Plan Review Notes
Plan Review Notes For Permit 06090314
Permit Number 06090314
Review Stop M
Sequence Number 2
Notes
Date Text
2006-12-13 13:31:36*** DENIED ***
 1)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 2) AS NOTED IN LAST REVIEW 9-28-06, THE ENERGY
 CALCULATIONS CAN NOT BE ON
 FORM 600C-04 AS THE ADDITION IS OVER 600
 SQ. FT. PER 2004 FBC 13-600.3.C . PLEASE SUBMIT FORM A
 OR B.
  
 3) AS NOTED IN LAST REVIEW 9-28-06, WHEN RE-DOING THE
 ENERGY CALCULATIONS
 THEY ALSO NEED TO BE SIGNED BY THE
 OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2
  
 4) AS NOTED IN LAST REVIEW 9-28-06, PLEASE SUBMIT
 MANUAL J CALCULATIONS
 FOR THE WHOLE HOUSE TO JUSTIFY THE NEED
 OF A 5 TON A/C SYSTEM, PER 2004 FBC
 13-607.1.ABC.1 .
  
 6) AS NOTED IN THE LAST REVIEW 9-28-06,SHOW ON THE
 MECHANICAL PLANS THE SIZE OF THE SUPPLY AIR TRUNK LINE
 ON THE FIRST FLOOR FROM THE AHU TO
 THE MIXING BOX.
  
 7) AS NOTED IN THE LAST REVIEW 9-28-06, SHOW ON THE
 MECHANICAL PLANS THE LOCATION OF THE CLOTHES
 DRYER VENT, SEE 2004 FBC/M 501.2 .
  
 8) SEE ATTACHED NOTICE FS 553.80(2)(B)
 REGARDING FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.