| 2007-08-10 11:25:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | | | *** REVISION DENIED *** | | | 1) PLEASE SHOW CLOTHES DRYER VENTS ON PLAN AND STATE | | | WERE THEY WILL DISCHARGE, SEE 2004 FBC/R M1501.1. | | | | | | 2) SHOW BATHROOM EXHAUST FANS ON PLAN, SEE 2004 FBC/R | | | R303.3. | | | | | | 3) SHOW LOCATION OF A/C CONDENSER UNITS ON PLAN. | | | | | | 4) SHOW ATTIC ACCESS ON PLANS FOR NEW AND RELOCATED AIR | | | HANDLERS, SEE 2004 FBC/R M1305.1.3 REFERENCING 6 FT.. | | | | | | 5) ENERGY CALCULATIONS ON FILE STATE AIR HANDLER IN | | | GARAGE, AS THE AIR HANDLER IS NOW BEING INSTALLED IN | | | THE ATTIC THE ENERGY CALCULATIONS NEED TO BE REVISED. | | | PLEASE SUBMIT REVISED ENERGY CALCULATIONS, SEE 2004 FBC | | | 13-103.1.2. | | | | | | 6) BUILDING PLANS ON FILE SHOW A DOOR BETWEEN THE FRONT | | | ENTRANCE AND THE KITCHEN, IF SO WHEN THE DOOR IS CLOSED | | | THE 30X14 RETURN AIR GRILL COULD NOT RETURN AIR BACK TO | | | THE AIR HANDLER, SEE 2004 FBC/R M1602.4. SEE YELLOW | | | HIGH LIGHT AND NOTE ON PLAN FOR LOCATION. IF THEIR IS A | | | DOOR RELOCATE GRILL, IF NO DOOR STATE SO ON PLAN. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL: [email protected]. | | | |
|