| 2007-01-02 15:59:23 | TWO STORY ADDITION |
| | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3)THE ENERGY CALCULATION FORMS THAT WERE SUBMITTED |
| | CAN ONLY BE USED FOR ADDITIONS OF 600 SQFT OR LESS. |
| | THIS ADDITION IS 952 SQFT. |
| | SUBMIT THE CORRECT FORMS. SEE FBC 13-6. |
| | |
| | 4) PROVIDE A DRAINAGE PLAN FOR THE LOT AS REQUIRED BY |
| | FBC R401.3. THE SITE PLAN SUBMITTED DOES NOT ADEQUATELY |
| | INDICATE THE SURFACE WATER DRAINAGE REQUIREMENTS OF |
| | SECTION R401.3 OF THE 2004 FBC RESIDENTIAL CODE. |
| | |
| | 5) THE LIVE LOAD FOR BALCONIES SHOULD BE 60 PSF UNDER |
| | STRUCTURAL NOTES ON SHEET D1. SEE TABLE R 301.5. |
| | |
| | 6) SPECIFY THE REQUIRED ATTIC VENTILATION FOR THE |
| | SECOND FLOOR. SEE FBC R806.1. SPECIFY HOW THE ADDITIONS |
| | ATTIC WILL BE VENTED. |
| | |
| | 7) SHOW COMPLIANCE WITH FBC R320.7 WHICH REQUIRES ALL |
| | BUILDINGS WITH EAVES LESS THAN 6"TO HAVE GUTTERS AND |
| | DOWNSPOUTS THAT DISCHARGE 1 FOOT FROM THE STRUCTURE. |
| | |
| | 8) SPECIFY THE 2 LAYERS OF UNDERLAYMENT FOR THE 3:12 |
| | PITCH CEMENT TILE ROOF THAT IS REQUIRED BY FBC |
| | R905.3.3.1 FOR LOW SLOPE ROOFS. |
| | |
| | 9) PROVIDE A DETAIL FOR THE REQUIRED GUARD AT THE OPEN |
| | SIDES OF THE STAIRS, SHOWING COMPLIANCE WITH FBC |
| | R312.1, R312.2.2 AND TABLE R 301.5. |
| | |
| | 10) PROVIDE HANDRAIL DETAILS AT THE STAIRS SHOWING |
| | COMPLIANCE WITH FBC R311.5.6, 311.5.6.1 AND 311.5.6.3. |
| | |
| | 11) CITY OF WPB AMENDMENTS TO FBC 106.3.3 REQUIRES THE |
| | DESIGNER OF RECORD FOR THE PROJECT TO REVIEW AND |
| | APPROVE IN WRITING ALL OF THE PRODUCT APPROVALS. THE |
| | ENGINEER THAT SIGNED AND SEALED THE PLANS IS THE |
| | DESIGNER OF RECORD AND IS REQUIRED TO APPROVE THE |
| | PRODUCT APPROVALS. |
| | |
| | 12) SPECIFYON THE PRODUCT APPROVAL NOA FOR THE MONIER |
| | SPANISH "S" CONCRETE TILE, WHICH ONE OF THE METHODS OF |
| | ATTACHMENTS LISTED WILL BE USED TO INSTALL THE TILE. |
| | THE FASTENERS THAT WERE SPECIFIED ON THE NOA DO NOT |
| | MEET THE REQUIRED MOMENT OF RESISTANCE. |
| | |
| | 13) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES AND |
| | DESIGN PRESSURE LISTED IN THE NOA FOR THE GAF BUR |
| | SYSTEM WILL BE INSTALLED. THE APPROVED ASSEMBLY AND |
| | MAXIMUM DESIGN PRESSURE WAS NOT SPECIFIED. SEE PAGES |
| | 10-19 OF THE NOA. ENHANCED FASTENING MAY BE REQUIRED IN |
| | THE PERIMETER AND CORNER ZONES,SUBMIT THE RAS 117 |
| | CALCULATIONS (SEE LIMITATION NUMBER 7). |
| | |
| | 14) THE PRODUCT APPROVAL SUBMITTED FOR THE PGT SH-4000 |
| | WINDOWS IS NOT FOR IMPACT RESISTANT WINDOWS AS |
| | SPECIFIED ON THE PLANS. IT IS ALSO EXPIRED. |
| | |
| | 15) THE PRODUCT APPROVAL NOA FOR THE PGT HR710 IMPACT |
| | WINDOW IS EXPIRED. THE CURRENT ONE IS NOA 03-0612.06 |
| | FOR FL 242-R3. |
| | |
| | 16) SUBMIT PRODUCT APPROVALS FOR THE IMPACT RESISTANT |
| | FIXED GLASS WINDOW. |
| | |
| | 17) SUBMIT PRODUCT APPROVALS FOR THE IMPACT RESISTANT |
| | STRUCTURAL WINDOW MULLIONS. |
| | |
| | 18) IF THE NEW WINDOWS ARE NOT IMPACT RATED, THEN |
| | SPECIFY HOW THE GLAZED OPENINGS WILL BE PROTECTED FROM |
| | WINDBOURNE DEBRIS AS REQUIRED BY FBC R301.2.1.2. SUBMIT |
| | PRODUCT APPROVALS FOR STORM PANELS, WITH AN |
| | INSTALLATION SCHEDULE AND KEY PLAN. |
| | |
| | 19) PR0VIDE A DETAIL INDICATING HOW THE DECK WILL BE |
| | WATERPROOFED SO THAT WHEN DECKING IS NAILED THROUGH THE |
| | ROOF MEMBRANE IT WILL NOT LEAK. ALSO SPECIFY THE |
| | FLASHING BETWEEN THE DECK AND THE EXTERIORWALL. |
| | |
| | 20) FOUR SETS OF PLANS WERE SUBMITTED. TWO OF THE SETS |
| | DO NOT HAVE ALL SHEETS SIGNED AND SEALED. TWO COMPLETE |
| | SETS OF THE SIGNED AND SEALED DRAWINGS ARE REQUIRED. |
| | PLEASE REMOVE EXTRA PLANS TO AVOID CONFUSION. IF PLAN |
| | SHEETS ARE REVISED THEN YOU CAN SUBMIT ONE COPY OF THE |
| | OLD PLAN SHEETS FOR COMPARISON PURPOSES. HOWEVER, |
| | PLEASE MARK THE OLD SHEETS VOID OR OLD SHEETS. |
| | |
| | NOTE: MOST OF THE ABOVE COMMENTS ARE FROM THE FIRST |
| | REVIEW AND HAVE NOT BEEN ADDRESSED. IF YOU HAVE |
| | QUESTIONS PLEASE CALL. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |