Plan Review Notes
Plan Review Notes For Permit 06090295
Permit Number 06090295
Review Stop M
Sequence Number 7
Notes
Date Text
2007-09-04 15:51:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) REVISED ENERGY CALCULATIONS LINE 15 IS TAKING A
 CREDIT FOR CEILING FANS, REVISED ELECTRICAL PLANS ON
 FILE SHOW NO CEILING FANS TO BE INSTALLED. PER 2004 FBC
 13-607.2.A.3.1.CEILING FAN CREDIT MAY BE TAKEN IF ONE
 OR MORE CEILING FANS ARE INSTALLED IN EACH OF THE
 BEDROOMS AND A MINIMUM OF ONE CEILING FAN IS INSTALLED
 IN ALL PRIMARY LIVING AREAS (LIVING ROOMS, FAMILY
 ROOMS, OR GREAT ROOMS). PRESCRIPTIVE REQUIREMENTS IN
 SECTION 13-607.1.A.1 SHALL BE MET. PLEASE REVISE
 ELECTRICAL PLANS TO SHOW CEILING FANS (NOT JUST
 JUNCTION BOX) AND SUBMIT WITH THIS REVISION OR CORRECT
 ENERGY CALCULATIONS.
  
 2)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  