Plan Review Notes
Plan Review Notes For Permit 06090295
Permit Number 06090295
Review Stop M
Sequence Number 6
Notes
Date Text
2007-08-10 11:25:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** REVISION DENIED ***
 1) PLEASE SHOW CLOTHES DRYER VENTS ON PLAN AND STATE
 WERE THEY WILL DISCHARGE, SEE 2004 FBC/R M1501.1.
  
 2) SHOW BATHROOM EXHAUST FANS ON PLAN, SEE 2004 FBC/R
 R303.3.
  
 3) SHOW LOCATION OF A/C CONDENSER UNITS ON PLAN.
  
 4) SHOW ATTIC ACCESS ON PLANS FOR NEW AND RELOCATED AIR
 HANDLERS, SEE 2004 FBC/R M1305.1.3 REFERENCING 6 FT..
  
 5) ENERGY CALCULATIONS ON FILE STATE AIR HANDLER IN
 GARAGE, AS THE AIR HANDLER IS NOW BEING INSTALLED IN
 THE ATTIC THE ENERGY CALCULATIONS NEED TO BE REVISED.
 PLEASE SUBMIT REVISED ENERGY CALCULATIONS, SEE 2004 FBC
 13-103.1.2.
  
 6) BUILDING PLANS ON FILE SHOW A DOOR BETWEEN THE FRONT
 ENTRANCE AND THE KITCHEN, IF SO WHEN THE DOOR IS CLOSED
 THE 30X14 RETURN AIR GRILL COULD NOT RETURN AIR BACK TO
 THE AIR HANDLER, SEE 2004 FBC/R M1602.4. SEE YELLOW
 HIGH LIGHT AND NOTE ON PLAN FOR LOCATION. IF THEIR IS A
 DOOR RELOCATE GRILL, IF NO DOOR STATE SO ON PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].
  