 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 2} LABEL THE PANELS.
  
 3} LOCATE PANELS ON THE PLAN. PROVIDE A SITE PLAN IF
 NECESSARY. MORE PANELS ARE ADDED AND NO RECORD OF THEIR
 LOCATIONS. 106.1.3 FBC.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  