Plan Review Notes
Plan Review Notes For Permit 06090314
Permit Number 06090314
Review Stop B
Sequence Number 3
Notes
Date Text
2007-06-20 16:58:13DENIED BY BUILDING
  
 NOTE: THE ORIGINAL SCOPE OF WORK WAS CHANGED AND NEW
 DRAWINGS WERE SUBMITTED.
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. THE WORK IS REQUIRED TO BEGIN
 WITHIN 90 DAYS OF THE DATE THE NOC IS RECORDED OR IT
 WILL HAVE TO BE RE-RECORDED.
  
 2) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE
 SIGNED BY THE OWNER/AGENT.
  
 3) PROVIDE A DRAINAGE PLAN FOR THE LOT AS REQUIRED BY
 FBC R401.3. INDICATE HOW AND WHERE THE SURFACE WATER
 WILL BE DIRECTED TO AN APPROVED POINT OF COLLECTION.
  
 4) SPECIFY HOW THE ROOF VENTILATION AS REQUIRED BY FBC
 R806.1 WILL BE PROVIDED FOR THE FLAT ROOF ADDITION.
  
 5)SHOW COMPLIANCE WITH R903.4 FOR ROOF DRAINAGE.
 INDICATE THE LOCATIONS AND SIZES OF THE ROOF DRAINS OR
 SCUPPERS. PROVIDE CALCULATIONS FOR SCUPPER SIZING.
 SPECIFY SIZES AND LOCATIONS OF OVERFLOW SCUPPERS AS
 REQUIRED BY R903.4.1.
  
 6) SHOW COMPLIANCE WITH R320.7, WHICH REQUIRES ALL
 BUILDINGS WITH EAVES LESS THAN 6" TO HAVE GUTTERS WITH
 DOWNSPOUTS THAT DISCHARGE AT LEAST ONE FOOT FROM THE
 STRUCTURE.
  
 7) FBC R905.3.3.1 FOR LOW SLOPE ROOFS REQUIRES TWO
 LAYERS OF UNDERLAYMENT. SPECIFY TWO LAYERS OF
 UNDERLAYMENT FOR THE 3:12 AND 2.25:12 PITCH ROOF.
  
 8) PLEASE REVISE SCOPE OF WORK ON SHEET C1. THE SCOPE
 OF WORK WAS CHANGED TO ELIMINATE THE SECOND STORY.
  
 9) PLEASE REVISE THE UPLIFT INFORMATION ON C1. THERE IS
 NO LONGER AN UPPER AND LOWER ROOF. THERE IS A SLOPED
 ROOF AND A FLAT ROOF. PLEASE REVISE THE SPECIFIED
 UPLIFT PRESSURES TO COMPLY WITH FBC TABLE 1609.6.2.1(2)
 OR SUBMIT SIGNED AND SEALED CALCULATIONS INDICATING HOW
 THE PRESSURES WERE DETERMINED.
  
 10) THE LIST OF PRODUCT APPROVALS ON C1 SPECIFIES FLAT
 ROOF AND THIS SHOULD STATE FLAT ROOF COVERING MATERIAL
 OR BUR ROOF SYSTEM. PLEASE CORRECT. THE PRODUCT
 APPROVALS ARE REQUIRED TO BE SUBMITTED. THIS PRODUCT
 APPROVAL CONTAINS SEVERAL APPROVED ASSEMBLIES FOR
 INSULATED AND NON-INSULATED DECKS, AS WELL AS,
 DIFFERENT FASTENING OPTIONS AND DESIGN PRESSURES.
 THEREFORE, THE ASSEMBLY, FASTENING OPTION AND DESIGN
 PRESSURE ARE REQUIRED TO BE SPECIFIED. THIS CAN BE
 ACCOMPLISHED BY CIRCLING THE APPROPRIATE ITEMS ON THE
 NOA. ALSO NOTE THAT RAS 117 CALCULATIONS MAY BE
 REQUIRED FOR PERIMETER AND CORNER AREAS, ROOF ZONES 2
 AND 3 RESPECTIVELY. SEE LIMITATION NUMBER 7 OF THE
 NOA.
  
 11) THE PRODUCT INFORMATION ON C1 HAS BEEN REVISED AND
 UPDATED. PLEASE REMOVE IT OR CORRECT IT.
  
 12)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT 2 COPIES OF THE
 PRODUCT APPROVALS. THE FLORIDA COVERSHEET AND NOA OR
 OTHER EVALUATION IS REQUIRED. PRODUCT APPROVALS ARE
 REQUIRED FOR EXTERIOR DOORS AND WINDOWS, ROOF
 COVERINGS, STORM PANELS, TRUSS HANGERS, CONNECTORS AND
 STRAPS AND OTHER PRODUCTS LISTED BY RULE 9B-72.
  
 13)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 14)IF THE GLAZED OPENINGS ARE NOT IMPACT RESISTANT
 SUBMIT PRODUCT APPROVALS, KEY PLANS AND INSTALLATION
 SCHEDULES ( INCLUDE FASTENER TYPES, SPACING ,ETC.) FOR
 THE STORM PANELS.
  
 15)TWO SETS OF SIGNED AND SEALED PLANS, PRODUCT
 APPROVALS, ENERGY FORMS, ETC. OR REQUIRED.
  
 16) THE INFORMATION SUBMITTED FOR THE WINDOWS IS NOT
 ACCEPTABLE. IT IS INCOMPLETE AND HAS BEEN REVISED.
  
 17) PLEASE RESUBMIT THE PLAN SHEETS WITH THE COUNTY
 IMPACT FEE STAMPS OR HAVE THE NEW REVISED SHEETS
 STAMPED FOR IMPACT FEES.
  
 18) ONE SET OF THE OLD PLANS CAN BE RESUBMITTED FOR
 REFERENCE PURPOSES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  