2006-11-14 11:36:04 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE SERVICE IS LOPCATED REMOTE FROM THE RESIDENCE ON
 SHEET A-1, THEREFORE A DISCONNECTING MEANS PER 225.31,
 LOCATED PER 250.32 AND GROUNDED PER 250.32 IS REQUIRED
 AT THE RESIDENSE. THE PANEL(S) INDICATED AS MLO ON THE
 RISER DO NOT MEET THESE REQUIREMENTS. PLEASE CORRECT.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR SIZE PER 250.66 IS
 NOT INDICATED ON THE RISER. ALSO THE REFERENCE TO A #5
 DRIVEN GROUND ROD IS INCORRECT.
  
 3} THE KITCHEN COUNTERRECEPTACLES, INCLUDING THE
 ISLAND, MUST BE GFI PROTECTEDPER 210.8(A)(7), INDICATE
 THE SAME ON THE DRAWINGS.
  
 4} A RECEPTACLE IS REQUIRED FOR SERVICING THE
 CONDENSING UNITS PER 210.63. PLACE ON PLAN.
  
 5} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE. THIS IS THE
 SECOND TIME THIS COMMENT HAS BEEN MADE. PLEASE ADDRESS,
 LOCATE ON THE PLAN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.