Plan Review Notes
Plan Review Notes For Permit 06090314
Permit Number 06090314
Review Stop M
Sequence Number 1
Notes
Date Text
2006-09-28 00:00:00*** DENIED ***
 1) THE ENGINEER WHOSE NAME APPEARS ON
 THE TITLE BLOCK MUST SIGN, DATE, AND
 SEAL THE MECHANICAL PLANS, PER FAC
 61G15-23.002 .
  
 2) THE ENERGY CALCULATIONS CAN NOT BE ON
 FORM 600C-04 AS THE ADDITION IS OVER 600
 SQ. FT. PER 2004 FBC 13-600.3.C .
  
 3) WHEN RE-DOING THE ENERGY CALCULATIONS
 THEY ALSO NEED TO BE SIGNED BY THE
 OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2
  
 4) PLEASE SUBMITMANUAL J CALCULATIONS
 FOR THE WHOLE HOUSE TO JUSTIFY THE NEED
 OF A 5 TON A/C SYSTEM, PER 2004 FBC
 13-607.1.ABC.1 .
  
 5) PLEASE SUBMIT MANUAL D CALCULATIONS
 FOR RESIDENTIAL DUCT DESIGN, PER 2004
 FBC/R M1601.1 AND FBC 13-610.1.ABC.1 .
 AS 10" SUPPLY AIR DUCTS APPEAR OVER
 SIZED FOR THE ROOMS.
  
 6) SHOW THE SIZE OF THE SUPPLY AIR TRUNK
 LINE ON THE FIRST FLOOR FROM THE AHU TO
 THE MIXING BOX ON THE MECH. PLANS.
  
 7) SHOW THE LOCATION OF THE CLOTHES
 DRYER VENT ON THE MECH. PLANS, PLEASE
 NOTE CLOTHES DRYER VENT TERMINATION MUST
 BE A MIN. OF 4 FT. FROM A/C CONDENSER
 UNIT, PER 2004 FBC/M 501.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.