2006-09-26 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SHOW THE PHYSICAL LOCATION OF ALL
 SERVICE EQUIPMENT ON THE PLAN SO THAT
 COMPLIANCE WITH 230.70(A)(1) CAN BE
 REVIEWED.
  
 2} THE EQUIPMENT GROUND RAN FROM THE
 METER TO THE PANEL IS IN VIOLATION OF
 250.6. NOTE THAT THE GROUNDING ELECTRODE
 SYSTEM IS ESTABLISHED AT THE FIRST MEANS
 OF DISCONNECT, ALL EQUIPMENT GROUNDS
 SHALL BE RAN FROM THAT POINT.
  
 3} PROVIDE LOAD CALCULATIONS PER ARTICLE
 220.31 OR STANDARD CALCULATION IF
 REDUCING THE NEUTRAL SIZE.
  
 4} THE RANGE(CIRCUIT #11/13)OVERCURRENT
 SIZE IS TOO LARGE FOR THE CONDUCTOR (#8)
 PER 310.16, AND FOR THE 8KW LOAD.
  
 5} PLEASE SEE THE EXISTING BUILDING CODE
 REQUIRES A SMOKE DETECTOR IN THE
 EXISTING BEDROOM UNDER LEVEL 2
 ALTERATIONS, ARTICLE 604.4.3. THAT
 DETECTOR MUST BE INTERCONNECTED PER
 R313.1.1, IF THE EXEPTIION PROVISION
 EXISTS.
  
 6} THE ENGINEER WHOSE NAME APPEARS ON
 THE TITLE BLOCK MUST SIGN, DATE AND SEAL
 THE DOCUMENT. 61G15-23.002 FAC.
  
 NOTE: THERE ARE NUMEROUS INSTANCES IN
 THE PANEL SCHEDULE INDICATING #12
 CONDUCTORS ON 15 AMP BREAKERS. WHILE
 THIS IS NOT A CODE VIOLATION, IF IT IS
 INDICATED ON THE PLAN IT MUST ACTUALLY
 BE INSTALLED THAT WAY OR THE PLANS
 REVISED TO INDICATE ACTUAL CONDITIONS.
 PLEASE VERIFY.
  
 ONLY TWO SETS OF PLANS ARE REQUIRED FOR
 REVIEW, FOUR WERE SUBMITTED.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  