2006-10-04 00:00:00DENIED;
 1.AUTOMATIC CLOTHES WASHER BRANCH DRAIN
 TO BE 3". FBC-2004 PLUMBING SECTION
 406.3. A CLEANOUT IS REQUIRED AT 48"
 ABOVE FINISH FLOOR.
 2.KITCHEN SINK TO DISCHARGE DOWN STREAM
 OF THE BATHROOM GROUP. SEC 909.1
 3.ONLY 3 FIXTURE UNITS PERMITED ON 1
 1/2" PIPE. TABLE 710.1(1).
 PLUMBING PLAN REVIEW BY;