Plan Review Notes
Plan Review Notes For Permit 06090295
Permit Number 06090295
Review Stop B
Sequence Number 2
Notes
Date Text
2006-11-27 15:16:02BUILDING REVIEW 2ND CHECKLIST:
  
 1- PAY IMPACT FEES TO PALM BEACH COUNTY. BRING BACK
 STAMPED PLANS AND PAID RECEIPT.
  
 2- SOIL TEST REPORT:
 A) BOTH COPIES TO HAVE ORIGINAL ENGINEER'S SIGNATURE
 (NO COPIES) AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES.
  
 B) NEED THE ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) FRENCH DOOR. DADE COUNTY NOA #01-0417.04
 SUBMITTEDEXPIRED ON 11-22-06.
  
 B) PRECAST LINTELS. NO INFORMATION SUBMITTED.
  
 C) ROOF TILE. NO INFORMATION SUBMITTED.
  
 D) FLAT ROOF SYSTEMS. SEE PLANS. NO INFORMATION
 SUBMITTED.
 ***NOTE: NEED TO IDENTIFY SPECIFIC APPROVED ASSEMBLIES.
 CHECK SYSTEM LIMITATIONS BECAUSE GENERAL LIMITATION #9
 MAY NOT BE USED IN THIS AREA. IF SYSTEM IS LIMITED BY
 GENERAL LIMITATION #7, THEN PROVIDE REQUIRED
 INFORMATION. SEE LAST PAGE OF NOA TO CHECK GENERAL
 LIMITATIONS.
  
 E) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON
 PLANS.
  
 F) WINDOWS WERE REVISED FROM CASEMENT WINDOWS TO
 SINGLE HUNG WINDOWS.ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGES WERE SUBMITTED. NEED TO PROVIDE COMPLETE
 WINDOW DRAWINGS PACKAGE ALSO.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOSIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5-DETAIL A/A3 DOESN'T COMPLY WITH SEC. R311.5.3.2
 2004 FLORIDA RESIDENTIAL CODE. 7" RISERS AND 12" DON'T
 COMPLY WITH THE 24 TO 25 RISER TREAD RATIO. REVISE AS
 REQUIRED.
  
 6- SHEET A-4:CLARIFY WHY TREAD DIMENSIONS ON STAIRS
 BY BREAKFAST AREAARE DIFFERENT FROM TREAD DIMENSIONS
 ON OTHER STAIRS. ALSO, COORDINATE DIMENSIONS WITH
 DETAIL A/A3 REVISION.
  
 7- SHEET A-5:
 A) WIND LOAD SCHEDULE CHART IS INCOMPLETE. IT
 DOESN'T SPECIFY THE WIND LOAD FOR THIS AREA AND THE
 EXPOSURE TYPE AS REQUIRED BY SEC. R301 2004 RESIDENTIAL
 CODE.ALSO, MISSING THE DESIGN PRESSURES FOR FLAT
 ROOF. SEE TABLE 1609.6B FBC 2004.
  
 B) ROOF SHEATHING NAILING SCHEDULE DOESN'T MATCH
 INFORMATION GIVEN ON SHEET A-8 WALL SECTION "A". REVISE
 AS REQUIRED.
  
 8- PROVIDE COMPLETE DETAILS AND SPECS FOR RAILING,
 INCLUDING FASTENING TO ROOF SYSTEM AS REQUIRED BY SEC.
 1607.7.1 FBC 2004 AND SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004.
 INFORMATION NO PROVIDED.
  
 10- WALL SECTION "A" ON SHEET A-8 DOENS'T SHOW OR
 SPECIFY ATTIC VENTILATION. PROVIDE INFORMATION AS
 REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712