| Plan Review Notes For Permit 06090295 |
| Permit Number |
06090295 |
|
| Review Stop |
E |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2007-05-30 16:18:08 | | | | | | | | | | REVISION DENIED/INCOMPLETE INFORMATION | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | | FS, RESPECTIVELY. | | | | | | 2} LABEL THE PANELS. | | | | | | 3} LOCATE PANELS ON THE PLAN. PROVIDE A SITE PLAN IF | | | NECESSARY. MORE PANELS ARE ADDED AND NO RECORD OF THEIR | | | LOCATIONS. 106.1.3 FBC. | | | | | | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|