| 2006-09-28 00:00:00 | *** DENIED *** |
| | 1) THE ENGINEER WHOSE NAME APPEARS ON |
| | THE TITLE BLOCK MUST SIGN, DATE, AND |
| | SEAL THE MECHANICAL PLANS, PER FAC |
| | 61G15-23.002 . |
| | |
| | 2) THE ENERGY CALCULATIONS CAN NOT BE ON |
| | FORM 600C-04 AS THE ADDITION IS OVER 600 |
| | SQ. FT. PER 2004 FBC 13-600.3.C . |
| | |
| | 3) WHEN RE-DOING THE ENERGY CALCULATIONS |
| | THEY ALSO NEED TO BE SIGNED BY THE |
| | OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2 |
| | |
| | 4) PLEASE SUBMITMANUAL J CALCULATIONS |
| | FOR THE WHOLE HOUSE TO JUSTIFY THE NEED |
| | OF A 5 TON A/C SYSTEM, PER 2004 FBC |
| | 13-607.1.ABC.1 . |
| | |
| | 5) PLEASE SUBMIT MANUAL D CALCULATIONS |
| | FOR RESIDENTIAL DUCT DESIGN, PER 2004 |
| | FBC/R M1601.1 AND FBC 13-610.1.ABC.1 . |
| | AS 10" SUPPLY AIR DUCTS APPEAR OVER |
| | SIZED FOR THE ROOMS. |
| | |
| | 6) SHOW THE SIZE OF THE SUPPLY AIR TRUNK |
| | LINE ON THE FIRST FLOOR FROM THE AHU TO |
| | THE MIXING BOX ON THE MECH. PLANS. |
| | |
| | 7) SHOW THE LOCATION OF THE CLOTHES |
| | DRYER VENT ON THE MECH. PLANS, PLEASE |
| | NOTE CLOTHES DRYER VENT TERMINATION MUST |
| | BE A MIN. OF 4 FT. FROM A/C CONDENSER |
| | UNIT, PER 2004 FBC/M 501.2 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |