Notes
Date Text
2006-12-08 07:10:20 
 PROVISO
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ANY
 ELECTRICAL INSPECTIONS.
  
 1} THE SERVICE IS LOCATED REMOTE FROM THE RESIDENCE ON
 SHEET A-1, THEREFORE A DISCONNECTING MEANS PER 225.31,
 LOCATED PER 250.32 AND GROUNDED PER 250.32 IS REQUIRED
 AT THE RESIDENSE. THE PANEL(S) INDICATED AS MLO ON THE
 RISER DO NOT MEET THESE REQUIREMENTS. PLEASE CORRECT,
 AND RESUBMIT FOR REVIEW.
  