| Plan Review Notes For Permit 06090295 |
| Permit Number |
06090295 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-14 11:36:04 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE SERVICE IS LOPCATED REMOTE FROM THE RESIDENCE ON | | | SHEET A-1, THEREFORE A DISCONNECTING MEANS PER 225.31, | | | LOCATED PER 250.32 AND GROUNDED PER 250.32 IS REQUIRED | | | AT THE RESIDENSE. THE PANEL(S) INDICATED AS MLO ON THE | | | RISER DO NOT MEET THESE REQUIREMENTS. PLEASE CORRECT. | | | | | | 2} THE GROUNDING ELECTRODE CONDUCTOR SIZE PER 250.66 IS | | | NOT INDICATED ON THE RISER. ALSO THE REFERENCE TO A #5 | | | DRIVEN GROUND ROD IS INCORRECT. | | | | | | 3} THE KITCHEN COUNTERRECEPTACLES, INCLUDING THE | | | ISLAND, MUST BE GFI PROTECTEDPER 210.8(A)(7), INDICATE | | | THE SAME ON THE DRAWINGS. | | | | | | 4} A RECEPTACLE IS REQUIRED FOR SERVICING THE | | | CONDENSING UNITS PER 210.63. PLACE ON PLAN. | | | | | | 5} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH | | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. THIS IS THE | | | SECOND TIME THIS COMMENT HAS BEEN MADE. PLEASE ADDRESS, | | | LOCATE ON THE PLAN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|