| Plan Review Notes For Permit 06090295 |
| Permit Number |
06090295 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-12-08 16:38:33 | BUILDING REVIEW PROVISO: | | | 1- PROVIDE UPDATED NOA FOR PRECAST LINTELS. NOA | | | 03-0605.05 EXPIRED IN 05/21/06.. | | | 2- AS PER PHONE CONVERSATION WITH JOHN ANDERSEN, | | | PROVIDE COMPLETE INFORMATION FOR FLAT ROOF SYSTEM UNDER | | | A SEPARATE PERMIT AND FEES. SEE ATTACHED COPY OF CITY | | | POLICY FOR ROOFING PERMITS FOR REQUIRED INFORMATION. | | | | | | 3- PROVIDE COMPLETE TRUSS PACKAGE FOR REVIEW PRIOR | | | TO INSTALLATION. DESIGNER OF RECORD TO REVIEW AND | | | APPROVE IT PRIOR TO SUBMITTAL. SEE SEC. R802.10 FOR ALL | | | INFORMATION REQUIRED TO BE IN THE TRUSS PACKAGE. TWO | | | COPIES REQUIRED. | | | 4- WIND LOAD CHART: DESIGN PRESSURES FOR FLAT ROOF | | | AREAS ARE LOW IN COMPARISON WITH ASCE 7-02 AND TABLE | | | 1609.6B FBC 2004. PROVIDE ACTUAL CALCULATIONS TO VERIFY | | | COMPLIANCE WITH SEC. 1609 FBC 2004. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. |
|