| Plan Review Notes For Permit 06090295 |
| Permit Number |
06090295 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-12-08 07:10:20 | | | | PROVISO | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ANY | | | ELECTRICAL INSPECTIONS. | | | | | | 1} THE SERVICE IS LOCATED REMOTE FROM THE RESIDENCE ON | | | SHEET A-1, THEREFORE A DISCONNECTING MEANS PER 225.31, | | | LOCATED PER 250.32 AND GROUNDED PER 250.32 IS REQUIRED | | | AT THE RESIDENSE. THE PANEL(S) INDICATED AS MLO ON THE | | | RISER DO NOT MEET THESE REQUIREMENTS. PLEASE CORRECT, | | | AND RESUBMIT FOR REVIEW. | | | | | | THE REVIEWED PLAN MUST BE ON THE JOB | | | SITE AT TIME OF INSPECTION. ALLOW AT | | | LEAST ONE WEEK (PER TRADE) FOR PLAN | | | REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|