Plan Review Notes
Plan Review Notes For Permit 06090314
Permit Number 06090314
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-12 15:49:48 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SHOW THE PHYSICAL LOCATION OF ALL
 SERVICE EQUIPMENT ON THE PLAN SO THAT
 COMPLIANCE WITH 230.70(A)(1) CAN BE
 REVIEWED. THERE ARE REFERENCES TO THE SERVICE BEING
 MOVED, SHOW THAT LOCATION, AND THE LOCATION OF THE
 RELOCATED PANEL.
  
 2} THE RISER INDICATES TWO CONDUCTORS (WRONG SIZE @
 #30) TO THE PANEL.ALSO SEE 250.66 FOR THE CORRECT
 GROUNDING ELECTRODE CONDUCTOR.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718