| Plan Review Notes For Permit 06090314 |
| Permit Number |
06090314 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-12-12 15:49:48 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SHOW THE PHYSICAL LOCATION OF ALL | | | SERVICE EQUIPMENT ON THE PLAN SO THAT | | | COMPLIANCE WITH 230.70(A)(1) CAN BE | | | REVIEWED. THERE ARE REFERENCES TO THE SERVICE BEING | | | MOVED, SHOW THAT LOCATION, AND THE LOCATION OF THE | | | RELOCATED PANEL. | | | | | | 2} THE RISER INDICATES TWO CONDUCTORS (WRONG SIZE @ | | | #30) TO THE PANEL.ALSO SEE 250.66 FOR THE CORRECT | | | GROUNDING ELECTRODE CONDUCTOR. | | | | | | PLEASE REMOVE OLD SHEETS, INSERT NEW | | | ONES, SUBMIT OLD SHEETS TO EXPEDITE | | | REVIEW AND SUBMIT WRITTEN RESPONSE TO | | | THE COMMENTS MADE IN THIS REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|