |
| | |